 Estimating Fs and ALF for Various CTs

2
00:00:23,984 --> 00:00:33,203
In measurement CTs (Current Transformers), a parameter called Fs (Security Factor) exists

3
00:00:33,516 --> 00:00:38,515
which is used to describe the CT and its accuracy class

4
00:00:38,984 --> 00:00:51,406
According to the IEC60044-1 standard, Fs is defined such that at a current of Fs times the rated current

5
00:00:51,720 --> 00:01:04,687
the composite error in the secondary is 10%. For example, for a CT with a class of 0.5Fs10, at 10 times the rated current

6
00:01:04,922 --> 00:01:11,640
the composite error is 10%. On the CT nameplate provided in this example

7
00:01:11,797 --> 00:01:18,515
Core number one is a measurement type and its class is 0.2Fs10

8
00:01:19,375 --> 00:01:27,109
. This means that at 10 times the rated current, the composite error at the output is 10%

9
00:01:27,422 --> 00:01:35,000
The 0.2 figure before Fs represents the accuracy class of the CT at the rated current

10
00:01:35,468 --> 00:01:42,733
This means that at 100% and 120% of the rated current on the primary side

11
00:01:42,891 --> 00:01:48,906
the ratio error at the secondary terminal is less than 0.2%.

12
00:01:53,047 --> 00:02:00,630
For protective CTs, a similar concept exists known as ALF (Accuracy Limit Factor)

13
00:02:00,842 --> 00:02:11,411
To explain this parameter, consider the previous example. Core number 2 is a protective core with a class of 5P20

14
00:02:11,724 --> 00:02:24,224
In this example, ALF = 20, and according to the definition provided by IEC60044-1, at 20 times the rated current

15
00:02:24,693 --> 00:02:35,240
the composite error is 5%. For a more detailed explanation, consider a protective CT with a class of 10P5

16
00:02:35,709 --> 00:02:46,568
In this case, ALF = 5, and according to the definition, at 5 times the rated current, the composite error is 10%.

17
00:02:47,271 --> 00:02:58,443
One key point about these two parameters is that for measurement CTs, the actual Fs is less than the value indicated on the nameplate

18
00:02:58,834 --> 00:03:06,724
whereas for protective CTs, the actual ALF is greater than the value shown on the nameplate

19
00:03:07,428 --> 00:03:10,084
Ratio Error and Composite Error

20
00:03:10,240 --> 00:03:20,865
According to the definition provided in the IEC60044-1 standard, the ratio error is represented as follows:

21
00:03:21,021 --> 00:03:27,427
ALF or Fs is where the composite error is 5% or 10%.

22
00:03:28,053 --> 00:03:44,069
According to the definition, ALF or FS is where Ipse/Ipn equals 5% or 10% of Ip/N .

23
00:03:45,459 --> 00:04:01,161
In indirect method according to the definition of ALF or FS which are also show as ALFi and FSi

24
00:04:02,880 --> 00:04:14,677
is where of Iext/Iout=0.1 .The same method is also used in the software

25
00:04:14,912 --> 00:04:19,130
Software Method for Calculating ALF and Fs

26
00:04:19,365 --> 00:04:30,068
In the software, to estimate Fs and ALF, the saturation curve and the relationship between the current and voltage of the parallel branch are used.

27
00:04:30,693 --> 00:04:34,599
To calculate the composite error using the indirect method (disregarding the ratio error)

28
00:04:34,834 --> 00:04:42,255
it can be said that the parallel branch current is the cause of the composite error between the primary and secondary sides

29
00:04:42,490 --> 00:04:54,755
Therefore, to ensure that the composite error at Fs times the rated current is 10%, the parallel branch current must be 10% of the output current

30
00:04:55,414 --> 00:05:03,695
In such conditions, the parallel branch voltage is also equal to Fs times the parallel branch voltage

31
00:05:03,930 --> 00:05:09,945
under conditions where the rated current passes through the CT terminal at the nominal load:

32
00:05:10,257 --> 00:05:18,694
According to the provided relationship, for a specified ALF (Fs), there is a line with a constant slope

33
00:05:19,164 --> 00:05:27,132
The intersection of this line with the saturation curve indicates the point where the CT’s composite error is 10%.

34
00:05:28,695 --> 00:05:40,961
By dividing the obtained voltage by the nominal impedance, the output current is obtained, and its ratio to the rated current will correspond to ALF (Fs)
