﻿1
00:00:22,018 --> 00:00:24,914
Introducing “Current Transformer (CT)” room:

2
00:00:25,001 --> 00:00:31,890
One of the equipment which can be tested by “AMT105” device of Vebko Company is current transformer or “CT”.

3
00:00:32,160 --> 00:00:39,755
“CTs” are very useful for converting the high current of an electrical system to a current measurable by relays and measurement devices.

4
00:00:39,889 --> 00:00:44,319
Generally, there are two types of “CTs” including “Measuring” and “Protection”.

5
00:00:44,344 --> 00:00:51,814
The difference between these two types is in their turns ratio accuracy or accuracy class as well as saturation level.

6
00:00:52,013 --> 00:00:59,395
Since “Measuring” “CT”s are used in measurement devices, in the event of a fault, if the current entered this equipment increases too much,

7
00:00:59,420 --> 00:01:08,906
the equipment might be damaged.  But “Protection” “CTs” are used in relays and since the performance of a relay is in accordance with the amount of fault current,

8
00:01:08,931 --> 00:01:16,332
these “CTs” need to be able to move the fault current of the network to the secondary with the least possible error.

9
00:01:16,357 --> 00:01:22,123
In drawing the equivalent circuit of this transformer, the “CT” turns ratio is “1:N”.

10
00:01:22,148 --> 00:01:33,400
“Rp” and “Xp” equal the “CT” transformed to the secondary while “Xs” and “Rs” indicate the resistance and “CT” secondary leakage flux.

11
00:01:33,425 --> 00:01:48,409
In parallel branch, “Re” and “Rh” are indicators of losses of eddy current and the hysteresis respectively and “L” indicates the magnetization inductance or “CT” secondary self-inductance.

12
00:01:48,867 --> 00:02:01,050
In the equivalent “CT” circuit, unlike normal transformers, the parallel branch is located in the secondary side and this very branch is the reason for core saturation in high currents.

13
00:02:01,075 --> 00:02:08,817
Since the primary resistance and leakage flux in “CT” is insignificant, “RP”, “Xp” and “Xs” can be ignored.

14
00:02:08,842 --> 00:02:14,787
By clicking on “Current Transformer (CT)” on the start page of the software, the “CT” test room opens.

15
00:02:14,812 --> 00:02:26,312
In tests performable by the “AMT 105” device, RCT, saturation curve and the turns ratio are achieved with two methods of voltage or current.

16
00:02:26,337 --> 00:02:33,401
Moreover, measurement test of the burden connected to the “CT” secondary is performable by this device as well.

17
00:02:33,426 --> 00:02:41,272
“Test Object” and “Megger” tabs are used to enter the nominal information of “CT” and the results of “Megger” test respectively.

18
00:02:41,297 --> 00:02:42,161
“Test Object” tab:

19
00:02:42,200 --> 00:02:46,902
Any module to be able to perform a test needs some information about the equipment.

20
00:02:46,927 --> 00:02:49,871
This information is entered in “Test Object” section.

21
00:02:49,896 --> 00:02:56,913
The general information about “CT” which should be recorded in the report is entered in “General Information” section.

22
00:02:57,043 --> 00:03:04,465
The company’s title, the country, name and the address of the substation and installation place of “CT”,

23
00:03:04,490 --> 00:03:13,787
title of the manufacturer of “CT”, “Type” of “CT”, serial number of “CT”, title of the feeder on which “CT” is installed, phase number,

24
00:03:13,812 --> 00:03:24,885
“IEC” standard number written on the plaque of “CT”, number of cores of “CT”, number of taps of “CT” and additional information are entered in “Company”,

25
00:03:24,910 --> 00:03:35,036
“CT Serial Number”, “Feeder/Bay”, “Phase”, “IEC-ID”, “Core Number”, Tap” and “Additional Information” fields respectively to be added to the report.

26
00:03:35,061 --> 00:03:45,249
In “Extra Data” section, the test run date in A.D., the information of the performer of the test and the information of the supervisor are entered in “Date”,

27
00:03:45,274 --> 00:03:48,488
“Tested By” and “Approved By” fields respectively.

28
00:03:48,513 --> 00:03:53,796
By checking “Easy Mode” option in “Accessories” section, the wiring of the tests changes.

29
00:03:53,821 --> 00:03:59,088
This wiring is based on the board designed by Vebko Company for the “CT” test.

30
00:03:59,786 --> 00:04:13,778
The mentioned board is located on the front panel of the device and there are some relays placed on it which automatically manage the wirings of the front panel of the device which makes performing the test easier.

31
00:04:13,803 --> 00:04:23,289
The main information of the “CT” which has influence on the calculations of knee point and evaluation of the tests are entered in “Test Setting” section.

32
00:04:23,314 --> 00:04:29,011
The CT core type is selected from among “Measuring” and “Protection” in “Core Type” field.

33
00:04:29,277 --> 00:04:35,344
The accuracy class of the “CT” is specified in “Class” field. If the type of “CT” is “Measuring”,

34
00:04:35,369 --> 00:04:46,796
the accuracy classes available in drop-down field such as “0.5s” mean that in 100 to 120 percent of the nominal current crossing the primary “CT”,

35
00:04:46,962 --> 00:04:51,602
there may be measurement fault up to this percentage max.

36
00:04:51,738 --> 00:05:05,019
If the “CT” is “Protection” there are different accuracy classes one of which is selected according to the “CT” type and the information required for every “CT” is displayed in “Nominal Values” section.

37
00:05:05,044 --> 00:05:17,037
For example, if “10P or 10Pr” is selected as accuracy class, based on “ALF” in “CT”, there may be up to 10 percent error in “ALF” times the primary nominal current.

38
00:05:17,062 --> 00:05:27,188
This means that if the “ALF” for a “CT” with an accuracy class of “10P” is “20”, in 20 times of the nominal current in the “CT” primary,

39
00:05:27,213 --> 00:05:33,866
if the nominal “Burden” is connected to its secondary, there may be up to 10 percent measurement deviation.

40
00:05:33,891 --> 00:05:38,948
In “Applied Standard” field, the standard used for the “CT” is determined.

41
00:05:38,973 --> 00:05:47,092
In “Class Multiplier” field, a factor is entered between “0.2” and “1” to be multiplied by accuracy class.

42
00:05:47,278 --> 00:05:52,316
This factor makes the “CT” accuracy class harder in turns ratio test.

43
00:05:52,341 --> 00:06:04,780
This means that if the “CT” accuracy class equals “10P” and its accuracy factor equals “0.8”, the maximum “CT” error in “ALF” times the primary nominal current is 8 percent.

44
00:06:06,353 --> 00:06:12,866
In “Nominal Values” section, the nominal values are entered according to the type and class of the “CT”.

45
00:06:12,891 --> 00:06:25,940
Primary current, secondary current, nominal frequency, apparent power and secondary resistance in the temperature specified on its plaque (usually 75 degrees) are entered in their related fields.

46
00:06:27,209 --> 00:06:39,405
“Fs” or “Security Factor” indicates the measuring “CT” security factor and is defined as the ratio of instrument limit primary current to the rated primary current.

47
00:06:39,430 --> 00:06:45,074
Note that the actual “Fs” value is dependent on the burden of the “CT”.

48
00:06:45,233 --> 00:06:55,011
If the burden connected to the “CT” is lower than its nominal burden, the “Fs” value is increased and the “CT” is saturated in higher current.

49
00:06:55,036 --> 00:07:02,633
For example, when the “Fs” of a “CT” is “5”, this “CT” is saturated in 5 times the nominal current.

50
00:07:02,911 --> 00:07:11,181
“ALF” or “Accuracy Limit Factor” is defined as the proportion of accuracy limit of the primary current to the nominal current.

51
00:07:13,040 --> 00:07:25,500
The value of actual “ALF” is dependent to the burden connected to the protective “CT” secondary and its value decreases as the value of the connected “Burden” increases. “CT” Power factor,

52
00:07:25,525 --> 00:07:35,226
apparent power of the actual burden connected to the “CT” and the ambient temperature which equals 25C are entered in “Cos (phi)”,

53
00:07:35,251 --> 00:07:38,773
“Actual Burden” and “Ambient Temperature” fields respectively.

54
00:07:38,798 --> 00:07:52,239
If the “CT” accuracy level is “X or PX”, “PXR”, “TPX”, “TPY” and “TPZ”, options such as “Exciting Current (Ie)”, “Kssc”, “Rb”, etc.

55
00:07:52,264 --> 00:07:57,063
are added to “Nominal Values” section which should be entered from the “CT” plaque.

56
00:07:57,088 --> 00:08:01,782
This information is used to estimate the knee point for saturation test.

57
00:08:01,893 --> 00:08:12,352
To view how these parameters work you can go to “Excitation Test” tab and by holding the “Mouse” pointer on the estimated knee voltage, view its relation.

58
00:08:12,377 --> 00:08:20,377
In “Winding Material” field in “Temperature Correction” section, the kind of material used in the coils is selected from among “Copper” and “Aluminum”.

59
00:08:21,299 --> 00:08:27,280
In “Winding Temp” field, the current temperature of the “CT” coil is entered. Also, in “Reference Temp.”

60
00:08:27,305 --> 00:08:35,941
field, the reference temperature is entered to measure the resistance value of the coils so it can be used to correct the values measured in different temperatures.

61
00:08:35,966 --> 00:08:45,053
Normally, the reference temperature is written on the “CT” plaque in front of the secondary coil resistance which usually equals 75 degrees.

62
00:08:45,311 --> 00:08:57,023
. In “Correction Factor” field, the temperature correction factor is calculated in accordance with the ambient temperature, reference temperature as well as the material of the coil which is not editable.

63
00:08:57,341 --> 00:09:06,181
In some cases, in the “Test Sheet” which comes with the “CT”, the coil resistance is measured in a temperature other than the one mentioned on the plaque.

64
00:09:07,772 --> 00:09:15,240
If you wish to enter the value of this resistance, by checking “R Man.(Ref.Temp.)” option, you can enter the resistance.

65
00:09:15,421 --> 00:09:24,680
In this case, this resistance and its temperature are considered as the reference and are added to the results table in the “R Man.(Ref.Temp.)”

66
00:09:24,705 --> 00:09:35,413
column in “Resistance Test” tab that the temperature which is measured by the manufacturer is based on the resistance and is measured and showed in this test.

67
00:09:36,113 --> 00:09:47,912
The number entered in “RMS Accuracy” box in “Number of Period” field, shows the number of cycles that used. By default, this number is set at “1”.

68
00:09:47,982 --> 00:09:57,262
As the number of cycle’s increases, the software uses more cycles in “AC” mode and more time in “DC” mode for calculations.

69
00:09:57,339 --> 00:10:07,374
By doing so, the number of calculations increases and the software speed is decreased but the result of the test will be more precise.

70
00:10:08,425 --> 00:10:12,204
By clicking “Add to Report” option at the bottom of the page,

71
00:10:12,229 --> 00:10:19,287
this information is added to the output report and then a message saying “The Report was added to the list” is displayed.

72
00:10:19,312 --> 00:10:26,179
By selecting “Report” window from the box at the right side, it is possible to view the output report.

73
00:10:26,459 --> 00:10:33,040
By clicking on “Delete Report” option, the report added from “Report” window is removed from “Delete from Report” window.

74
00:10:33,065 --> 00:10:43,964
If “Set as default” option is selected, the entered information is saved and set as default and by opening “Current Transformer (CT)” room, this information is displayed.

75
00:10:43,989 --> 00:10:58,670
For the instructional videos of this section, a 10P10 protective CT with 500/1 as conversion ratio, 50 Hz as frequency and 15 Amps as Burden is going to be tested.
