﻿1
00:00:18,945 --> 00:00:24,468
Drawing the MHO characteristic in GEC PYTC relay

2
00:00:24,672 --> 00:00:30,578
For example, we consider the PYTC relay to manually draw the distance characteristic.

3
00:00:30,664 --> 00:00:38,398
PYTC is actually a model of the PYTS relay used to protect systems including underground cables,

4
00:00:38,437 --> 00:00:42,843
as well as systems consisting of cable and airlines combination.

5
00:00:42,868 --> 00:00:49,718
The Mho characteristic in this relay makes the Distance function available to protect these systems.

6
00:00:49,750 --> 00:00:56,046
The modules on this relay allow adjusting the protection zones based on different parameters.

7
00:00:56,071 --> 00:01:00,843
assume the different element settings of the modules in this relay as follows:

8
00:01:00,867 --> 00:01:08,468
In this case, considering the angle of the line is equal to 66 degrees, we add three Mho zones.

9
00:01:08,492 --> 00:01:16,031
The first zone features a forward with a reach of 5.1 ohms and an angle of 66 degrees.

10
00:01:16,055 --> 00:01:23,257
The second zone haves a forward characteristic of 7.65 ohms reach and an angle of 66 degrees,

11
00:01:23,273 --> 00:01:28,882
and finally the third zone 16.78 ohms reach with the same angle.

12
00:01:28,882 --> 00:01:34,023
After this, you can also manually enter the trip time for each zone.
