﻿1
00:00:19,444 --> 00:00:24,444
A Guide for CVT Test Wiring Using the Instrument Module

2
00:00:27,381 --> 00:00:35,952
The instrument module is designed as a user interface. Its power rating is the same as the device

3
00:00:36,825 --> 00:00:47,619
but with a single calibration, you can perform all relevant routine tests in a much shorter time with a lower calibration error percentage

4
00:00:47,778 --> 00:00:55,952
First, install the Base module on the front panel of the device so that the male banana connectors of the Base module

5
00:00:56,269 --> 00:01:07,063
fit into the indicated part. Then, install three 18650 lithium batteries, 4.2 volts, 2000 mAh

6
00:01:07,381 --> 00:01:16,904
, in the indicated order from right to left. Install the relevant module, which in this test is the CVT or CT module

7
00:01:17,063 --> 00:01:23,095
on the Base module, then tighten the three screws of the transformer module

8
00:01:23,730 --> 00:01:32,936
and finally turn on the module. Here, you will see four boxes that indicate the battery charge percentage

9
00:01:33,333 --> 00:01:38,492
 each box indicating 25% of the battery charge

10
00:01:39,762 --> 00:01:49,285
Also, when you connect the battery charger to the module, the corresponding box will start
blinking depending on the battery charge percentage

11
00:01:49,762 --> 00:01:55,238
and when the battery is fully charged, all boxes will blink

12
00:01:56,746 --> 00:02:02,936
Warning: Do not use the module to perform tests while the batteries are charging

13
00:02:03,387 --> 00:02:13,386
The reason
for using batteries on the module is to isolate the module's power supply from the device's power supply and eliminate noise

14
00:02:14,022 --> 00:02:15,529
Important Notes:

15
00:02:16,165 --> 00:02:23,069
The Base module's optical sensor must be placed directly over the device's Error light

16
00:02:23,704 --> 00:02:30,052
The first time the batteries are installed on the module, even if they are fully charged

17
00:02:31,006 --> 00:02:38,545
due
to the defined protection, a charger must be connected to the module once for the module
to turn on

18
00:02:40,291 --> 00:02:46,323
Now, to perform calibration, enter the Setting window from the software's start page

19
00:02:46,561 --> 00:02:54,497
click on Apply Calibration Instrument in the Hardware tab, and after 5 seconds, the calibration will be complete

20
00:02:54,894 --> 00:03:01,878
Enter the CVT room, set the Type Device to 205AMT

21
00:03:02,038 --> 00:03:10,847
and in the Accessories section, set the Version Mode Easy to CT _205_ Ver01

22
00:03:11,165 --> 00:03:20,767
Note that calibrating the module is only necessary once and should only be done if the device or base module has been replaced

23
00:03:27,434 --> 00:03:36,243
To connect each end of the CVT (Voltage Transformer) to the module, we require two wires: a voltage wire and a current wire

24
00:03:36,402 --> 00:03:47,275
For instance, from the P1 end of the capacitive voltage transformer, two wires (one for voltage and one for current) are connected to the P1 outputs of the module

25
00:04:14,310 --> 00:04:22,880
The connections for 2P, 1S, and 2S are similar to the 1P connections

26
00:05:10,738 --> 00:05:21,452
Finally, the C1 and C0 terminals of the module are connected to one of the capacitors in the capacitor bank
