Synchronizer function test in Siprotec siemens 7SD82 relay

2
00:00:25,953 --> 00:00:33,382
In AMT Synchronizer, we're going to test the synchronous check function in Siemens' 7SD82 relay.

3
00:00:33,530 --> 00:00:41,585
This function can be used to synchronize the line and busbar, two busbars with coupling or a generator and busbar.

4
00:00:42,093 --> 00:00:46,109
This function, which is located in circuit breaker function group,

5
00:00:46,134 --> 00:00:51,132
can be used in different modes such as checking the synchronous of two systems,

6
00:00:51,157 --> 00:00:58,289
switching synchronous power systems, switching asynchronous power systems and switching the busbar/ line outage.

7
00:00:58,696 --> 00:01:03,648
For this purpose, different stages can be used in the form of synchronous check Stage

8
00:01:04,282 --> 00:01:08,406
(with two stages) or Synchronous/Asynchronous Stage (with six stages).

9
00:01:08,431 --> 00:01:12,648
This function uses two voltages to check the connecting conditions.

10
00:01:12,782 --> 00:01:20,006
The reference voltage of the first side which is called V1 and the reference voltage of the second side which is V2.

11
00:01:20,031 --> 00:01:25,446
Choosing voltages to synchronize depends on the system connection on the primary side.

12
00:01:25,694 --> 00:01:32,813
In this test, a 4-input voltage connection is used, which includes a single-phase voltage and a three-phase combination.

13
00:01:32,838 --> 00:01:38,493
In this case, the voltage attached to the single-phase Measuring Point is the decisive reference.

14
00:01:38,518 --> 00:01:45,758
The measured values related to this performance are displayed on the relay as primary, secondary and percentage.

15
00:01:45,783 --> 00:01:54,063
When the function is activated, the values of Delta V, Delta F and Delta Alpha are checked to connect the synchronous of the two systems.

16
00:01:54,088 --> 00:01:56,971
The settings on the relay are as follows:

17
00:01:56,996 --> 00:02:01,688
If we want to differentiate between synchronous and asynchronous conditions,

18
00:02:01,960 --> 00:02:09,249
we should use synchronous/Asynchronous stage, whose voltage-frequency diagram is as follows:

19
00:02:09,274 --> 00:02:14,079
By opening the AMT Synchronizer room to enter the relay information for testing,

20
00:02:14,104 --> 00:02:18,524
the first task is to enter the relay nominal information in "Device".

21
00:02:18,549 --> 00:02:24,063
In this section, related settings for CT and VT conversion ratio are entered.

22
00:02:24,088 --> 00:02:31,554
Keep in mind that if there is a different VT conversion ratio between the two systems, should be using a virtual VT,

23
00:02:31,579 --> 00:02:37,585
according to the manual relay recipe, used a coefficient to match the conversion ratio.

24
00:02:37,610 --> 00:02:39,742
In the Hardware Configuration section,

25
00:02:39,767 --> 00:02:49,290
5 Input binaries are defined by default to transfer relay outputs to the test device to adjust the voltage and frequency and issue the connecting command.

26
00:02:49,315 --> 00:02:55,327
Considering that in this test, alarms about voltage and frequency values are read from the relay

27
00:02:55,352 --> 00:03:00,774
, we only configure the binary related to the issuance of the command connected by the relay.

28
00:03:00,799 --> 00:03:06,094
Next, in the Synchronizing Parameters window the relay settings are entered.

29
00:03:06,119 --> 00:03:14,836
By specifying the phase sequence, connected voltages, breaker connection settings, and secondary voltage in the Protection Device tab,

30
00:03:14,861 --> 00:03:17,845
it is time to reach the Synchronizing Window tab.

31
00:03:17,870 --> 00:03:23,977
In this section, the minimum and maximum values for voltage and frequency parameters are entered,

32
00:03:24,002 --> 00:03:30,961
followed by the allowed tolerances for the Phi, V and f parameters.

33
00:03:30,986 --> 00:03:38,571
Keep in mind that for this relay, Dead Zone is not defined as an area where no output is exported from the relay.

34
00:03:38,596 --> 00:03:43,047
When the settings are confirmed, it is time to take the test.

35
00:03:43,072 --> 00:03:48,352
In this section, system settings 1 and 2 can be seen in the relevant tables.

36
00:03:48,377 --> 00:03:53,680
In addition to the possibility of manually entering specifications for two systems,

37
00:03:53,705 --> 00:03:59,750
it is possible to monitor the delta value of voltage, frequency and angle elements.

38
00:03:59,775 --> 00:04:05,196
In the next step, simply add points to the attribute and run the test.

39
00:04:05,221 --> 00:04:12,993
It is also possible to create points on either side of the characteristic boundary line using the Quick Test option.

40
00:04:16,087 --> 00:04:23,961
With the completion of the test, the selected items and elements can be viewed in the Report View window.
