00:00:19,500 --> 00:00:21,676
AMT VCC Room

2
00:00:21,701 --> 00:00:26,460
This room is designed to test different relays in the shortest possible time and in the form

3
00:00:26,485 --> 00:00:33,078
of using standard scenarios based on periodic testing regulation of Iranian power grid protection systems, it is possible.

4
00:00:34,644 --> 00:00:39,201
You will see two windows by entering to the AMT VCC room.

5
00:00:39,334 --> 00:00:44,765
VCC Panel, which is actually the main window for selecting functions and test management.

6
00:00:44,790 --> 00:00:49,070
VCC Report View, will show you the relay test report.

7
00:00:50,107 --> 00:00:54,492
In the first step, simply upload the default template to the desired relay.

8
00:00:54,740 --> 00:00:58,343
This will be done by selecting an icon with the letter L.

9
00:00:58,368 --> 00:01:02,359
These templates are available in two categories for each relay.

10
00:01:02,384 --> 00:01:06,984
In the Fast Test section, you will see a limited number of tests.

11
00:01:07,009 --> 00:01:10,930
For example, in quick tests, there is no transient test.

12
00:01:10,955 --> 00:01:16,710
However, by selecting the other option, there will be a complete set of tests in front of you.

13
00:01:16,735 --> 00:01:24,516
As you can see, by loading the template, a variety set of tests for different functions will be in front of you.

14
00:01:24,541 --> 00:01:30,093
In the Nodes section, you'll see available subcategories to test each function.

15
00:01:30,118 --> 00:01:37,468
In the Summary column, a summary of the test status and whether it is successful or unsuccessful will be displayed.

16
00:01:37,493 --> 00:01:46,734
The three options of Inheriet Xrio, Inherit Hardware Config and Inherit Report Settings by being active, respectively,

17
00:01:46,759 --> 00:01:52,132
will make the user's chosen function inherit all settings from Xrio,

18
00:01:52,157 --> 00:01:55,085
hardware settings and report settings.

19
00:01:55,296 --> 00:02:01,620
However, by disabling them, you can apply the settings to each one as you wish and manually.

20
00:02:01,645 --> 00:02:08,404
The Open UI option will also allow you to manage the opening of the related window to each test.

21
00:02:09,647 --> 00:02:13,125
If you select Advanced View from the above section,

22
00:02:13,150 --> 00:02:21,414
more elements such as test window status, reporting status, test progress rate, and more will be observed.

23
00:02:21,439 --> 00:02:25,782
In the Root subset, the Xrio file is located first.

24
00:02:25,960 --> 00:02:29,625
By selecting this option and clicking the Open option,

25
00:02:29,650 --> 00:02:35,953
you can upload the Xrio received from the relay, which actually fits the active functions set.

26
00:02:35,978 --> 00:02:41,117
You can access the details by clicking on any other option and selecting Open.

27
00:02:41,142 --> 00:02:49,407
For example, by clicking HardwareConfigFile you can view and edit the default hardware configuration for current and voltage injection,

28
00:02:49,432 --> 00:02:53,125
as well as inputs and outputs of the test device.

29
00:02:53,150 --> 00:02:57,414
The Start Note option, which is located before testing each function,

30
00:02:57,439 --> 00:03:02,576
also provides the user with explanations to guide the test further.

31
00:03:04,044 --> 00:03:10,068
In this section you can enter the information that will actually be my test guide during the test.

32
00:03:10,093 --> 00:03:15,850
For example, you can place a note in the overcurrent protection function that indicates the overcurrent

33
00:03:15,875 --> 00:03:24,685
protection in your relay is an emergency type and can only be activated by blocking distance protection and can be tested.

34
00:03:25,475 --> 00:03:31,678
In the top part of the page, you can add or remove tests by clicking Add Item or Remove.

35
00:03:31,703 --> 00:03:35,535
For example, here we remove Switch Onto Fault,

36
00:03:35,560 --> 00:03:45,166
Recloser and VTS tests due to the inactivity of these functions in our relay as well as the shortening of the testing process.

37
00:03:45,191 --> 00:03:50,872
       In addition, you can make it possible to change settings or points by disabling Inheriet Xrio.

38
00:03:51,036 --> 00:03:53,863
For example, for overcurrent protection,

39
00:03:53,888 --> 00:04:03,934
we applied settings manually and placed different points on the characteristic curve than those designed in accordance with XRIO.

40
00:04:10,255 --> 00:04:16,465
In the first stage of testing, Wiring Test is designed to check the current and voltage values

41
00:04:16,490 --> 00:04:21,152
injected from the device on the relay to ensure the correct wiring.

42
00:04:27,151 --> 00:04:31,816
Electrical Test is another option that, with three state including PreFault,

43
00:04:31,841 --> 00:04:40,379
Fault and PostFault, checks the relay conditions in different situations and ensures you register trip when a fault occurs.

44
00:04:42,088 --> 00:04:43,301
As mentioned above,

45
00:04:43,326 --> 00:04:53,520
a set of tests for different functions is designed in the default template but it is possible to remove, add and manage the tests accurately for the user.

46
00:04:53,545 --> 00:04:57,902
In this way, you can determine the priority of performing different tests,

47
00:04:57,927 --> 00:05:00,957
disable some tests, and even more precisely,

48
00:05:00,982 --> 00:05:04,871
specify which tests to do with what values and in what range.

49
00:05:04,896 --> 00:05:11,253
You can check how the test is designed by clicking on each test and selecting Open.

50
00:05:11,722 --> 00:05:20,652
For example, you can view or edit points on the characteristic by selecting Zone Reaches for the Distance function.

51
00:05:24,957 --> 00:05:26,418
By running the test,

52
00:05:26,443 --> 00:05:28,965
you can check different functions.

53
00:05:28,997 --> 00:05:32,769
Finally, by right-clicking on the VccReportView window,

54
00:05:32,802 --> 00:05:39,418
you can have a complete management of the items that are going to be displayed in the report.

55
00:05:39,744 --> 00:05:40,731
For example,

56
00:05:40,756 --> 00:05:47,020
here we will perform the Micom P444 relay test in AMT VCC room.

57
00:05:47,461 --> 00:05:53,277
In the Configuration section, you can see the active or inactive status of the functions.

58
00:05:53,302 --> 00:06:00,973
In the group 1 subset of settings, you can also see details about each function's settings and values.

59
00:06:00,998 --> 00:06:07,691
In the PSL relay section, we also configured the inputs, outputs and leds for different functions.

60
00:06:07,716 --> 00:06:10,738
Now it's time to save the XRIO settings file.

61
00:06:10,763 --> 00:06:18,684
In the next step, we re-enter the AMT VCC room and first load the template related to the P444 relay.

62
00:06:26,924 --> 00:06:35,285
Now we prepare different function tests using the XRIO file that we took from the relay in the previous step.

63
00:06:35,310 --> 00:06:40,629
By running the test, you can control the test of different functions step by step.
