﻿1
00:00:23,678 --> 00:00:23,745
C

2
00:00:23,746 --> 00:00:23,814
CB

3
00:00:23,815 --> 00:00:23,882
CB 

4
00:00:23,883 --> 00:00:23,950
CB “

5
00:00:23,951 --> 00:00:24,019
CB “T

6
00:00:24,020 --> 00:00:24,087
CB “Ti

7
00:00:24,088 --> 00:00:24,155
CB “Tim

8
00:00:24,156 --> 00:00:24,223
CB “Timi

9
00:00:24,224 --> 00:00:24,292
CB “Timin

10
00:00:24,293 --> 00:00:24,360
CB “Timing

11
00:00:24,361 --> 00:00:24,428
CB “Timing 

12
00:00:24,429 --> 00:00:24,497
CB “Timing T

13
00:00:24,498 --> 00:00:24,565
CB “Timing Te

14
00:00:24,566 --> 00:00:24,633
CB “Timing Tes

15
00:00:24,634 --> 00:00:24,702
CB “Timing Test

16
00:00:24,703 --> 00:00:24,770
CB “Timing Test”

17
00:00:24,771 --> 00:00:25,271
CB “Timing Test”

18
00:00:25,296 --> 00:00:28,924
One of the most important tests performed in CB is “Timing Test”.

19
00:00:28,949 --> 00:00:34,720
To perform a “Timing Test” it is necessary to specify three main important sections including

20
00:00:34,745 --> 00:00:43,398
1- Supplement method of bobbins, 2- Wiring type of “Binary Outputs” and 3- type of “Binary inputs”.

21
00:00:43,423 --> 00:00:53,518
The supplement method of bobbins is specified in “Power Supply” section which is set at “AMT105” by default and its value is taken from “Test Object”.

22
00:00:53,543 --> 00:01:00,440
To control the voltage applied to “Open” and “Close” bobbins, “Binary Outputs” of the device are used.

23
00:01:00,480 --> 00:01:09,720
In “Binary Output” section it is specified that which “Binary Outputs” are to be used to control “Close” and “Open” commands which is set at “Series” by default.

24
00:01:10,357 --> 00:01:18,936
In this mode, huge voltages which occur during opening and closing are divided between the two relays which prevents damage to the device.

25
00:01:18,961 --> 00:01:25,679
But if one of the “Binary Outputs” is not available, by selecting other options, it is possible to use only two “Binaries”.

26
00:01:25,703 --> 00:01:35,283
For example, by selecting “Bin1” and “Bin4” you can only use the “Binaries” 1 and 4. In this instruction, “Series” mode is used.

27
00:01:35,307 --> 00:01:42,936
“Binary Input” is used to sense when the CB is closed or open. Since there is noise in substations,

28
00:01:42,960 --> 00:01:49,140
“Binary Inputs” are set at “Wet” by default so noise is removed from the “Binary Inputs”.

29
00:01:49,164 --> 00:01:58,079
But if there is no noise in the test environment you can set the type of “Binary Inputs” at “Dry” and by changing the “Binary” type, the wiring changes as well.

30
00:01:58,104 --> 00:02:09,527
Next you need to select the test type from among “Open—Close—Open Close--…” By selecting any of them, you need to enter the time in the specified box.

31
00:02:09,551 --> 00:02:17,958
For example, in “Open” test, you need to enter “three” times in the designed fields; the first “time” is related to before command,

32
00:02:17,982 --> 00:02:26,510
the second “time” is related to the Duration which the command is kept on the bobbin and the third time is related to after command.

33
00:02:26,534 --> 00:02:35,787
In this example, the bobbin is supplied by the device and “Binary Output” and “Binary Input” are set at “Series” and “Wet” respectively.

34
00:02:35,811 --> 00:02:40,460
For “Open” test, the default time values are considered as the time values.

35
00:02:40,484 --> 00:02:44,423
Then, you need to set the wiring according to the specified picture.

36
00:02:44,447 --> 00:02:48,972
Note that by double-clicking on the picture, it is possible to magnify it.

37
00:02:57,682 --> 00:03:05,682
In this wiring, the specified connections must be set, those points that have the same name must be connected to each other,

38
00:03:21,998 --> 00:03:34,630
Close and Open bobbins must be connected to the lower end of “Binary Outputs” number 3 and 4 and finally,

39
00:03:34,668 --> 00:03:40,395
the connections of “Binary Input” must be set to receive the key contacts.

40
00:04:13,326 --> 00:04:20,198
After setting the wiring, open “Signal View” and initiate the test by selecting “Init Test”.

41
00:04:22,364 --> 00:04:29,638
In “Signal View” window, it is possible to view the voltage and current loaded from the device as well as the CB opening time.

42
00:04:29,662 --> 00:04:35,068
 “Vc1+” and “Vc2+” indicate the status of the “Close”

43
00:04:35,108 --> 00:04:45,480
command control “Binary Outputs” while “Vo1+” and “Vo2+” are indicators of the status of the “Open” command control “Binary Outputs”.

44
00:04:45,504 --> 00:04:49,903
“L1”, “L2” and “L3” indicate the status of the CB contacts:

45
00:04:49,927 --> 00:04:56,287
Three colored lines mean that the CB contacts are closed while no lines suggest the opposite.

46
00:04:56,311 --> 00:05:03,529
“AUX Open” and “AUX Close” signals are used to determine the origin time for measuring the performance time.

47
00:05:04,053 --> 00:05:13,697
As mentioned before, the CB performance is measured since when the voltage of the “Binaries” 7 and 8 exceeds the “Threshold” specified in “Test Object”.

48
00:05:14,395 --> 00:05:19,009
Moreover, the test results are available in “Summary of Result” section.

49
00:05:19,096 --> 00:05:28,536
In this section, the peak current and “Steady State” current and in the “Open” table the opening time of each contact is provided separately.

50
00:05:28,560 --> 00:05:35,647
Note that the evaluation of these times is done in accordance with the “Opening Time” and “Opening Sync” specified in “Test Object”.

51
00:05:35,671 --> 00:05:43,414
If the operating time is somewhere within the range specified in “Test Object” the test “Passes”, otherwise it “Fails”.

52
00:05:43,438 --> 00:05:49,252
For adding the results to the report, you can do so by pressing “Add to Report”. Also,

53
00:05:49,276 --> 00:05:57,300
if you wish to add some specific parts to the report, or delete and edit the report, you need to use the “Add to Report” cog.

54
00:05:57,324 --> 00:06:07,602
By clicking on this cog, you can view the items that can be added to the report. If you do not need each of them, you can unselect by unchecking them.

55
00:06:07,626 --> 00:06:19,582
Note that after performing a test the results are not automatically added to the report and it is necessary to add the results to the report by “Add To Report” before “Clearing” the test.

56
00:06:19,606 --> 00:06:23,907
In the following, some points about the test are provided:

57
00:06:24,296 --> 00:06:28,699
The first point is that if you wish to use only one voltage group,

58
00:06:28,723 --> 00:06:36,671
first you need to press “Init Test” and then check “Don’t Change Hardware Setting” and by going to the “Hardware Configuration”,

59
00:06:36,695 --> 00:06:46,765
activate your intended voltage phases and deactivate the others in the “Analog Output” tab and perform the test using only the voltages of the intended group.

60
00:06:46,789 --> 00:06:53,511
For example, here voltage group “A” is activated and voltage group “B” is deactivated.

61
00:06:53,535 --> 00:07:05,029
The second point is that when you enter “150” milliseconds as the command time, this means that the command voltage is kept on the bobbin for “150” milliseconds

62
00:07:05,069 --> 00:07:11,504
If you check “Command Termination Trigger” option and enter “10” milliamps as the “Minimum Time”,

63
00:07:11,528 --> 00:07:19,035
the command is removed from the CB, “10” milliseconds after its operation. To view this item, “Close” test is selected.

64
00:07:19,059 --> 00:07:26,431
To initiate the test, “Init” is pressed and test starts. After that, you can see that because of checking this option,

65
00:07:26,463 --> 00:07:32,876
unlike the previous case, “10” milliseconds after the CB operation the command is removed.

66
00:07:32,900 --> 00:07:41,685
The third point is that if the current needed to exciting the bobbin is more than “2.5” amps, it is necessary to use an external source.

67
00:07:41,709 --> 00:07:49,137
In this case, check the “External” option and set the new wiring and start the test after pressing “Init Test”.

68
00:07:49,162 --> 00:07:54,741
If you are using an external source to provide the voltage of the bobbins, to better protect the bobbins,

69
00:07:54,766 --> 00:08:06,355
put a glass relay with the “Binary Outputs” in series so that if something unexpected happened to the “Binary Outputs” which made them no longer able to disconnect the voltage applied to the bobbins,

70
00:08:06,379 --> 00:08:14,438
the CB is not damaged and in this way you can have more control on connecting and disconnecting the supply applied to them.

71
00:08:14,463 --> 00:08:20,935
In using a glass relay, since the voltage of the binaries number 7 and 8 is used as the time origin,

72
00:08:20,959 --> 00:08:27,402
delay of the glass relay has no effect on the test result and this delay is deleted by the software.

73
00:08:27,426 --> 00:08:32,654
Also, when testing the CB time test, it is necessary to know the current loaded by the CB.

74
00:08:32,678 --> 00:08:38,263
A “100” milliohm resistance is considered for this and when the current flow,

75
00:08:38,287 --> 00:08:45,445
a voltage is measured by the “Binary Input” 10 and by dividing the voltage by the resistance,

76
00:08:45,469 --> 00:08:53,164
“Coil Current” is calculated by the software and displayed in “Coil Current” section in “Signal View”.

77
00:08:54,283 --> 00:09:08,634
The third point is that “Error Other” while performing a test means that there is an issue with the connections or the high current loaded by the bobbins in a way that the device is unable to provide needed current.

78
00:09:08,681 --> 00:09:14,339
Therefore, in case of encountering this error, check the “Actual Current” value in “Signal View”.

79
00:09:14,363 --> 00:09:23,713
If the “Actual Current” reaches “2.5” amps and then the test is stopped, it means that the device is not capable of injecting that current and an external source should be used.

80
00:09:23,744 --> 00:09:34,886
If the time recorded in the table is “-1ks”, this means that the CB has been “Open” before performing the test or it has been closed for the “Close” test of the CB.

81
00:09:34,918 --> 00:09:40,240
In this case, other than the wiring, you need to check whether the CB is closed or open.
