CT Test Wiring Guide Using the Instrument Module

2
00:00:22,551 --> 00:00:25,972
The instrument module is designed as a user interface

3
00:00:26,761 --> 00:00:30,712
The capacity of these modules is the same as the device

4
00:00:30,779 --> 00:00:35,247
but with the difference that by performing the wiring once

5
00:00:35,412 --> 00:00:43,724
you can perform all the related room tests in a much shorter time and with a much lower wiring error rate

6
00:00:43,884 --> 00:00:49,880
First, Install the Base module. Install the Base module on the front panel of the device

7
00:00:50,022 --> 00:00:54,982
so that the male banana of the Base module fits into the indicated section

8
00:00:55,115 --> 00:01:04,134
Then install three batteries with the specifications of 18650 lithium battery

9
00:01:04,491 --> 00:01:08,865


10
00:01:08,919 --> 00:01:12,365
 4.2 volts, 2000 milliampere hours, in order from right to left in the indicated state

11
00:01:12,568 --> 00:01:22,490
. Place the corresponding module, which in this test is the CT module, on the Base module and then tighten the three screws of the CT module

12
00:01:24,787 --> 00:01:32,372
 Finally, turn on the module. Check the battery charge. You will see 4 squares that indicate the battery charge percentage

13
00:01:32,498 --> 00:01:36,575
 with each square indicating 25% of the battery charge

14
00:01:36,935 --> 00:01:44,213
When you connect the battery charger to the module, the corresponding square will start blinking according to the battery charge percentage

15
00:01:44,342 --> 00:01:48,232
 When the battery is fully charged, all the squares will start blinking

16
00:01:48,373 --> 00:01:53,388
Warning: Do not use the module to perform tests while the batteries are charging

17
00:01:53,545 --> 00:02:01,857
The reason for using a battery on the module is to isolate the module power supply from the device power supply and eliminate noise

18
00:02:02,029 --> 00:02:03,333
Important notes

19
00:02:03,670 --> 00:02:09,505
The eye sensor of the Base module must be completely placed on the Error light of the device

20
00:02:09,630 --> 00:02:12,669
The first time the batteries are installed on the module

21
00:02:12,842 --> 00:02:16,880
even if they are fully charged, due to the defined protection

22
00:02:17,138 --> 00:02:23,208
the charger must be connected to the module once for the module to turn on

23
00:02:31,771 --> 00:02:38,107
To perform the calibration, enter the Setting window from the software start page.In the Hardware tab

24
00:02:38,263 --> 00:02:44,435
click Apply Calibration Instrument and after 5 seconds the calibration will be completed

25
00:02:44,732 --> 00:02:46,880
CT Room Settings

26
00:02:47,107 --> 00:02:52,357
Enter the CT room and set the Type Device to 205AMT

27
00:02:52,560 --> 00:03:00,013
In the Accessories section, set Version Mode Esay to 01Ver_205_CT

28
00:03:00,240 --> 00:03:08,958
Module calibration is only required once and should only be performed if the device or base module has been replaced

29
00:03:09,131 --> 00:03:13,974
Wiring: Connect 1Cp to the positive terminal of the capacitor box

30
00:03:18,334 --> 00:03:22,286
Connect CapCom to the negative terminal of the capacitor box

31
00:03:26,342 --> 00:03:29,529
Connect 1Vs to 1S of the CT

32
00:03:39,638 --> 00:03:42,544
Connect S1 to S1 of the CT

33
00:03:49,803 --> 00:03:53,825
Connect 2Vs to S2 of the CT

34
00:04:01,849 --> 00:04:05,075
Connect S2 to S2 of the CT

35
00:04:13,271 --> 00:04:19,232
Finally, connect 1Vp to 2Vp of the module after passing through the CT

36
00:04:19,354 --> 00:04:26,177
After completing the wiring, perform the remaining steps of the test without considering the old wiring
