**“Winding Resistance” Tab

2
00:00:22,219 --> 00:00:27,640
*One of the most common and important tests of transformers is the winding resistance test.

3
00:00:27,719 --> 00:00:37,304
In this test the amount of “DC” resistance or “Rmeas” is calculated by dividing the voltage measured through the binary inputs by the injected current.

4
00:00:37,391 --> 00:00:44,882
To perform this test, first, you need to specify the primary or secondary side among “HV” and “LV” in “Side” field.

5
00:00:45,023 --> 00:00:51,617
Note that, if the transformer has three windings, “TV” is added to the two mentioned options.

6
00:00:51,642 --> 00:01:00,007
Then, you need to specify the test time and current in “I Test” and “State Time” fields in “State Setting” section, respectively.

7
00:01:00,109 --> 00:01:06,195
Since transformers have a big self-inductance and core, in the beginning of DC injection,

8
00:01:06,203 --> 00:01:15,484
there is a huge difference between the actual current and the specified current and after some time, the actual current is equal to the specified time.

9
00:01:15,609 --> 00:01:18,937
This time is entered in the “Initiated Time” field.

10
00:01:19,305 --> 00:01:27,492
Due to the fluctuation in voltage and DC current during this time, the measured resistance has a lot of fluctuations.

11
00:01:27,719 --> 00:01:34,631
Since resistance measurement must happen in a situation with the least voltage and DC current fluctuations,

12
00:01:35,172 --> 00:01:50,250
the maximum allowed fluctuations of the impedance and the shortest time during which the measured impedance needs to fluctuate below the “Nominal Stability” value are specified in “Nominal Stability” and “Stable Time” fields, respectively.

13
00:01:50,336 --> 00:01:58,195
The current measurement mode is specified in “Current Measurement Mode” section and if the current is below 0.6 amps,

14
00:01:58,242 --> 00:02:04,906
“Analog Input” should be selected while if it is higher than 0.6 amps, “Actual Current” should be selected.

15
00:02:04,922 --> 00:02:08,492
*The voltage measurement mode is specified in “Voltage Measurement Mode”.

16
00:02:08,523 --> 00:02:12,890
Since the resistance measurement method divides voltage by the current,

17
00:02:12,922 --> 00:02:17,338
voltage Range of the binary inputs affects the measurement accuracy.

18
00:02:17,367 --> 00:02:27,742
Therefore, it is necessary to select one of the inputs of this section for measurement based on the winding resistance and the maximum resistance specified to each binary input.

19
00:02:27,805 --> 00:02:33,500
If the resistance is bigger than the specified range, the device shows an “Overvoltage” error,

20
00:02:33,555 --> 00:02:40,019
in which case, you need to either decrease the current or increase the resistance measurement range.

21
00:02:40,141 --> 00:02:46,477
Also, if you are facing an “Error Other” of the current outputs, you need to decrease the current.

22
00:02:46,578 --> 00:02:54,450
*The order and the position of the “Taps” of the transformers are specified in “Insert Mode” and “Insert Position” section.

23
00:02:54,508 --> 00:02:59,695
The mentioned section has already been explained in the video related to the test.

24
00:02:59,749 --> 00:03:07,365
Another one of the most important options of the software, which helps a lot in accelerating the test, is “Sort Mode”.

25
00:03:07,438 --> 00:03:15,351
Generally, for tap changer transformers it is suggested that this option is set at “Phase”; by doing so,

26
00:03:15,376 --> 00:03:19,875
it is possible to test all taps of a phase and then go to the next phase.

27
00:03:19,969 --> 00:03:27,078
But if “Tap No.” is selected, first you need to measure the resistance of all three phases and then change the tap.

28
00:03:27,109 --> 00:03:31,210
For example, suppose that your transformer has 21 taps.

29
00:03:31,305 --> 00:03:43,148
By setting “Sort Mode” at Phase and selecting “Insert Rows” you can see that the rows are arranged according to the selected phase which helps a lot to increase the speed of the test.

30
00:03:43,140 --> 00:03:54,554
After creating the table, you need to select the intended row and then adjust the wiring according to the guide picture and then run the test by pressing “Apply Test”.

31
00:04:10,875 --> 00:04:13,468
Running the Test and Analyzing the Results

32
00:04:13,493 --> 00:04:22,687
*To perform this test, for example, the “HV” side with three “Offload” taps and 0.5 amps of current is tested for all three taps.

33
00:04:22,703 --> 00:04:33,187
The settings related to time is left at its default and “Sort by” is set at “Phase” and then by pressing “Insert Rows”, the test table is created.

34
00:04:34,671 --> 00:04:41,519
The “Signal View” window is opened so that it is possible to view the current changes of the read voltage.

35
00:04:42,734 --> 00:04:47,093
To perform the test, the first row is selected,

36
00:05:42,578 --> 00:05:45,914
the wiring is adjusted in accordance with the guide picture.

37
00:05:45,930 --> 00:05:51,007
Then the first row is selected and test runs by pressing “Apply Test”.

38
00:05:51,021 --> 00:05:56,460
By running the test, the changes of the measured voltage as well as the injected current can be viewed.

39
00:05:56,500 --> 00:05:59,132
You can see that by changing the voltage and the current,

40
00:05:59,157 --> 00:06:05,445
the value of “Stability” changes as well and the test goes on until these changes reach below 1 percent.

41
00:06:05,469 --> 00:06:08,734
After the time test is finished, the actual voltage and current,

42
00:06:08,766 --> 00:06:13,921
“Stability” and the measured and corrected resistance (according to the reference temperature) are inserted in “Test Object”.

43
00:06:13,945 --> 00:06:18,681
To continue the test, two other rows are selected and the test is applied.

44
00:06:44,445 --> 00:06:53,140
Then, the wiring is adjusted for the next phase according to the guide picture and three rows are selected and the test is applied.

45
00:07:57,476 --> 00:08:04,964
After the test is finished, in “Plot” tab, the curve resistance change in different “Taps” and phases can be viewed.

46
00:08:06,359 --> 00:08:11,351
In the end, by pressing “Add to Report”, the results are added to the report.

47
00:08:16,359 --> 00:08:19,445
Some Points about Winding Resistance Test

48
00:08:19,470 --> 00:08:27,968
*Since these transformers have a huge self-inductance, injecting “DC” current causes huge voltage “Spikes” and the more the injected current,

49
00:08:27,993 --> 00:08:30,126
the bigger the created voltage.

50
00:08:30,151 --> 00:08:37,398
This voltage causes two problems: the first problem is “Error Overvoltage” of the inputs of the device; as you know,

51
00:08:37,430 --> 00:08:45,687
if the voltage of the input is more than 0.1 second bigger than the value specified for it, the device displays an error.

52
00:08:45,712 --> 00:08:51,828
Therefore, if the caused voltage “Spikes” have too long durations, the device may display an error.

53
00:08:51,852 --> 00:08:56,171
Another problem is the voltage that occurs to the “Mosfets” of the device.

54
00:08:56,203 --> 00:09:00,335
In case of injecting too big currents, this voltage damages the device.

55
00:09:00,375 --> 00:09:04,914
Therefore, we suggest to consider these points while injecting the current.
