00:00:18,516 --> 00:00:20,625
Secondary Burden Test

2
00:00:21,016 --> 00:00:25,468
In this test, the burden connected to the secondary side of the CT is measured

3
00:00:25,938 --> 00:00:30,860
. By injecting AC current and measuring the AC voltage through the "Binary/Analog Input,"

4
00:00:31,016 --> 00:00:37,109
and then dividing voltage by current, the impedance value "Z" and its phase angle are obtained.

5
00:00:37,266 --> 00:00:43,750
. From these, the resistance "R" and reactance "X" of the secondary circuit can be determined

6
00:00:44,141 --> 00:00:50,390
To perform this test, you need to enter the test current and test duration in the "Test setting" section

7
00:00:50,547 --> 00:00:54,218
specifically in the "I test" and "State Time" fields

8
00:00:54,688 --> 00:00:59,062
The current limit for this test is set to 32 amps. However,

9
00:00:59,375 --> 00:01:06,406
, injecting 5 amps is sufficient for 5 A CTs,

10
00:01:07,422 --> 00:01:14,531
and 1 amp for 1 A CTs.In the "Hardware Config" section, you can change the current injection output via the "Wiring Type" setting

11
00:01:15,078 --> 00:01:21,875
The voltage measurement input can be selected from the "Voltmeter Contact" dropdown, depending on the CT's resistance

12
00:01:22,500 --> 00:01:26,015
. Inputs 1 to 7 or input 10 may be used.

13
00:01:26,563 --> 00:01:33,829
If you choose inputs 1 to 7, the "Voltmeter Type" can be set to "wet" depending on the voltage across the selected input

14
00:01:34,844 --> 00:01:39,921
Input 10 should be used when the measured voltage is less than 200 millivolts

15
00:01:40,547 --> 00:01:47,890
Current measurement during this test is done either via the actual current ("Actual") or through "Input 9"

16
00:01:48,828 --> 00:01:55,234

By selecting the "Insert Rows" option, test rows are added based on the number of taps defined

17
00:01:55,469 --> 00:02:01,875
defined in the "Test Object" section.If more than one "Core" has been entered in the "Test Object",

18
00:02:02,031 --> 00:02:08,906
you can use the "Insert Mode" to add all of them to the test rows in either "Up" or "Down" order

19
00:02:09,334 --> 00:02:15,036
Alternatively, you can add a specific "Core" to the list by selecting "Specific Core".

20
00:02:15,349 --> 00:02:21,286
In the newer versions of the software, the option "Don’t change hardware settings" has been removed

21
00:02:21,678 --> 00:02:28,786
Instead, you can use the "Manually" option, which is available under both "Wiring Type" and "Voltmeter Contact".

22
00:02:29,256 --> 00:02:35,661
After entering the information in the "State Setting" section, follow the wiring diagram shown

23
00:02:48,162 --> 00:02:54,412
Note that you can double-click the image to enlarge it for better visibility

24
00:03:11,365 --> 00:03:21,208
To perform this test, the first step is to disconnect the CT from all components that transmit current to the measuring equipment

25
00:03:52,849 --> 00:03:57,615
. In the default wiring configuration, connect the output phase currents

26
00:03:58,162 --> 00:04:03,630
"Ia1" and "Ian" to the current-carrying path of the CT.

27
00:04:04,178 --> 00:04:12,380
To measure the "AC" voltage, connect "Binary/Analog Input 1" to the test path, ahead of the current injection connectors.

28
00:05:01,490 --> 00:05:07,661
To run the test, select one of the rows in the table, right-click on it, and choose "Apply Test"

29
00:05:07,818 --> 00:05:10,786
This action applies the current settings

30
00:05:11,178 --> 00:05:16,178
test duration, and all relevant hardware configurations under "Hardware Config"

31
00:05:16,646 --> 00:05:21,177
including the device’s outputs and "Binary/Analog Inputs".

32
00:05:21,802 --> 00:05:30,553
Alternatively, after selecting the desired row, you can also start the test by clicking the "Run" button in the top toolbar

33
00:05:31,568 --> 00:05:34,224
Running the Test and Analyzing the Results

34
00:05:34,536 --> 00:05:39,223
Once the wiring is complete and the current and time values have been set

35
00:05:39,302 --> 00:05:43,364
, right-click on a row and select "Apply Test" to start the test.

36
00:05:43,678 --> 00:05:48,990
 If you need to adjust the current or test time, make the changes in the "Test Setting" section,

37
00:05:49,224 --> 00:05:52,662
then click "Insert Rows" to add a new test row

38
00:05:53,053 --> 00:05:57,661
. You can also directly modify the test current in the "I test" column of each row.

39
00:05:58,131 --> 00:06:08,208
After running the test, in the "Hardware Configuration" section, under the "Analog Output" tab, you will see that the device wiring is set to

40
00:06:08,599 --> 00:06:16,255
"6×32A" and "Binary/Analog Input 1" has been activated for voltage measurement.

41
00:06:25,099 --> 00:06:31,271
For a more detailed test analysis, you can use the "Table View," "Detail View," and "Signal View" windows.

42
00:06:31,818 --> 00:06:39,318
Once you open the "Table View" window, you will see that a "State" with a frequency of "50Hz" has been created,

43
00:06:39,709 --> 00:06:43,771
in accordance with the data entered in the "State Setting" section

44
00:06:44,084 --> 00:06:49,786
If you need more detailed information from the "Table View," you should use the "Detail View" window.

45
00:06:51,584 --> 00:07:00,255
In "Signal View," you can observe the current waveform and its "Actual" value, as well as the voltage measured by "Binary/Analog Input."

46
00:07:00,568 --> 00:07:09,396
." Using the "Actual" current and voltage waveforms in "Signal View," you can verify the correctness of the connector connections.

47
00:07:09,631 --> 00:07:14,474
. In the "Result" section, after the test is completed, the results will be displayed.

48
00:07:14,709 --> 00:07:20,880
These results include "I test act," the actual injected current, "Vmeas.,"

49
00:07:21,271 --> 00:07:28,458
the measured voltage, "Z," the impedance, "Angle," the impedance angle

50
00:07:28,771 --> 00:07:33,224
and finally, the values of "R" and "X" calculated using the formulas

51
00:07:33,615 --> 00:07:41,193
"Z Cos(φ)" and "Z Sin(φ)." In the "Burden @ Itest" field, the burden

52
00:07:41,428 --> 00:07:47,756
that the secondary "CT" can provide during the test current is calculated and entered by the software.

53
00:07:47,990 --> 00:07:54,708
The last column shows "cos φ." Finally, after the test is completed,

54
00:07:55,021 --> 00:08:02,443
the evaluation results need to be added to the report, which can be done by selecting "Add To Report" during equipment testing.

55
00:08:02,990 --> 00:08:06,583
If you want to include specific parts of the evaluation

56
00:08:06,896 --> 00:08:12,130
evaluation in the report or edit the report, you must use the "Add To Report" gear icon.

57
00:08:12,678 --> 00:08:19,240
By clicking on this gear, the items that can be added to the "Report" will be checked

58
00:08:20,178 --> 00:08:24,552
and if you don't need any of these items, you can uncheck them

59
00:08:25,256 --> 00:08:31,661
Please note that after each test, the results are not automatically added to the report

60
00:08:32,131 --> 00:08:39,396
You must manually add the test results to the output report by clicking "Add To Report" before selecting "Clear Test."

61
00:08:40,803 --> 00:08:45,803
Additionally, if you want to adjust the settings for displaying the table columns

62
00:08:46,427 --> 00:08:50,646
on the test page or in the report, you can right-click on the table

63
00:08:51,037 --> 00:08:55,568
go to "Show/Hide," and if you don't need a specific column

64
00:08:55,724 --> 00:08:59,552
you can uncheck it in the "Report" or "Table" section.

65
00:09:00,021 --> 00:09:07,833
If the "Burden" of the path is low and you need a more accurate measurement, you can set the "Voltmeter Contact" to "Input 10."

66
00:09:08,381 --> 00:09:15,958
Or, if "Input 1" is experiencing issues, you can select a different input in the "Voltmeter Contact" section.

67
00:09:16,271 --> 00:09:24,943
Also, to change the injected current output, you can select the desired current output from the "Wiring Type" section

68
00:09:25,646 --> 00:09:32,833
Furthermore, if you want to conduct the test with different settings—for example, you want the current injection to be set to

69
00:09:33,068 --> 00:09:42,130
 "1×128A" and voltage measurement to be done with a "Sample rate" of 1.2 milliseconds

70
00:09:42,521 --> 00:09:48,380
you can set the "Wiring Type" and "Voltmeter Contact" to "Manually," open "Hardware Configuration,"

71
00:09:48,537 --> 00:09:54,865
and apply the necessary changes. Then you can perform the test with the new settings.

72
00:11:18,180 --> 00:11:21,460
It is important to note a few things

73
00:11:21,538 --> 00:11:28,256
If the current injected by the device ("Actual Current") differs significantly from the set current,

74
00:11:28,569 --> 00:11:33,959
the wiring resistance is high, and in this case, two actions can be taken

75
00:11:34,273 --> 00:11:40,445
1) Reduce the injected current. 2) Change the wiring to series

76
00:11:41,227 --> 00:11:47,867
series current sources to provide a higher "Burden." Another point is that a reading of zero

77
00:11:48,179 --> 00:11:57,631
for "Actual Current" indicates an open current injection path; in this case, the connector connections should be checked.
