﻿1
00:00:18,992 --> 00:00:21,076
Introducing “Transformer”Room

2
00:00:21,101 --> 00:00:25,367
Power transformer tests are performed in “AMT Transformer” room.

3
00:00:25,392 --> 00:00:34,890
This room comprises of nine tabs. In “Test Object” tab, information and the nominal characteristics of the transformer are entered from the “Name Plate”

4
00:00:34,915 --> 00:00:38,726
”. In any of the “Vector Group, Turns Ratio and No Load”,

5
00:00:38,751 --> 00:00:43,132
“Magnetic Balance”, “Winding Resistance”, “Continuity Tap Changer”,

6
00:00:43,157 --> 00:00:49,648
“Leakage Reactance” and “Demagnetize” tabs, one of the tests of the transformer are performed.

7
00:00:49,673 --> 00:00:56,234
Also, in “Megger Test Report” tab it is possible to enter the insulation resistance test or “Megger”.

8
00:00:56,296 --> 00:01:02,687
Also, In “Vector Group Check” it is possible to test the transformers vector group independently.

9
00:01:02,712 --> 00:01:04,233
“Test Object” Tab

10
00:01:04,258 --> 00:01:10,257
“Test Object” tab: as mentioned earlier, the nominal characteristics of the transformer being tested are entered in this tab.

11
00:01:10,282 --> 00:01:14,715
in “Transformer Data” section, a group of information including serial number,

12
00:01:14,740 --> 00:01:20,387
name of the manufacturer and name of the manufacturing country of the transformer as well as the location

13
00:01:20,412 --> 00:01:26,932
 on which the transformer is used and the type of the cooling system of the transformer are entered.

14
00:01:26,957 --> 00:01:32,010
In “Extra Date” section, the date of performing the test in AD,

15
00:01:32,035 --> 00:01:43,777
the information regarding the person who is performing the test and the information regarding the supervisor are entered in “Date”, “Tested By” and “Approved By” fields respectively.

16
00:01:43,809 --> 00:01:50,035
By checking “Easy Mode” option in “Accessories” section, the wiring type of tests changes.

17
00:01:50,060 --> 00:01:56,504
This wiring is in accordance with the board which is designed by Vebko Company to test the transformer.

18
00:01:56,529 --> 00:02:02,941
This board is located on the front panel of the device and on it there are relays

19
00:02:02,966 --> 00:02:10,105
that do the wirings of the front panel of the device automatically which makes performing the test easier.

20
00:02:10,130 --> 00:02:17,777
In “Winding Configuration” section, the vector group of the transformer as well as the type of wiring of its two ends are selected.

21
00:02:17,802 --> 00:02:28,933
The wiring type of the primary and secondary windings are entered in “Primary (H)” and “Secondary(X)” fields and if there is a third winding, its wiring type is entered in “Tertiary(Y)” field.

22
00:02:28,972 --> 00:02:33,714
If the transformer has three windings, by checking “Three Winding” option,

23
00:02:33,739 --> 00:02:42,245
the third winding is added while if the transformer is single-phase, “1phase” option should be checked.

24
00:02:43,656 --> 00:02:50,691
In “Rating” section, the nominal value of voltages and the apparent power of the transformer are specified.

25
00:02:50,716 --> 00:03:00,347
Also, in “Voltage Rating” field, the primary and secondary nominal voltages as well as the third one, in case of its existence, are entered.

26
00:03:00,372 --> 00:03:12,292
In “Power Rating” field, the nominal power of the transformer as well as its impedance are entered in the corresponding fields in terms of KVA and percent, respectively.

27
00:03:12,566 --> 00:03:19,018
The information regarding the tap changer of the transformer needs to be entered in “Tap Changer” section.

28
00:03:19,131 --> 00:03:27,604
The tap changer type is selected from among “OLTC (On-Load Tap Changer)” and “DETC (De-Energized Tap Changer)” in “Type” field.

29
00:03:27,629 --> 00:03:35,698
In “Winding” field, it is required to specify that at which side of the transformer winding is the tap changer located.

30
00:03:35,723 --> 00:03:42,050
In “No. of Taps” field, the number of taps of the tap changer are entered while in “Start Tap No.

31
00:03:42,075 --> 00:03:48,026
.” it is specified that from what number are the transformer taps to begin.

32
00:03:48,051 --> 00:03:54,604
In the next step it is necessary to enter the voltage of every tap which can be done in multiple ways.

33
00:03:54,629 --> 00:04:01,065
In the first method if the distance between the taps of the transformer is equal, the first,

34
00:04:01,097 --> 00:04:05,018
middle and last voltages are entered in “First Voltage”,

35
00:04:05,043 --> 00:04:13,472
“Middle Voltage” and “Last Voltage” fields, respectively, so that the software can calculate the voltage in other taps.

36
00:04:13,537 --> 00:04:25,268
In some “Name Plates” of transformer, it may happen that only the middle tap voltage and the difference between the tap voltages are mentioned in percent.

37
00:04:25,293 --> 00:04:35,830
In this case, the “Middle” option is selected and the middle tap deviation percentage as well as its voltage are entered in “Deviation” and “Middle Voltage” fields,

38
00:04:35,855 --> 00:04:41,793
, respectively, and the software calculates the voltage of other taps automatically.

39
00:04:41,818 --> 00:04:55,782
If the difference between the taps is equal and voltages of the first and second taps are mentioned on the transformer plate, this option is selected and the voltage of “First Voltage” and “Second Voltage” fields are entered.

40
00:04:55,807 --> 00:05:02,415
In all of the mentioned cases the voltage of the taps are calculated and displayed in “Voltage Value” table.

41
00:05:02,440 --> 00:05:11,595
If the distance between the taps is not equal or the user wishes to enter the tap voltages manually, “Custom” option can be used

42
00:05:11,826 --> 00:05:19,375
By selecting this option, “Voltage Value” table appears and you can manually enter the voltage for each tap.

43
00:05:20,576 --> 00:05:26,735
The tap changer type is specified in “Tap Control Setting” section.

44
00:05:26,760 --> 00:05:37,493
If you wish to control the taps manually you should select “Manual” option; otherwise, select “Automatic Tap Control” so that the taps are controlled automatically.

45
00:05:37,518 --> 00:05:44,954
If “Automatic Tap Control” is selected, “Tap Changing Setting” and “State Termination” sections are displayed.

46
00:05:44,979 --> 00:05:50,203
In “Tap Changing Setting” section, the settings related to tap changing is specified.

47
00:05:50,228 --> 00:05:57,547
In “Impulse” field the time during which the pulse is sent by the device binary to change the tap is specified.

48
00:05:57,572 --> 00:06:04,008
In fact, “Raise” or “Low” command is issued by the device to change the tap for 1 second.

49
00:06:04,033 --> 00:06:14,563
In “Time” field the stop time for each tap is specified which is a 10-second delay after the tap change command is issued during which the tap changes.

50
00:06:14,588 --> 00:06:22,500
In “State Termination” section, the ending style of every “State” to inject the voltage to the next tap is specified.

51
00:06:22,525 --> 00:06:24,516
If “by Time” is selected,

52
00:06:24,541 --> 00:06:36,242
the voltage injected in every tap is specified in accordance with the time selected in “Tap Changing Setting” section and after the time is passed, a pulse is sent to change the tap.

53
00:06:36,274 --> 00:06:44,219
By selecting “by Inprogress Contact” and using a contact and connecting it to the binary inputs of the device,

54
00:06:44,244 --> 00:06:53,125
by changing the binary input mode, “AMT105” device recognizes the tap change and regardless of the time entered for tap change,

55
00:06:53,150 --> 00:06:55,594
ognizes the tap change and regardless of the time entered for tap change,

56
00:06:55,619 --> 00:07:06,718
In “No. of Analog Input” field, number of the binary used to detect the tap change is specified while in “Reverse” field, the primary state of the binary input is specified.

57
00:07:06,743 --> 00:07:14,179
By selecting “Wet”, “Inprogress” contact is determined to be of the wet type and its voltage level is entered in front of it.

58
00:07:14,204 --> 00:07:18,952
By selecting “Dry” option, the contact is determined to be of the dry type.

59
00:07:18,977 --> 00:07:26,827
The amount of allowed measurement tolerance to detect “Pass” and “Fail” of the test is entered in “Tolerance” section.

60
00:07:26,852 --> 00:07:34,405
In “Ratio dev.” Field, the allowed tolerance value for the measured phases is specified in terms of degree.

61
00:07:34,430 --> 00:07:39,530
In “Winding Material” field in “Temperature Correction” section,

62
00:07:40,152 --> 00:07:47,437
the material used in the windings is selected from among “Copper” and “Aluminum”.

63
00:07:47,462 --> 00:07:58,405
The current temperature of the winding of the transformer and the reference temperature for measuring the winding resistance are entered in “Winding Temp”, “Reference Temp.

64
00:07:58,430 --> 00:08:05,249
.” fields, respectively, so that the resistance values measured are corrected in different temperatures.

65
00:08:05,274 --> 00:08:11,812
“Correction Factor” field is related to transformer correction factor (K Factor) and by changing “Winding Material”

66
00:08:11,837 --> 00:08:17,124
”, “Winding Temp.” and “Reference Temp.” sections, this section changes automatically.

67
00:08:17,149 --> 00:08:29,515
Also, by pressing “Add to Report” option in the box at the bottom of the screen, this information is added to the output report and a message stating “The Report was added to the list” is displayed.

68
00:08:29,577 --> 00:08:36,171
It is possible to view the output report by selecting “Report” window from the box at the right side.

69
00:08:36,211 --> 00:08:44,101
By clicking on “Delete Report” option in “Delete from Report” window, it is possible to delete the added report from the “Report” window.

70
00:08:44,125 --> 00:08:56,201
If “Set as default” option is selected, the entered values will be saved as default and every time, by opening the “Current Transformer (CT)” room this information is displayed.
