“Magnetic Balance” Tab

2
00:00:20,931 --> 00:00:24,523
The transformer magnetic flux test is performed in this tab.

3
00:00:24,548 --> 00:00:34,664
In this test, the voltage is applied to a voltage transformer coil and the voltage of other coils is measured and the flux division ratio between the two other coils is analyzed.

4
00:00:34,689 --> 00:00:43,234
Two important points for this test are that firstly magnetic balance test is not performed for single-phase transformers and secondly,

5
00:00:43,259 --> 00:00:49,476
this test can be performed on three-phase transformers only in the side where there is a grounded neutral.

6
00:00:49,501 --> 00:00:52,710
Flux division test has three steps for every phase.

7
00:00:52,735 --> 00:00:58,523
In the first step, voltage is applied to coil #1 and voltages of the two other coils are measured.

8
00:00:58,548 --> 00:01:07,859
In the second step the second coil is short circuited and voltage is applied to the coil of phase #1 and voltages of the two ends of the third coil are measured.

9
00:01:07,884 --> 00:01:16,663
In the third step, the third coil is short circuited and by applying voltage to phase #1, voltages of the two ends of coil #2 are measured.

10
00:01:16,688 --> 00:01:19,929
These steps are repeated for the two other phases.

11
00:01:19,954 --> 00:01:31,085
Note that the voltage of the short circuited coil is zero and during all three steps, sum of the measured voltages of the two coils must equal the voltage applied to the first coil.

12
00:01:31,110 --> 00:01:32,788
If “Dev.” option is checked,

13
00:01:32,813 --> 00:01:44,569
the total difference between the two measured phases and the phase to which the voltage is applied is calculated and is displayed in “Dev%” field in in terms of a percentage of the applied voltage.

14
00:01:44,594 --> 00:01:50,866
Also, if you wish to measure the voltage that occurs to the secondary side of the transformer during the test,

15
00:01:50,891 --> 00:01:53,030
you can use “W2” option.

16
00:01:53,055 --> 00:01:57,968
Note that if this option is checked, you need to do another step of wiring.

17
00:01:57,993 --> 00:02:01,835
In “Test Setting” section, the settings related to the test is entered

18
00:02:01,860 --> 00:02:10,444
Also, in “VLE Test” and “State Time”, the amount of voltage of the test and the test performance time of the test are entered, respectively.

19
00:02:10,469 --> 00:02:19,140
In “Display Values” it is specified that the test results are to be displayed as numerical values (in terms of volt) or as a percentage of the voltage of the test.

20
00:02:19,165 --> 00:02:28,444
If “Absolute” is selected, the applied voltage and the measured voltages of different taps are displayed in terms of volt while if “Relative” is selected,

21
00:02:28,476 --> 00:02:33,015
these voltages are displayed in terms of a percentage of the test voltage.

22
00:02:33,047 --> 00:02:41,062
The use of "Insert Mode" and "Insert Position" sections are exactly the same as those explained in conversion ratio test video

23
00:02:41,059 --> 00:02:45,951
In “Magnetic Balance Result”, the results of the flux division test are displayed.

24
00:02:45,976 --> 00:02:50,084
This section is designed to help better analyze the test results.

25
00:02:50,109 --> 00:02:59,982
In this section, the voltage is injected from a phase and the voltage induced to the two ends of the coil is read by the inputs and displayed in this section.

26
00:03:00,007 --> 00:03:10,537
By checking “Insert Rows”, a row is added to the test table in accordance with the settings adjusted in “Total Result” and all the results of the test are displayed in a row.

27
00:03:10,562 --> 00:03:13,200
Performing the test and analyzing the results:

28
00:03:13,225 --> 00:03:20,169
“15” volts is specified to perform the test and after selecting “Insert Rows” and inserting the transformer “Taps”,

29
00:03:20,194 --> 00:03:24,380
the wiring needs to be done in accordance with the picture.

30
00:04:25,875 --> 00:04:32,232
In this wiring, you only need to connect the voltage outputs of the device to the transformer and the inputs of the device.

31
00:04:32,264 --> 00:04:33,419
To measure the voltage,

32
00:04:33,444 --> 00:04:42,998
open signal view before beginning the test so that you can view the voltage signal,“Actual Current” and the voltage measured by the binary inputs of the device during the test.

33
00:04:43,023 --> 00:04:51,615
By selecting the related row and pressing “Apply Test”, the necessary hardware and software changes are applied automatically and the test starts.

34
00:04:54,005 --> 00:05:00,638
Note that if “Start Test” option is selected instead of “Apply Test”, the test will not begin.

35
00:05:01,545 --> 00:05:09,904
In the end after the test is finished, it is necessary to add the results of the evaluation to the report, which is done by selecting “Add to Report”.

36
00:05:10,242 --> 00:05:15,026
In addition, if you wish to add specific parts of the evaluation to the report,

37
00:05:15,137 --> 00:05:19,201
edit, or delete the report, you can use “Add to Report” cog.

38
00:05:19,226 --> 00:05:30,115
By clicking on this cog, you can see that the elements, which can be added to the report, are displayed with a checkmark and it is possible to uncheck any of them that you do not need in your report.

39
00:05:30,140 --> 00:05:43,709
Note that after finishing every test, the results are not added to the report automatically and it is a necessity to add the test results to the output report by pressing “Add to Report” before “Clearing the Test” and after performing a test.

40
00:05:43,734 --> 00:05:47,162
In perfuming this test, it is vital to consider some points:

41
00:05:47,187 --> 00:05:56,631
the first point is that “Error Other” in performing the test means that there is a problem in connection of the wirings and the null point of the device is connected to its phase.

42
00:05:56,656 --> 00:06:00,598
The second point is that if “Error Power” appears during performing a test,

43
00:06:00,623 --> 00:06:07,840
it means that too much current is drawn from the voltage phases and you need to decrease the test voltage to resolve this issue.

44
00:06:07,873 --> 00:06:13,076
‪The third point is that if for any reason you wish to change the wiring of the device,

45
00:06:13,100 --> 00:06:20,318
first you need to select “Apply test” and then check “Don’t Change Hardware Setting” option and select another output from

46
00:06:20,329 --> 00:06:28,545
“Hardware Configuration” window and set its “Output Target” at VL1-E and run the test after changing the test wiring.

47
00:06:28,569 --> 00:06:37,717
It should be noted that to select other inputs, “Binary Input Target” of the selected input must be similar to the default “Binary Input Target”.

48
00:06:37,733 --> 00:06:47,365
To do this, it is suggested to right-click on “Input1” row and then “Cut” the information and then “Paste” the information in the intended row.
