﻿1
00:00:20,062 --> 00:00:21,234
Excitation tab

2
00:00:21,259 --> 00:00:25,921
In fact, “Excitation” or saturation test, analyzes the characteristic of the core.

3
00:00:25,946 --> 00:00:32,101
In this test, by decreasing the frequency, a method is used to keep the voltage at a safe level.

4
00:00:32,126 --> 00:00:40,773
The core flux is in accordance with the relation between the voltage and the frequency and by using this relation and to prevent high voltages in CVT primary,

5
00:00:40,798 --> 00:00:45,593
it is possible to use a lower voltage for the test by decreasing the frequency.

6
00:00:45,626 --> 00:00:51,546
It should be noted that the software calculates and displays the saturation point in the nominal frequency.

7
00:00:51,571 --> 00:00:58,187
Moreover, decreasing the frequency helps to remove the effects caused by the stray capacity of the primary side.

8
00:00:58,212 --> 00:01:05,835
Since the CVT damping circuit is used to stop the Ferro resonance effects, before performing the saturation test,

9
00:01:05,860 --> 00:01:09,187
it is necessary to isolate its circuit from CVT.

10
00:01:09,212 --> 00:01:14,914
Moreover, to perform coil resistance, secondary short-circuit impedance and saturation tests,

11
00:01:14,947 --> 00:01:22,539
it is necessary to detach the PLC/NHF terminal from the ground so that the high voltage does not cause any problem.

12
00:01:22,564 --> 00:01:30,117
By doing the wiring in accordance with the picture and applying AC voltage to the secondary coil, the saturation curve is obtained.

13
00:01:30,142 --> 00:01:38,492
In this process, the voltage of the secondary terminal, excitation current and the phase angle between the excitation voltage and current are measured.

14
00:01:38,525 --> 00:01:43,390
In this room, first, it is necessary for the amount of voltage intended for the test,

15
00:01:43,415 --> 00:01:47,765
frequency and test duration to be entered in “State Setting” section.

16
00:01:47,790 --> 00:01:56,421
In this section, in fact, “Vtest” is “Vend” and, in this field, the test voltage increases from zero to the specified voltage.

17
00:01:56,446 --> 00:01:58,335
In “Demagnetize” section,

18
00:01:58,360 --> 00:02:08,742
before performing the saturation test, the software demagnetizes the “CVT” by AC voltage so that the residue flux caused by the “DC” resistance test is eliminated.

19
00:02:08,767 --> 00:02:15,492
In this section it is necessary to enter the “Demagnetization” time and the voltage in terms of a percentage of the “Vend”.

20
00:02:15,517 --> 00:02:17,539
In “Choose Current Measurement Mode” section,

21
00:02:17,564 --> 00:02:24,968
it is possible to specify the current measurement mode so that the proper algorithm is applied in accordance with the current range.

22
00:02:24,993 --> 00:02:28,750
In this case, it should be noted that if the load current is low,

23
00:02:28,775 --> 00:02:34,710
it is better to use “Low current” mode because in this mode, the accuracy of load current measurement is higher.

24
00:02:34,735 --> 00:02:37,468
Performing the test and analyzing the results

25
00:02:37,493 --> 00:02:40,593
To perform this test, as an example, 20 volts,

26
00:02:40,618 --> 00:02:47,687
10 Hz, 15s, and “High Current” are entered as “Vtest”, frequency, and test time and test mode

27
00:02:47,712 --> 00:02:55,054
On this page a warning can be seen which says that in this test the primary side voltage will reach 36000 volts.

28
00:02:55,079 --> 00:02:59,492
Therefore, while performing this test, observing safety points is required.

29
00:02:59,517 --> 00:03:04,085
After specifying the settings, the wiring should be done in accordance with the picture.

30
00:03:04,110 --> 00:03:14,015
In this wiring, the voltage of the first phase of the device is connected to the positive polarity of the capacitor and after connecting two negative polarity of the capacitors,

31
00:03:14,040 --> 00:03:24,906
the positive polarity of the second capacitor is connected to the positive polarity of the “CVT” and the other polarity of the “CVT” is connected to the null of the device.

32
00:03:34,302 --> 00:03:47,507
The reason for using the connections of capacitors in the path of applying voltage to the “CVT” is to filter the “DC” offset which is caused by the linear amplifier of the device.

33
00:03:47,792 --> 00:03:49,460
After doing the wiring,

34
00:03:49,485 --> 00:03:57,843
“Signal View” window is opened so that the signals of the load voltage and current and also the saturation curve can be viewed during the test.

35
00:03:57,868 --> 00:04:03,226
After completing these steps it is necessary to click on “Init Test” every time

36
00:04:03,251 --> 00:04:08,742
before performing the test so that the settings needed for the test are adjusted automatically.

37
00:04:08,767 --> 00:04:19,438
By running the test, it can be seen that first, the “CVT” is “Demagnetized” and then the saturation test is performed.

38
00:04:29,163 --> 00:04:36,859
After the test is finished, the test voltage and current are displayed on the diagram in “Excitation Result” box.

39
00:04:36,884 --> 00:04:43,257
After the test is finished, to add the test results to the report, click on “Add to Report”.

40
00:04:43,876 --> 00:04:53,273
Also, by using the cog next to this option, before selecting “Add to Report”, uncheck any item that you do not wish to be added to the report.

41
00:04:53,298 --> 00:04:59,952
If for any reason, wish to use a voltage other than the voltage of the first phase, first, press “Init Test”

42
00:04:59,977 --> 00:05:08,015
and then check “Don’t Change Hardware Setting” option and then select a different output from “Hardware Configuration”

43
00:05:08,040 --> 00:05:14,499
window and set its “Output Target” at “VL1-E” and after changing the wiring, run the test.

44
00:05:14,524 --> 00:05:21,772
Note that if the device displays an “Overcurrent” error before finding the knee and saturation points,

45
00:05:21,825 --> 00:05:28,741
the wiring needs to be changed to “High Current” and the test can be run after pressing “Init Test”.

46
00:05:28,766 --> 00:05:34,944
If again, the device displays an “Overcurrent” error before finding the saturation point,

47
00:05:34,969 --> 00:05:44,687
this means that the saturation point current is higher than the “limits” of the device and it is not possible to find the knee point using this device.
