﻿1
00:00:18,810 --> 00:00:25,158
A Guide for Performing CB Test Connections Using the Instrument Module

2
00:00:25,635 --> 00:00:29,761
The Instrument Module is designed as a user interface

3
00:00:29,786 --> 00:00:36,984
The power of these modules is the same as the device, with the difference that with a single connection

4
00:00:36,937 --> 00:00:44,761
you can perform all relevant tests in a shorter time and with significantly lower connection error rates

5
00:00:45,635 --> 00:00:50,158
First, install the Base module on the front panel of the device

6
00:00:50,635 --> 00:00:55,873
so that the male pins of the Base module fit into the shown section

7
00:00:56,349 --> 00:01:01,984
Then, install three batteries with the specifications of Lithium-ion

8
00:01:02,222 --> 00:01:13,492
18650, 4.2 volts, 2000 mAh, from right to left as shown

9
00:01:13,810 --> 00:01:21,269
Place the relevant module, which in this test is the CT module, on the Base module

10
00:01:21,667 --> 00:01:27,460
Tighten the three screws of the transformer module and then turn on the module

11
00:01:27,721 --> 00:01:35,793
You will see 4 sections indicating the battery charge percentage, where each section represents 25% battery charge

12
00:01:36,190 --> 00:01:45,158
Also, when connecting the battery charger to the module, the corresponding section will start flashing according to the battery charge percentage

13
00:01:45,635 --> 00:01:50,873
When the battery is fully charged, all sections will start flashing

14
00:01:51,349 --> 00:01:56,984
Warning: Do not use the module for tests while the batteries are charging

15
00:01:57,143 --> 00:02:06,984
The reason for using batteries on the module is to isolate the module's power supply from the device's power supply and to eliminate noise

16
00:02:08,260 --> 00:02:10,878
A few important points to note:

17
00:02:11,990 --> 00:02:20,164
1. The optical sensor of the Base module must be completely aligned with the device's Error 
light

18
00:02:21,117 --> 00:02:26,355
2. The first time the batteries are installed on the module

19
00:02:26,593 --> 00:02:36,196
even if they are fully charged, you 
need to connect the charger to the module once due to the defined protection to turn the 
module on.

20
00:02:36,514 --> 00:02:43,021
Now, to perform calibration, enter the Settings window from the software's start page

21
00:02:43,339 --> 00:02:52,307
click on Apply Calibration Instrument in the Hardware tab, and after 5 seconds, the calibration will be completed

22
00:02:52,783 --> 00:02:59,212
Enter the CB Room, set the Device Type to 205AMT

23
00:02:59,379 --> 00:03:08,577
and in the Accessories section, set the Version Mode Easy to CB _205_ Ver 01

24
00:03:09,371 --> 00:03:20,482
Note that module calibration is only necessary once and should only be performed again if the device or the Base module has been replaced

25
00:03:22,863 --> 00:03:28,021
For connection, if using the device's internal power supply

26
00:03:27,941 --> 00:03:33,259
connect the Close output of the module to the Close coil of the switch

27
00:03:33,346 --> 00:03:42,386
Open to the Open coil, and Com to the common part of the Open and Close coils of the switch

28
00:03:44,132 --> 00:03:52,942
Additionally, for connecting the switch contacts to its test module, you will need two sets of six voltage and current cables

29
00:03:53,101 --> 00:04:00,085
Each switch contact must have one voltage wire and one current wire connected to the module

30
00:04:01,593 --> 00:04:12,291
For example, from contact L1of the switch, connect one voltage wire named L1 and one current wire named IL1 to the module

31
00:04:12,530 --> 00:04:25,386
and similarly, from contact L1N of the switch, connect the voltage wire L1N and the current wire I L1N to the module

32
00:04:25,546 --> 00:04:28,720
The same connection applies to other contacts

33
00:06:00,270 --> 00:06:12,174
On the switch test module, the M+, SH+, and SH- outputs are also used according to the existing connections in the Current Motor test
