PMU test

3
00:00:20,895 --> 00:00:29,607
The function of the PMUR device is to record phasor, frequency and rate of frequency changes

4
00:00:29,897 --> 00:00:39,200
The measurement error of each of these values  is defined by TVE، FE and RFE respectively as follows:

5
00:00:39,387 --> 00:00:48,497
In the above, X and  X ̂  represent the real value of the phase and the value estimated by the PMU

6
00:00:48,521 --> 00:00:56,708
the i and r indices represent the imaginary and real parts of the phase X respectively.

7
00:00:57,833 --> 00:01:07,911
The test device is required to record the theoretical value of the injected signal for all time tags along with its signal-to-noise ratio (SNR).

8
00:01:08,466 --> 00:01:19,021
The PMU sends the measured data to the test machine using C37.118 protocol.

9
00:01:19,622 --> 00:01:31,724
The test device compares the theoretical and measured values of phase، frequency and ROCOF for specific time tags determined by the rate of data

10
00:01:31,748 --> 00:01:38,646
transmission and compute TVE , FE  and RFE values

11
00:01:39,779 --> 00:01:51,443
A phase measurement unit (PMU) is a device used to estimate the amount and phase angle of an electric phase value

12
00:01:51,997 --> 00:01:57,833
in an electrical grid using a common time source for synchronization.

13
00:01:58,771 --> 00:02:09,419
Time synchronization is usually provided by GPS or IEEE 1588 Precision Time protocol

14
00:02:09,443 --> 00:02:16,279
 which allows simultaneous measurement of multiple remote points on the network.

15
00:02:16,881 --> 00:02:30,341
which consists of an angle measurement and a large measurement

16
00:02:30,365 --> 00:02:45,139
These synchronous measurements are important because if the supply and demand of the network are not fully matched

17
00:02:45,163 --> 00:02:53,005
frequency imbalances can cause stress on the grid, which is a potential cause of power outages.

18
00:02:53,489 --> 00:03:03,950
PMUs can also be used to measure frequencies on the power grid. A typical commercial one can report measurements with very high temporal resolution

19
00:03:04,106 --> 00:03:07,880
up to 120 measurements per second.

20
00:03:08,021 --> 00:03:22,763
This helps engineers analyze the dynamic events in the network that are not feasible with traditional SCADA measurements that create a measurement every 2 or 4 seconds.

21
00:03:23,997 --> 00:03:38,591
Consequently, PMUs equip installations with advanced monitoring and control capabilities and are considered to be one of the most important measurement devices in the future of power systems.

22
00:03:39,622 --> 00:03:49,544
The PMU can be a dedicated device, or the PMU function can be incorporated into a protective relay or other device.

23
00:03:50,442 --> 00:03:54,911
To perform PMU test on the start screen of the software

24
00:03:54,935 --> 00:04:08,700
click on the Phasor measurement unit (PMU) room, and in the opened page, 4 tests are designed in 4 tabs called Steady State, Modulation, Frequency ramp, Step.

25
00:04:10,082 --> 00:04:26,724
In the Steady State tab, you can see different modes. For example، in Fault Type Vl1، Mode adds two points with harmonic characteristics of 2، 40% and 70% and 0.2 seconds

26
00:04:27,044 --> 00:04:33,380
adds two points with harmonic characteristics of 2، 40% and 70% and 0.2 seconds and after testing and comparing the nominal and measured values، the test will pass or fail.

27
00:04:33,724 --> 00:04:39,966
The Modulation tab consists of two tests of amplitude modulation and phase.

28
00:04:39,990 --> 00:04:52,482
According to the standard, either amplitude modulation or phase modulation is applied. The signal model in modulation is considered as follows:

29
00:04:53,685 --> 00:05:03,505
For this test, the first points of interest are added, for example, a point with the specifications of F0=500Hz

30
00:05:03,919 --> 00:05:19,060
amplitude 100%, Kx=0.1, Fa=100Hz, Ka=0.9 and SNR=40db,

31
00:05:19,396 --> 00:05:30,068
and after performing the test and getting feedback from PMU and comparing the nominal and measured values, the test will pass or fail.

32
00:05:30,209 --> 00:05:42,341
The other two tests will be passed or fail after adding the points and running the test and getting feedback from the PMU and comparing the measured and rated values.
