00:00:18,765 --> 00:00:23,123
Directional overcurrent protection test in AMR relay (simple test using templates)

2
00:00:23,156 --> 00:00:28,476
AMR modular relay of Vebko company supports various protection functions.

3
00:00:28,508 --> 00:00:32,687
Explanations of the capabilities and software environment of this relay

4
00:00:32,680 --> 00:00:37,085
have already been presented in the video related to differential protection test.

5
00:00:37,117 --> 00:00:40,017
After connecting to the AMR relay at first,

6
00:00:40,185 --> 00:00:47,801
simply load the device's hardware configuration from the Device menu by selecting the Read Hardware from Relay option.

7
00:00:47,800 --> 00:00:53,820
The default password is 123456 in order to receive elements.

8
00:00:53,991 --> 00:00:58,695
At this point, a message is given to remove the signal, which if confirmed,

9
00:00:58,800 --> 00:01:02,320
if the current hardware is not the same as the relay hardware,

10
00:01:02,359 --> 00:01:08,398
the current hardware signals used in the VFC section are deleted.

11
00:01:08,423 --> 00:01:16,148
It should be noted that the settings for the conversion ratio of voltage and current transformers are determined in the related card.

12
00:01:16,200 --> 00:01:21,257
Here the ratio of current card conversion is 200A to 1A.

13
00:01:21,240 --> 00:01:24,406
As mentioned earlier in the AMR software,

14
00:01:24,531 --> 00:01:31,351
configuring some of the most widely used functions as examples are placed in the software and the user can send

15
00:01:31,359 --> 00:01:38,531
new settings to the relay by selecting each of them and applying the desired changes.

16
00:01:39,406 --> 00:01:46,126
For this purpose, a set of functions can be seen in the Relay VFC tab and in the Temp Functions section.

17
00:01:46,201 --> 00:01:52,820
It should be noted that by selecting each Temp Function, the blocks in the VFC are removed.

18
00:01:52,845 --> 00:01:58,523
Here the directional overcurrent function displayed with the name OC 67 is selected.

19
00:01:58,560 --> 00:02:05,726
In Configuring, this function uses an OC Inverse block and two OC Definite blocks that have

20
00:02:05,751 --> 00:02:09,539
different settings and the signals of a current card are assigned to their input (from a measuring point).

21
00:02:09,566 --> 00:02:17,702
Finally, output signals are assigned to Binary Outputs and relay LEDs by Output and LED blocks.

22
00:02:24,297 --> 00:02:31,085
To change the settings, simply right-click on each block to access a set of options.

23
00:02:31,421 --> 00:02:35,007
Finally, the changes are sent to the relay.

24
00:02:35,320 --> 00:02:42,390
In this video, by double-clicking on blocks that contain constant time stages for the directional overcurrent function,

25
00:02:42,400 --> 00:02:51,789
disables them and define the 1A and TMS current settings equal to 0.1 by double-clicking on the first stage,

26
00:02:51,844 --> 00:02:56,843
which is defined as reverse time. By double-clicking on the Direction block,

27
00:02:56,880 --> 00:03:03,546
the elements related to the directional function include rotation angle and ground polarization.

28
00:03:03,602 --> 00:03:10,000
After this, the changes will be sent to the relay by selecting send config and setting to relay option.

29
00:03:10,089 --> 00:03:15,414
In the next step, by running AMPro software and opening the AMT Overcurrent room,

30
00:03:15,445 --> 00:03:22,523
it is enough to go to the Object Parameters test section and create the test characteristic after entering the information.

31
00:03:22,548 --> 00:03:28,367
Keep in mind that it is also possible to test this function using the Xrio file.

32
00:03:28,695 --> 00:03:33,140
Here, the current setting value is equal to 1 amp, TMS is 0.1.

33
00:03:33,160 --> 00:03:40,328
In the overcurrent test, it is required to set two parameters maximum torque angle and sector operation.

34
00:03:40,353 --> 00:03:44,585
To do this from the Overcurrent window and the Relay Parameters tab,

35
00:03:44,610 --> 00:03:50,726
the directional option is selected and from the Element tab, the Directional section is placed on forward.

36
00:03:51,109 --> 00:04:05,531
Then enter under the Define Element Directional Behavior tab and the maximum torque angle and Sector operation parameters are equal to -45 and 172 degrees, respectively.

37
00:04:05,563 --> 00:04:09,070
In directional overcurrent relays, In order to better performance of relay,

38
00:04:09,120 --> 00:04:16,234
in orientation and reaching the MTA value ,the rotation of the reference voltage angle is used.

39
00:04:16,273 --> 00:04:25,835
The performance area or forward area in this relay is set from -131 degrees to +41 degrees.

40
00:04:25,890 --> 00:04:30,757
In order to investigate the directional overcurrent function, in addition to the time of operation and current,

41
00:04:30,781 --> 00:04:33,710
the angle of performance should also be investigated.

42
00:04:33,735 --> 00:04:39,390
For this purpose, performance time tests are performed along with amplitude and phase tests.

43
00:04:39,415 --> 00:04:45,726
In the time test, the accuracy of the performance time is investigated and in the amplitude and phase test,

44
00:04:45,720 --> 00:04:56,414
the detection and evaluation of the accuracy of the actual current and the actual angle of the performance threshold and reset threshold are considered.

45
00:04:56,438 --> 00:05:03,976
Cross Polarized method is used in AMR Vebko relay, i.e. using healthy phases to detect fault direction.

46
00:05:04,016 --> 00:05:12,976
For example, in case of faults in phase A, the relay uses VBC reference voltage and IA current to detect the fault current direction.

47
00:05:13,023 --> 00:05:22,500
The Forward or Reverse area means the part where the relay must detect the fault will be determined by the start angle and end angle.

48
00:05:22,555 --> 00:05:23,459
Time Test

49
00:05:23,484 --> 00:05:26,820
In order to test the DOC function, three states are considered.

50
00:05:26,845 --> 00:05:35,213
The first state for 500 milliseconds, normal conditions this means that it will inject a nominal voltage with zero current.

51
00:05:35,238 --> 00:05:46,726
In the second state, the fault conditions are applied and the current is selected for all phases of L1E-L2E-L3E in the range of 2 to 4 times the nominal current.

52
00:05:46,750 --> 00:05:51,289
The duration of this state should be greater than the nominal time of the relay trip.

53
00:05:51,314 --> 00:05:57,804
The third state will also be activated as post-Fault with zero voltage and current for 500 milliseconds.

54
00:05:57,840 --> 00:06:04,484
In order to see better performance of the function, from the View menu, the Detail View window opens.

55
00:06:04,523 --> 00:06:10,781
After adding double points and four times the regulatory current at the best possible angle

56
00:06:10,800 --> 00:06:18,281
in terms of performance of the function i.e. -45 degrees for the L1E-L2E-L3E falt types,

57
00:06:18,306 --> 00:06:21,328
a point in the No Trip area (here at an angle of 135 degrees) is tested.

58
00:06:21,353 --> 00:06:23,734
Due to the nature of the two-phase fault,

59
00:06:23,759 --> 00:06:36,000
the currents in this fault will have a phase difference of 180 degrees so that the 3I0 current is not created and the 67N function is not activated.

60
00:07:01,734 --> 00:07:03,334
Pickup-Drop off Test

61
00:07:03,359 --> 00:07:05,340
In order to perform the Pickup-Drop off test,

62
00:07:05,365 --> 00:07:11,662
you can also use a relay or LED contact and even a setting change to instantaneous the function.

63
00:07:11,687 --> 00:07:17,531
For this purpose, three states are needed for example in the first state, the normal network conditions,

64
00:07:17,556 --> 00:07:23,015
applied, in the second state the pickup test and in the third state the drop-off test is performed.

65
00:07:23,040 --> 00:07:29,500
In the second state, for pickup and drop-off test of angle, the current value will be twice the regulatory current.

66
00:07:29,525 --> 00:07:36,093
these states are performed in the Overcurrent room automatically by entering the settings by the user.

67
00:07:36,322 --> 00:07:44,179
The performance range of overcurrent curves in the AMR relay starts from 1.1 regulatory current in the relay.

68
00:07:44,383 --> 00:07:51,703
Therefore, first, by enabling the Active Range Limits option in the Overcurrent Protection Parameters window,

69
00:07:51,734 --> 00:07:57,523
the Imin value is set to 1.1 Iref. In the next step,

70
00:07:57,555 --> 00:08:03,452
the current adjustment value for the pickup test of the current value is placed on 1.1*1=1.1 amps.

71
00:08:03,484 --> 00:08:11,421
This test is performed at the best possible angle in terms of relay performance i.e. -45 degrees.

72
00:08:11,400 --> 00:08:16,250
After the current pick up-drop off, it is time to Pick up-drop off on the angle.

73
00:08:16,275 --> 00:08:21,140
For this purpose, as mentioned above, the current value is applied twice as much as the regulatory current,

74
00:08:21,120 --> 00:08:26,432
and once the trend is performed for the upper limit of the angle, i.e. 41 degrees,

75
00:08:26,457 --> 00:08:31,601
and once for the lower limit of the angle, i.e. -131 degrees.

76
00:08:31,600 --> 00:08:39,789
By adding the necessary tests and performing, you can finally add favorites items to the report.
