﻿1
00:00:19,994 --> 00:00:24,692
Negative sequence overcurrent protection test in AMR relay (simple test using templates)

2
00:00:24,839 --> 00:00:30,470
AMR modular relay of Vebko company supports various protection functions.

3
00:00:30,478 --> 00:00:35,565
Explanations of the capabilities and software environment of this relay have alread

4
00:00:35,577 --> 00:00:39,319
been presented in the video related to differential protection test.

5
00:00:39,332 --> 00:00:43,040
After connecting to the AMR relay at first,

6
00:00:43,043 --> 00:00:50,393
simply load the device's hardware configuration from the Device menu by selecting the Read Hardware from Relay option.

7
00:00:50,425 --> 00:00:57,276
The default password is 123456 to receive elements.

8
00:00:57,336 --> 00:01:01,876
At this point, a message is given to remove the signal, which if confirmed,

9
00:01:01,883 --> 00:01:05,550
if the current hardware is not the same as the relay hardware,

10
00:01:05,575 --> 00:01:10,892
the current hardware signals used in the VFC section are deleted.

11
00:01:12,460 --> 00:01:16,845
It should be noted that the settings for the conversion ratio of voltage and current

12
00:01:16,870 --> 00:01:20,006
transformers are determined in the related card.

13
00:01:20,738 --> 00:01:30,655
Here, current card conversion ratio is 200A to 1A and voltage card conversion ratio is 63,000 to 100V.

14
00:01:30,716 --> 00:01:36,597
(First, enter the VFC page): As mentioned earlier in the AMR software,

15
00:01:37,185 --> 00:01:42,817
configuring some of the most widely used functions are placed in the software as samples

16
00:01:42,929 --> 00:01:49,585
the user can send new settings to the relay by selecting each of them and applying the desired changes.

17
00:01:51,247 --> 00:01:58,893
For this purpose, a set of functions can be seen in the Relay VFC tab and in the Temp Functions section.

18
00:01:59,873 --> 00:02:05,958
It should be noted that by selecting each Temp Function, the blocks in the VFC are removed.

19
00:02:06,998 --> 00:02:14,215
Here the negative sequence overcurrent function displayed with the name NS 46 is selected.

20
00:02:14,349 --> 00:02:24,168
In this template, first, the signals of a current card are given to the Current Quantities block to create different current sequences in its output.

21
00:02:24,322 --> 00:02:28,135
In the default config of the Negative Sequence function,

22
00:02:28,160 --> 00:02:35,210
a block with different stages and signals of a current card with negative sequence is assigned to its input.

23
00:02:37,373 --> 00:02:46,288
Finally, output signals are assigned to Binary Outputs and relay LEDs by Output and LED blocks.

24
00:02:46,895 --> 00:02:52,968
To change the settings, simply right-click on each block to access a set of options.

25
00:02:53,762 --> 00:03:00,162
By double-clicking on the Negative Sequence block, the settings for its various stages are visible.

26
00:03:00,537 --> 00:03:07,126
Here, the first stage with normal Inverse setting characteristic has a current of 0.1 amps,

27
00:03:07,151 --> 00:03:21,125
the TMS equals 1, and the two constant time stages with a current setting of 0.2 and 0.5A have a time setting of 1.5 and 0.5 seconds, respectively.

28
00:03:21,432 --> 00:03:28,378
By making these changes, simply select Send Config and Setting to Relay from the Device menu again.

29
00:03:28,538 --> 00:03:34,389
This way, the settings and applied configuration are moved to the relay. (Cut from this part until the overcurrent room opens).

30
00:03:34,588 --> 00:03:40,665
In the next step, by running AMPro software and opening the AMT Overcurrent room,

31
00:03:40,699 --> 00:03:47,743
it is enough to go to the Test Object Parameters section and create the test characteristic after entering the information.

32
00:03:47,830 --> 00:03:53,248
The test characteristic is created in the Elements tab in the Negative Sequence section.

33
00:03:53,435 --> 00:03:58,043
Therefore, the default characteristic in this section is removed first.

34
00:03:58,289 --> 00:04:06,595
First, a reverse time characteristic is created with a current setting of 0.1 amps and TMS=1.

35
00:04:07,357 --> 00:04:13,355
The next characteristic is created by current setting of 0.2 and a time of 1.5 seconds.

36
00:04:13,409 --> 00:04:20,967
Finally, the third characteristic is created by adjusting the current setting of 0.5 and the time of 0.5 seconds.

37
00:04:21,154 --> 00:04:26,338
Keep in mind that it is also possible to test this function using the Xrio file.

38
00:04:26,594 --> 00:04:30,850
In order to evaluate the performance of negative sequence overcurrent function,

39
00:04:30,890 --> 00:04:34,410
two Trip Time and Pickup-Drop Off tests are performed.

40
00:04:34,496 --> 00:04:40,025
The purpose of Trip Time is to detect and evaluate the accuracy of the performance

41
00:04:40,079 --> 00:04:47,690
time of this function and the purpose of pickup-drop off test is to detect and evaluate the accuracy

42
00:04:47,715 --> 00:04:52,150
of the actual current of the performance threshold and the reset threshold of this function.

43
00:04:52,226 --> 00:04:53,226
Trip Test

44
00:04:53,379 --> 00:04:59,922
To perform this test three states ones including PreFault, Fault and PostFault are required.

45
00:05:00,202 --> 00:05:07,727
PreFault time is suitable for 500 milliseconds, fault time should be greater than the maximum trip time,

46
00:05:07,800 --> 00:05:11,607
and Post Fault time is at least 500 milliseconds.

47
00:05:11,681 --> 00:05:17,188
PostFault time should be increased if the drop-off is not instantaneous.

48
00:05:17,755 --> 00:05:22,348
The suggested points for reduced time functions are 1.5 times,

49
00:05:22,355 --> 00:05:32,308
2 times and 4 times the regulatory current, and for constant time curves, 1.5 and 2 times the regulatory current.

50
00:05:32,335 --> 00:05:36,793
These points are added to the fault type 12 to prepare the test.

51
00:05:36,919 --> 00:05:42,467
Keep in mind that due to the existence of three different characteristic, in some cases,

52
00:05:42,487 --> 00:05:48,402
the added points with the mentioned coefficients fall on the other characteristic.

53
00:05:48,516 --> 00:05:56,607
In these cases, other points are manually added on each characteristicto ensure accurate time performance.

54
00:05:56,828 --> 00:06:00,735
To detect the regulatory current of the second and third units,

55
00:06:00,748 --> 00:06:11,018
two points can be added to 90 and 110 percent of the regulatory current of these units in order to perform a kind of pickup drop-off test for these characteristics.

56
00:06:11,185 --> 00:06:18,812
Once again, the Max Fault Time value is set based on the highest number inserted in the t nom section.

57
00:06:18,962 --> 00:06:26,902
By adding points, perform the test to check the performance of this function from the point of view of time accuracy.

58
00:06:53,268 --> 00:06:55,262
Pickup/Drop-off Test

59
00:06:56,510 --> 00:07:03,312
In order to perform this test, it is first to determine how the diagnosis of pickup and drop-off is performed.

60
00:07:03,445 --> 00:07:07,767
This process can be done through a separate contact, like Start,

61
00:07:07,802 --> 00:07:15,529
Relay LED viewing, or changing the setting for the instantaneous of the function and using the trip contact.

62
00:07:17,255 --> 00:07:20,628
Here we used the relay pickup contact.

63
00:07:20,829 --> 00:07:25,399
You can also put the current fault value in the desired range.

64
00:07:26,066 --> 00:07:30,630
Here the fault value is considered 5% by default.

65
00:07:30,704 --> 00:07:38,982
The performance range of overcurrent curves in the AMR relay starts from 1.1 regulatory current in the relay.

66
00:07:39,135 --> 00:07:45,215
Therefore, first, by enabling the Active Range Limits option in the Overcurrent Protection Parameters window,

67
00:07:45,240 --> 00:07:51,249
Imin value are determined to be 1.1*0.1=0.11 Iref. In the next step,

68
00:07:51,283 --> 00:07:56,685
the current adjustment value for the pickup is placed on 0.1*1.1=0.11 amps.

69
00:07:56,792 --> 00:08:05,016
By adding this point, it is enough to perform the test and add the necessary elements to the report when it is finished.
