﻿1
00:00:19,297 --> 00:00:22,187
CT and PT Turns Ratio

2
00:00:23,672 --> 00:00:27,265
Calculation of CT and PT Turns Ratio

3
00:00:28,906 --> 00:00:34,922
The first point to consider when testing the transformation ratio of CT (Current Transformer) and PT (Potential Transformer)

4
00:00:35,313 --> 00:00:42,657
is that the accuracy class is defined for the working conditions of nominal burden and nominal current for these transformers

5
00:00:42,812 --> 00:00:48,749
For example, for a CT with a 0.5 accuracy class and a 5 VA burden

6
00:00:48,906 --> 00:00:54,765
the transformation ratio error will be a maximum of 0.5% at 1 A current

7
00:00:55,000 --> 00:01:00,234
assuming a 5 VA load is connected to the CT terminal.

8
00:01:00,547 --> 00:01:09,531
A common method used for testing in substations is to short-circuit the CT secondary and inject current (typically 20%) into the primary

9
00:01:09,688 --> 00:01:14,610
measure the current flowing through the secondary, and record the transformation ratio

10
00:01:14,921 --> 00:01:24,140
For PT, the usual method involves applying voltage (2-12 kV) to the PT primary and measuring the open-circuit voltage at the PT secondary

11
00:01:24,375 --> 00:01:32,265
As evident from the common testing methods, these transformers are not tested under their actual working conditions

12
00:01:32,578 --> 00:01:38,437
and the tests merely determine the "turns ratio" between the primary and secondary

13
00:01:38,828 --> 00:01:50,312
which may be outside the designed accuracy class. Therefore, to determine the transformation ratio error, the test must be conducted under different conditions

14
00:01:51,797 --> 00:02:03,437
For testing the transformation ratio and accuracy class of the CT under different loads and currents, voltage is applied to the secondary, and the primary voltage is measured

15
00:02:04,099 --> 00:02:10,036
In the first stage of this test, the "turns ratio" between the primary and secondary is obtained

16
00:02:10,271 --> 00:02:17,615
The voltage for this stage of the test is calculated by dividing the nominal burden by the nominal secondary current

17
00:02:17,849 --> 00:02:24,958
In addition to this voltage, half and double of it are also applied to achieve better measurement accuracy

18
00:02:25,193 --> 00:02:29,099
 By applying higher voltages, the CT turns ratio is obtained

19
00:02:29,256 --> 00:02:35,974
At this stage, the transformation ratio error must be calculated at various burdens and currents (based on nominal current)

20
00:02:36,599 --> 00:02:44,255
For example, transformation ratio error calculations are provided for three different scenarios

21
00:02:44,568 --> 00:02:47,458
1) 100% current and nominal burden.

22
00:02:52,303 --> 00:02:56,677
2) 100% current and 50% nominal burden.

23
00:02:59,568 --> 00:03:03,474
3) 50% current and 50% nominal burden.

24
00:03:04,099 --> 00:03:12,224
Using this calculation method, the CT transformation ratio error can be obtained under various current and burden conditions

25
00:03:12,771 --> 00:03:14,333
PT Testing

26
00:03:14,724 --> 00:03:20,427
For PT testing, the turns ratio between the PT primary and secondary must first be determined

27
00:03:20,818 --> 00:03:28,786
To do this, apply 450V to the PT primary, and measure the open-circuit voltage at the PT secondary

28
00:03:29,256 --> 00:03:33,943
. In this way, the "turns ratio" between the primary and secondary is obtained

29
00:03:36,521 --> 00:03:41,599
In the next step, the transformation ratio error at different burdens must be determined

30
00:03:42,146 --> 00:03:51,599
. For example, transformation ratio error calculations are provided for two different scenarios, assuming a secondary resistance of 0.1 ohms

31
00:03:51,990 --> 00:03:54,411
1) 100% nominal burden.

32
00:03:58,084 --> 00:04:00,427
2) 50% nominal burden.
