	Under Over Voltage Test Room

2
00:00:22,595 --> 00:00:28,343
On the start page of the software, by clicking on "Under Over Voltage Test“ from „Special Test“ subcategory,

3
00:00:28,368 --> 00:00:33,664
enter the environment related to testing numbers 27 and 59 voltage functions.

4
00:00:33,689 --> 00:00:39,578
This room is designed to simplify testing the mentioned functions and create various states automatically.

5
00:00:39,603 --> 00:00:44,460
„Under Over Voltage Test“ room is composed of six main windows of „Instrument Test“,

6
00:00:44,485 --> 00:00:47,632
„Detail View“, „Signal View“, „Table View“,

7
00:00:47,657 --> 00:00:52,210
Report“ and „Measurement View“ and for a better analysis and examination,

8
00:00:52,235 --> 00:00:57,141
it is possible to add other windows such as „Vector View“ from the menu at the top.

9
00:00:57,734 --> 00:01:03,148
To begin, different information such as relay type, serial number, station name,

10
00:01:03,173 --> 00:01:10,845
feeder/be number and the name of the device manufacturer must be entered in „Test Object“ section.

11
00:01:10,870 --> 00:01:15,804
The date of performing the test in AD, the information of the performer of the test and the

12
00:01:15,829 --> 00:01:23,882
information of the supervisor of the test are entered in „Date“, „Tested by“ and „Approved by“ fields, respectively.

13
00:01:23,907 --> 00:01:26,734
This information will be used in the final report.

14
00:01:26,759 --> 00:01:32,921
In ‚Test Settings“ section, the intended function is selected from among „OV“ and „UV“ in „Function Type“ field.

15
00:01:32,946 --> 00:01:43,046
Also, the secondary nominal voltage and the operation mode are selected from among OR and AND in „Vnom sec“ and „Operation mode“ fields,  respectively.

16
00:01:43,071 --> 00:01:46,562
If the mentioned functions need a current value to operate,

17
00:01:46,587 --> 00:01:48,640
such as „Minimum Current“ element,

18
00:01:48,665 --> 00:01:56,054
it is possible to check „Enable Current“ option and select the necessary current value.

19
00:01:57,070 --> 00:02:03,757
If the intended connection of the user is open delta connection, they can check “Open Delta” option.

20
00:02:03,782 --> 00:02:14,429
Every time „Insert Row“ is pressed in „Data Table“ a row is created in accordance with the number of voltage stages entered in the relay to enter the information of every Stage.

21
00:02:14,454 --> 00:02:24,171
In the created row, the stage number is entered in „Stage No“ and in „V setting“ section, the amount of the voltage setting for the mentioned functions is entered.

22
00:02:24,196 --> 00:02:32,532
In „Voltage Type“ section, the voltage calculation algorithm is specified which can be in form of phase to earth or phase to phase.

23
00:02:32,557 --> 00:02:36,492
Also, the time settings are entered in „Time Setting“ section.

24
00:02:36,525 --> 00:02:41,289
„Reset Ratio“ is the reference considered for measuring the amount of reset voltage,

25
00:02:41,314 --> 00:02:51,125
„Tol.Time“ is the amount of the accepted time error in form of percent and „Tol.Voltage“ determines the amount of the accepted voltage error in the result of the test.

26
00:02:51,150 --> 00:02:56,984
The settings related to „States“, „Binaries“, Pickup“ and „Dropoff“ are entered in „Testing“ tab.

27
00:02:57,009 --> 00:03:04,571
Also, it is possible to specify the voltage change condition from among „Continuous Ramp“ and „Step Ramp“ in „State Type“ section.

28
00:03:04,596 --> 00:03:17,390
In „State Pickup/Drop Out Termination“ section, the condition for ending the pickup and dropoff is selected in form of a separate contact such as C2 or pressing Space key )at the same time as the LED turns on( or the Trip contact.

29
00:03:17,415 --> 00:03:22,843
The conditions for recording the Trip is specified in „State Trip Termination“ section.

30
00:03:22,868 --> 00:03:30,273
Also, it is possible to consider a different binary input for recording pickup-dropoff or trip in „Hardware Configuration“ section.

31
00:03:30,306 --> 00:03:38,953
By pressing „Add Row“ key in „Test Plan“ section, new rows are added for the test in accordance with the stages created in „Test Object“.

32
00:03:38,978 --> 00:03:44,937
If „Continous Ramp“ option is checked in „State Type“ section, the settings are as follows:

33
00:03:44,985 --> 00:03:51,225
In „Stage No“ section, it is possible to specify the stage number of the function operation.

34
00:03:51,250 --> 00:03:57,185
In „Fault Type“ section, the fault type for every phase or a combination of phases is selected.

35
00:03:57,210 --> 00:04:04,959
In „Time Test“ section, it is specified that whether the user wishes the voltage function operation time to be estimated or not.

36
00:04:04,984 --> 00:04:10,943
In „Vtest“ section, the voltage in which the relay operation time is going to be examined is entered.

37
00:04:10,968 --> 00:04:19,000
In „PU Test“ and „T DOU“ sections it is specified that whether the user wishes to perform these two tests or not.

38
00:04:19,025 --> 00:04:29,226
In „PU Val. Assess“ section, the evaluated value from the pickup voltage is entered and in „PU Start“ section, the start point of the voltage test is specified.

39
00:04:29,251 --> 00:04:35,664
„PU End“ and „DOU End“ stand for the final voltage value in the pickup and dropoff, respectively.

40
00:04:35,696 --> 00:04:42,242
In „Total“ section, the time duration considered for every pickup or out dropoff state is entered.

41
00:04:42,368 --> 00:04:46,648
The longer this time, the longer the continuous paces increase time.

42
00:04:46,673 --> 00:04:51,757
If „Step Ramp“ option is selected in „State Type“ section, instead of „Total“ column,

43
00:04:51,782 --> 00:04:59,968
„dt (PU)“ which is the time duration considered for every voltage change pace in pickup states, „du(DOU)“

44
00:04:59,993 --> 00:05:09,023
which is the time duration considered for every voltage change pace in dropoff states and „dv“ which is the amount of the voltage change paces are specified.

45
00:05:09,048 --> 00:05:16,390
After entering the mentioned values, by clicking on „Init Test“, the user can view the states that are created in „Table View“,

46
00:05:16,415 --> 00:05:24,265
and in „Measurement View“, in „Time Assessmet“ and „Ramp Assessment“ windows, see that the values are entered as the test result evaluation.

47
00:05:24,290 --> 00:05:32,265
It should be noted that by selecting any State and pressing the middle button of the mouse, the user can view the details related to that state.

48
00:05:32,290 --> 00:05:34,687
Running the test and analyzing the results

49
00:05:34,712 --> 00:05:44,703
As an example, here an overvoltage function with 76 volts as the setting, and 4 seconds as the time setting in Micom P141 relay is tested.

50
00:05:44,728 --> 00:05:50,609
After applying the necessary settings in the relay, the configuration is specified as it can be seen.

51
00:05:50,634 --> 00:05:59,015
For this purpose, LEDs 1 and 4 of the relay are configured to show the pickup and the trip of this function, respectively.

52
00:05:59,047 --> 00:06:05,320
In the output contacts section, R4 is specified as the contact for recording the pickup.

53
00:06:05,345 --> 00:06:10,837
Moreover, R6 output contact in the relay is configured as a trip contact.

54
00:06:10,862 --> 00:06:19,581
To run the test, by opening a new window in „Over/Unver Voltage“ room and after entering the primary information such as the relay type,

55
00:06:19,606 --> 00:06:26,612
serial number, station name, feeder/be name and the manufacturer company, as an example,

56
00:06:26,637 --> 00:06:40,516
function OV is selected and the secondary voltage is set at 110 volts and OR is selected as the operation mode so that the results are recorded with pickup or trip of any of the phases.

57
00:06:40,541 --> 00:06:46,151
Since here there is no need for current injection, Enable Current option is not enabled.

58
00:06:46,176 --> 00:06:53,282
Also, since here open delta connection is not the case, Open Delta option is not selected either.

59
00:06:53,307 --> 00:07:02,276
In Data Table, stage 1 is selected and the voltage setting is set at 76 volts (the value specified in the relay) and LN is selected in Voltage Type section.

60
00:07:02,301 --> 00:07:08,093
The time setting of the relay is 4 seconds which is entered in Time Setting section.

61
00:07:09,120 --> 00:07:14,831
Now by going to the State Setting in Testing section, Continuous Ramp option is selected.

62
00:07:14,856 --> 00:07:21,885
Here binary C2 and C1 are selected to record the pickup and drop and record the trip, respectively.

63
00:07:21,910 --> 00:07:31,799
Since the purpose of the overvoltage element test is to test all three phases, Fault Type option is set at L1E L2E L3E.

64
00:07:31,824 --> 00:07:42,971
80 volts is entered In Vtest section which is bigger than the voltage specified in the relay settings and the relay must give a trip in this voltage.

65
00:07:42,996 --> 00:07:52,417
Also, by selecting Yes in “PU Test” and “DOU Test” section, pickup test and drop out will be done. In PU Val.

66
00:07:52,442 --> 00:08:00,276
Assess section, the approximate estimation of the value expected for the pickup which is 75.5 is entered.

67
00:08:00,301 --> 00:08:09,831
The test voltage start value and the final voltage value for the pickup test are specified in PU Start and PU End sections, respectively

68
00:08:09,856 --> 00:08:17,729
DOU End is the final voltage value for ending the dropout test. The total time is entered in Total section.

69
00:08:17,754 --> 00:08:25,393
Now Init test button is pressed so that the states are created in „Table View“ in accordance with the entered information.

70
00:08:25,418 --> 00:08:33,798
After running the test, the results of the evaluation can be viewed in „Measurement View“ window, „Time Assessment“ and „Ramp Assessment“ tabs.

71
00:08:53,233 --> 00:09:00,326
In the end, after runing the test it is necesary to add the results to the report which is done by pressing „Add to Report“.

72
00:09:00,351 --> 00:09:07,662
Also, if you wish to add specific parts of the test to the report or delete or edit the report, you need to use “Add to Report” cog.

73
00:09:07,687 --> 00:09:19,457
By clicking on this cog, the items that can be added to the “Report” are displayed as checked checkboxes and if you wish any of them not to be added to the report, uncheck the intended checkbox.

74
00:09:19,482 --> 00:09:26,464
It should be noted that after doing the tests, the results are not automatically added to the report and after doing every test

75
00:09:26,497 --> 00:09:34,878
it is necessary to manually add the results of the performed test to the output report by pressing “Add to Report” before Clearing the test.
