﻿1
00:00:19,117 --> 00:00:27,617
Drawing the distance characteristics and Practical example of drawing the Quad characteristic in SIEMENS 7SA522 relay

2
00:00:27,642 --> 00:00:34,226
Protection relays with Distance function are used to protect lines against faults in the network.

3
00:00:34,904 --> 00:00:39,023
In order to test this function, we must first draw its characteristic.

4
00:00:39,415 --> 00:00:45,580
Using Rio or Xrio is a simple solution to transfer settings and configure this function from relay

5
00:00:45,605 --> 00:00:49,840
and simulation of the distance characteristic in the test device.

6
00:00:49,865 --> 00:00:58,085
Using digital relays such as Import Rio and Xrio to draw protection characteristic will surely simplify the process

7
00:00:58,110 --> 00:01:01,250
of testing functions, including Distance.

8
00:01:03,134 --> 00:01:08,789
However, in the case of older relays such as static samples, in some cases,

9
00:01:08,814 --> 00:01:14,406
we still have to use step-by-step drawing and manual impedance characteristic.

10
00:01:15,035 --> 00:01:21,929
In addition, in some cases, we may not be able to get relay output in the form of files such as Xrio,

11
00:01:21,954 --> 00:01:26,500
CSV and Text for reasons such as software restrictions.

12
00:01:26,754 --> 00:01:31,531
In these cases, it is enough to open the Distance block from the Test Object Parameters

13
00:01:31,556 --> 00:01:36,406
section and use the Zone Settings header to draw the distance characteristic.

14
00:01:36,431 --> 00:01:44,585
At the top of the table, the New, Edit, Delete and Add duplicate options allow creating new zones,

15
00:01:45,103 --> 00:01:50,843
editing zones, deleting zones, and overwriting the zone, respectively.

16
00:01:52,003 --> 00:01:57,828
You can also have complete management over each zone using navigation options.

17
00:01:58,164 --> 00:02:02,279
In zone Details, you can also see details about trip time,

18
00:02:02,304 --> 00:02:08,101
impedance and values related to the duration of the operation and see the tolerance value.

19
00:02:08,484 --> 00:02:13,084
To get started, simply click on the New option to create a new zone.

20
00:02:13,672 --> 00:02:19,453
By default, this zone is marked as the tripe area for all fault loops.

21
00:02:20,219 --> 00:02:23,593
By selecting each zone and clicking on edit option,

22
00:02:23,625 --> 00:02:29,945
you can have a complete management of the type of distance element or specify the Trip and No Trip area.

23
00:02:29,969 --> 00:02:36,757
Impedance characteristics can be adjusted in the form of Quad and Mho type or lens in the relay.

24
00:02:36,805 --> 00:02:40,679
You can also use the default shapes for these three characteristics.

25
00:02:40,734 --> 00:02:43,976
Any added element can be a line or arc.

26
00:02:44,648 --> 00:02:48,484
Each element can be drawn by entering a point and angle.

27
00:02:48,648 --> 00:02:50,896
In the case of the Mho characteristic,

28
00:02:50,928 --> 00:02:55,928
the circle drawing is performed using the central point, radius and angle.

29
00:02:55,982 --> 00:03:03,516
After adding zones using different elements, you can specify the number, label, zone type and loop fault for it.

30
00:03:05,873 --> 00:03:11,505
Keep in mind that four different type can be specified for zones as follows:

31
00:03:12,615 --> 00:03:19,466
Tripping: It is used for zones that based on the relay settings, points inside trips.

32
00:03:19,818 --> 00:03:25,615
Starting: Used for zones that only lead to pickup of distance function.

33
00:03:25,717 --> 00:03:29,183
This pickup can lead to tripe after a certain time.

34
00:03:31,670 --> 00:03:36,450
Extended: This zone is only activated under certain conditions (for example enabling recloser or teleprotection schemes)

35
00:03:36,467 --> 00:03:41,607
Non-Tripping: In these zones, the relay will not issue trip command.

36
00:03:41,779 --> 00:03:45,979
It is also possible to disable the zones created in this list.

37
00:03:46,068 --> 00:03:51,052
After drawing the zones, trip time and related faults can be entered for each zone.

38
00:03:51,287 --> 00:03:57,020
Drawing the distance characteristic (zone 1 forward direction) in siemens 7SA522 relay

39
00:03:57,076 --> 00:04:03,676
For example, we will review drawing the Quad characteristic of a Siemens 7SA522 relay sample here.

40
00:04:03,873 --> 00:04:10,615
Keep in mind that by going to the Setting Group section in Digsi 4 software and choosing Distance Protection and then,

41
00:04:10,602 --> 00:04:16,529
General Settings you can view the distance characteristic of the relay by selecting the Graph option.

42
00:04:16,568 --> 00:04:18,568
In the Distance Zones section,

43
00:04:18,607 --> 00:04:24,560
you can see the values related to different parameters of the Distance characteristic in different zones.

44
00:04:24,585 --> 00:04:33,419
Here, zones 1 to 3 in forward direction, zone 4 in reverse direction and finally zone 5, is non-directional.

45
00:04:33,498 --> 00:04:38,388
Considering the overall characteristic of distance for this relay, which is as follows,

46
00:04:38,459 --> 00:04:42,818
as well as the directional characteristic in page R and X,

47
00:04:42,872 --> 00:04:46,396
it is necessary to pay attention to the following points:

48
00:04:46,498 --> 00:04:54,138
In general, six independent zones and one extra control zone are defined for each impedance fault loop in this relay.

49
00:04:54,201 --> 00:05:00,669
The process of defining lines is based on the parameters R, X and φDist.

50
00:05:01,365 --> 00:05:06,115
It is possible to include a cut area to define Load Encroachment.

51
00:05:06,209 --> 00:05:12,950
Reach element R value can be defined separately for phase-to-phase and phase-to-ground

52
00:05:12,952 --> 00:05:18,646
faults so that we can see wider coverage of faults for ground faults.

53
00:05:19,185 --> 00:05:28,466
For zone 1, another angle α can also be defined to avoid overreach caused by changing angles or more.

54
00:05:28,545 --> 00:05:31,545
This angle is not applicable to other zones.

55
00:05:32,146 --> 00:05:38,919
φDist, defined in the relay address 1211 and referred to as Distance Angle or Distance angle,

56
00:05:38,952 --> 00:05:42,146
shows the rotation angle in the Distance component.

57
00:05:42,217 --> 00:05:50,217
This element is used for both Quad and MHO characteristics and can be adjusted to the same value as the line angle (element 1105).

58
00:05:51,013 --> 00:05:55,005
Now it's time to drawing the distance characteristic.

59
00:05:55,076 --> 00:06:02,325
By revisiting the Zone Settings section and clicking on the New option, we select the Quad characteristic for the relay.

60
00:06:02,365 --> 00:06:11,825
Here, the value R moves the center of the line over the horizontal axis and the X value moves the center of the line over the vertical axis.

61
00:06:11,873 --> 00:06:16,349
The specified angle is also cause the line to rotate.

62
00:06:16,474 --> 00:06:24,708
The first line, while passing through the R axis with the value R1, that is, the resistance of zone 1 passes.

63
00:06:24,724 --> 00:06:31,255
has a φDist angle, which here is equal to the load angle of 82 degrees.

64
00:06:31,280 --> 00:06:40,794
In this way, we enter the value R equal to 24.899, X value equal to 0 and the angle value is 82 degrees.

65
00:06:40,865 --> 00:06:51,943
The second line is the horizontal line (taking alpha equal to zero degrees) with the specifications R=0, the value X is 6.211 and the angle is 180 degrees

66
00:06:52,232 --> 00:07:03,849
The third line that passes through the source is also draw by the specifications R=0, X=0 and the angle derived from the manual, that is 300 degrees.

67
00:07:03,928 --> 00:07:09,552
The fourth line that passes through the source has a 22-degree angle in according to the manual.

68
00:07:09,748 --> 00:07:18,333
For this purpose, we enter the value R=0, X=0 and the angle at 338 degrees.

69
00:07:18,358 --> 00:07:28,755
The fifth line is draw by considering the value R equal to zero, X equal to -6.211 and the angle equal to zero.

70
00:07:29,185 --> 00:07:33,519
By entering the above coordinates, zone 1 is created as Forward.

71
00:07:33,678 --> 00:07:39,318
Creating characteristics for reverse and non-directional zones also follows this process.

72
00:07:39,412 --> 00:07:41,419
By drawing the distance characteristic,

73
00:07:41,443 --> 00:07:48,474
it is possible to start the Shot Test and Search Test process in order to ensure the accuracy of the graphical characteristic.
