	Capacitive Voltage Transformers

2
00:00:21,148 --> 00:00:25,468
Voltage transformers are composed of a core, two windings, and insulation.

3
00:00:25,493 --> 00:00:33,007
VTs convert the high voltage of the primary side to low voltage on their secondary winding with the turn ratio written on their plate.

4
00:00:33,032 --> 00:00:41,210
Because of the internal casualties such as copper and iron casualties, the vector of the secondary voltage is different from the primary voltage.

5
00:00:41,258 --> 00:00:47,140
Moreover, the connected burden is capable of affecting the turn ratio error and phase displacement.

6
00:00:47,165 --> 00:00:53,687
If the actual amplitude of the secondary voltage is lower than nominal secondary voltage, the amplitude error is negative.

7
00:00:53,712 --> 00:00:59,740
Also, if the secondary vector is lagging in relation to the primary vector, the phase error is negative.

8
00:00:59,765 --> 00:01:05,968
To compensate for the turn ratio error, sometimes manufacturers adjust the number of primary or secondary turns.

9
00:01:05,993 --> 00:01:14,023
Nowadays, most of the VTs that are used in the industry are either inductive VTs or capacitive VTs which are called “CVT”.

10
00:01:14,048 --> 00:01:21,445
CVTs are composed of an inductive VT, a high-voltage capacitive divider and a compensator reactor.

11
00:01:21,470 --> 00:01:30,865
In the IEC standard, the title CVT is used for this equipment but in the ANSI standard, this equipment is called CCVT.

12
00:01:30,897 --> 00:01:38,107
The compensator rector is designed in a way that it can compensate for the phase displacement caused by the capacitive divider.

13
00:01:38,132 --> 00:01:45,068
All CVTs can be used for measurement purposes but only certain types of this equipment are suitable for protection purposes

14
00:01:45,093 --> 00:01:51,570
Dual-purpose CVTs (measurement and protection) must be in accordance with all of the considered descriptions and the current standards.

15
00:01:51,595 --> 00:01:54,125
According to the maximum allowed error percentage,

16
00:01:54,158 --> 00:02:04,523
the accuracy class of the protection CVTs is considered to be from 5 percent of the nominal voltage to a coefficient of the nominal voltage (Rated Voltage Factor) and after its value, the letter P is used.

17
00:02:04,548 --> 00:02:09,015
3P and 6P are the standard accuracy classes for protection CVTs.

18
00:02:09,040 --> 00:02:13,851
For example, 3P accuracy class means that the maximum allowed error is 3 percent.

19
00:02:13,876 --> 00:02:22,428
Moreover, in IEC standard, three classes of T1, T2 and T3 are considered for the function of CVT in transient state.

20
00:02:22,453 --> 00:02:31,295
For example, 3PT2 class indicates that the function of the 3P class is for protection purposes and T2 class is for transient states.

21
00:02:31,320 --> 00:02:35,742
Classes related to the transient response are a defined in the following table:

22
00:02:35,767 --> 00:02:37,046
In the above relation,

23
00:02:37,071 --> 00:02:40,671
Us (t) is the response for the transient secondary voltage.

24
00:02:40,703 --> 00:02:51,530
For example, for the 3PT2 class, the relation of the transient voltage to the nominal voltage peak in the range of from 10 ms to 90 ms after the beginning of the transient state,

25
00:02:51,595 --> 00:02:56,640
It should decreas and be in the range of less than 25 times to 0.2.

26
00:02:56,665 --> 00:03:00,203
In this regard, it is necessary to pay attention to several points:

27
00:03:00,228 --> 00:03:07,789
CVTs need a damping piece of equipment for the 6PT3 and 3PT3 transient response classes.

28
00:03:07,814 --> 00:03:15,328
By agreement between the manufacturer company and the customer, it is possible to consider different values for the turn ratio and Ts time.

29
00:03:15,353 --> 00:03:20,320
Selecting the transient response class depends on the characteristics of the protection relays.

30
00:03:20,345 --> 00:03:29,101
About Measuring CVTs, the accuracy class is defined based on the highest allowed error percentage in the nominal voltage with the nominal burden.

31
00:03:29,126 --> 00:03:37,156
The standard accuracy classes for single-phase Measuring CVTs are considered to be 0.2, 0.5, 1.0 and 3.0.

32
00:03:37,181 --> 00:03:38,468
Test Object tab

33
00:03:38,493 --> 00:03:44,187
To perform a test, every module needs a set of information about the equipment which is entered in “Test Object”.

34
00:03:44,212 --> 00:03:51,296
In this tab, the general characteristics of the “CVT” and its information for performing the test and adding to the report are specified.

35
00:03:51,329 --> 00:04:01,359
In “Data” section, information such as serial number, model, the manufacturer company and the installation location of the “CVT” are entered to be added to the report.

36
00:04:01,384 --> 00:04:09,703
In “Winding Material” field in “Temperature Correction” section, the conductor type of the windings is selected from among “Copper” and “Aluminum”.

37
00:04:09,728 --> 00:04:22,718
In “Winding Temp.” field the current temperature of the windings and in “Reference Temp.” field, the reference temperature for measuring the resistance of the windings are entered so that they can be used to correct the values measured in different temperatures.

38
00:04:22,743 --> 00:04:30,968
Usually, the reference temperature which is 75 degrees is written in front of the secondary winding resistance on the plate of the “CVT”.

39
00:04:30,993 --> 00:04:42,953
In “Correction Factor” field which is uneditable, the temperature correction factor is calculated by the software in accordance with the current ambient temperature as well as the reference temperature and the winding material.

40
00:04:42,978 --> 00:04:48,976
It is possible to view the relation used for calculating this factor, by holding the cursor on its field.

41
00:04:49,001 --> 00:04:54,453
The „RMS“ value of every parameter is calculated based on the average of several time periods.

42
00:04:54,478 --> 00:05:03,054
As the number of these time periods increases, it takes longer to make the calculations but also the accuracy increases and there will be fewer fluctuations.

43
00:05:03,079 --> 00:05:08,257
The number of these time periods is entered in „Averaging“ field in „Noise Suppression“ section.

44
00:05:08,282 --> 00:05:13,226
This field is the same as „No. of period“ field in „Setting“ in „Signal View“ window.

45
00:05:13,251 --> 00:05:23,546
In “Date” field in “Extra Data” section, the date of performing the test is entered in AD and the information about the performer of the test is entered in “Tested By” field.

46
00:05:23,571 --> 00:05:28,281
Also, the information about the supervisor is entered in “Approved By” field.

47
00:05:28,306 --> 00:05:35,234
In “Data Table”, the characteristics of every core and tap are entered in every row in accordance with the characteristics plate.

48
00:05:35,259 --> 00:05:40,750
The core number and the tap number are entered in “Core Number” and “Tap Number” fields, respectively.

49
00:05:40,775 --> 00:05:50,851
The primary parameters are entered in “Vprimary” and “Primary Factor” fields while the secondary characteristics are entered in “Vsecondary” and “Secondary Factor” fields.

50
00:05:50,890 --> 00:06:00,585
The burden is specified in “VA” field and in “CLP” and “CLM” fields, the Protection Core and Measuring of the transformer are entered, respectively.

51
00:06:00,610 --> 00:06:08,078
Likewise, the information related to the two other taps of the CVT that are being used is specified.

52
00:06:08,103 --> 00:06:18,397
Also, if the characteristics of the “VT resistance” are available, it is possible to check “Show Resistance Column” option to add the related column to the table.

53
00:06:18,422 --> 00:06:26,311
By checking this option, some changes are made in the “DC Resistance” test table which will be thoroughly explained in its related video.

54
00:06:26,336 --> 00:06:37,772
Also, by pressing the „Add to Report“ option in the box at the bottom, this information is added to the output report and a message stating „The Report was added to the list“ is displayed.

55
00:06:37,876 --> 00:06:43,850
It is possible to view the report by selecting „Report“ window from the bar at the right.

56
00:06:43,875 --> 00:06:50,420
By clicking on „Delete Report“ option in „Delete From Repor“ window, the added report is removed.

57
00:06:50,445 --> 00:06:52,787
If „Set as default“ option is checked,

58
00:06:52,812 --> 00:07:01,990
the entered information is saved as default and every time, by opening the „Capacitor Voltage Transformer(CVT)“ room this information is displayed.
