﻿1
00:00:19,746 --> 00:00:21,549
“Offload” test of the meter:

2
00:00:21,574 --> 00:00:26,546
To test Energy Meters, AMT Transducer & Meter room can be used.

3
00:00:26,571 --> 00:00:31,078
On “Start” page, the “AMT Transducer & Meter” room software is opened.

4
00:00:31,103 --> 00:00:36,440
This room is comprised of the two main windows of “Test View” and “Transducer Characteristic”;

5
00:00:36,465 --> 00:00:44,265
in “Test View” window, it is possible to perform a “Shot Test” for various quantities and compare the results with the meter characteristic.

6
00:00:45,441 --> 00:00:53,107
To begin the test, after completing the information in “Device” in “General Test Object” window, double click on “Transducer” option.

7
00:00:53,132 --> 00:00:57,842
On “Transducer Properties” page, it is possible to view a set of functions.

8
00:00:57,867 --> 00:01:04,865
To test the meter, two functions of “Wh” and “Varh” are used; here, “Wh” is selected.

9
00:01:04,890 --> 00:01:13,015
By selecting “Injection” option in “Input” section, it is possible to perform the “Offload” test of the meter by injection from the device.

10
00:01:13,040 --> 00:01:18,804
The other option is “Read from Binary” which is used to perform an “On Load” test of the meter.

11
00:01:18,829 --> 00:01:26,960
By selecting this option, it is necessary to enter the values into the inputs of the device using the clamps and interface cables.

12
00:01:26,985 --> 00:01:32,398
In “Output” section, it is possible to specify the type of the output received from the meter.

13
00:01:32,423 --> 00:01:35,281
To test transducers and their corresponding outputs,

14
00:01:35,306 --> 00:01:44,171
by selecting “Current” or “Voltage” options, it is possible to take the output current and voltage values to the inputs 9 and 10 for measurement.

15
00:01:44,196 --> 00:01:50,601
To test the meter, if only the output values are being displayed on the screen, “Open Loop” option can be used.

16
00:01:50,626 --> 00:01:59,203
Here, “Pulse” option is used so that using the light sensor which comes with the device, the number of the output pulses of the meter is recorded.

17
00:01:59,228 --> 00:02:05,326
In „CT Star point Connection“ section, the connection related to the current transformers are specified.

18
00:02:05,351 --> 00:02:10,843
Usually and since the active power flows from the busbar toward the line, "Toward Line” option is selected.

19
00:02:10,868 --> 00:02:22,146
Selecting “Toward Line” is in accordance with the injection of the active power from the device to the equipment. If “Toward Busbar” is selected, 180 degrees are added to the angle of the current.

20
00:02:22,171 --> 00:02:32,717
In “Full Scale Error Reference” section it is possible to specify the error recording reference which can be selected from a range of zero to the maximum or negative to the positive maximum.

21
00:02:32,742 --> 00:02:39,328
If the characteristic is asymmetrical the range is from zero to the maximum while if the characteristic is symmetrical,

22
00:02:39,353 --> 00:02:42,789
it is possible to select both options for error measurement.

23
00:02:42,814 --> 00:02:51,679
As for error measurement, suppose that for a transducer with a characteristic with the maximum input of 1 amp and output of 33 milliamperes,

24
00:02:51,704 --> 00:02:57,289
for a 0/5 amp current, the output of the transducer equals 16 milliamperes.

25
00:02:57,314 --> 00:03:01,562
In such a case, the error percentage is calculated as follows.

26
00:03:01,587 --> 00:03:08,640
This means that ideally, for a 480 milliamperes input, the output equals 16 milliamperes.

27
00:03:08,665 --> 00:03:16,639
Therefore, the absolute error value equals 20 milliamperes and the error percentage equals -4 percent:

28
00:03:16,664 --> 00:03:23,906
This method is used for cases where “Full Scale Error Reference” is set at “0…+max”.

29
00:03:23,931 --> 00:03:32,017
If the characteristic is “Symmetrical”, the error calculation method should be selected from among “0..+max” and “-max…+max”.

30
00:03:32,042 --> 00:03:43,585
For the previous example, if the characteristic was symmetrical and “-max..+max” was selected, the following relation is used for “Full Scale Error” calculation.

31
00:03:43,610 --> 00:03:53,742
In "Tolerance” section, it is possible to enter the error value as an absolute or a relative value; the default values are 1 milli pulse and 0/25 percent.

32
00:03:53,767 --> 00:04:00,328
Finally, a comparison is made between these two values and the larger value is selected as the allowed error value.

33
00:04:00,353 --> 00:04:05,968
In “Number of phases” section, it is possible to specify whether the meter is single-phase or three-phase.

34
00:04:05,993 --> 00:04:09,828
The test characteristic is specified in "Characteristic Definition” section.

35
00:04:09,853 --> 00:04:16,054
Since the meter characteristic is linear, “Linear” option is selected as the “Characteristic Type” and it is uneditable.

36
00:04:16,079 --> 00:04:25,304
To specify the energy “Import” and “Export” values, it is possible to check the “Symmetrical” option so that there is a Symmetrical characteristic in both sides available.

37
00:04:25,329 --> 00:04:32,787
The “Minimum Value”, “Knee Point” and “Saturation range” fields are disabled for meter test but in “Maximum Value” section,

38
00:04:32,812 --> 00:04:39,076
it is possible to enter the amount of power and the number of pulses received in exchange for that amount of power.

39
00:04:39,101 --> 00:04:43,732
Usually, the meter factor or “c/r” is entered in this section.

40
00:04:43,773 --> 00:04:51,638
For example, the factor for a edmi mk6e meter equals 5000 Wh per pulse.

41
00:04:51,663 --> 00:04:56,085
Note that by using “Primary” and “Secondary” options at the top of the screen

42
00:04:56,110 --> 00:05:05,413
it is possible to enter the values as primary or secondary in accordance with the meter type which needs to be done considering the CT and PT conversion ratios.

43
00:05:05,438 --> 00:05:11,117
Relative” and “Absolute” options are used for displaying the absolute or relative amount of the values.

44
00:05:11,142 --> 00:05:15,203
After entering the values, “Ok” is selected to continue with the test.

45
00:05:15,228 --> 00:05:21,921
After completing the information in "Transducer Properties” section, the “Hardware Configuration” settings need to be examined.

46
00:05:21,946 --> 00:05:26,476
By opening this window, you can see that the current and voltage outputs are set by default.

47
00:05:26,501 --> 00:05:33,015
In "Binary/Analog Input” tab, you see that the Binary number 8 is selected to record the pulses of the meter by default.

48
00:05:33,040 --> 00:05:37,617
However, it is possible for the user to use any other binary if necessary.

49
00:05:37,642 --> 00:05:41,249
By clicking on “Ok”, the applied changes are saved.

50
00:05:41,274 --> 00:05:47,109
To perform a test, a point on the characteristic must be selected which can be done using two methods:

51
00:05:47,134 --> 00:05:54,554
- Entering the values in the fields of “Test Point” section which means entering the related parameters including Wh value,

52
00:05:54,579 --> 00:05:58,210
number of pulses, test performance time and frequency.

53
00:05:58,235 --> 00:06:01,695
Then, by selecting “Add”, this point is added to the test table.

54
00:06:01,720 --> 00:06:06,063
Holding down the “CTRL” key and then clicking on the meter characteristic curve.

55
00:06:06,088 --> 00:06:11,743
On “Test View” page, by clicking on “Advanced View”, a page opens where it is possible to enter the voltage,

56
00:06:11,768 --> 00:06:18,327
current and their angle as well as the cos⁡∅ to be injected by the device.

57
00:06:18,352 --> 00:06:26,789
Moreover, in “Waveform” section it is possible to add phase shift and DC offset to the harmonic specified signals.

58
00:06:26,814 --> 00:06:29,586
After specifying these values, apparent,

59
00:06:29,611 --> 00:06:40,594
active and reactive powers are separately calculated for every phase and displayed in the box at the bottom of this section; if necessary it is possible to make changes from this section as well.

60
00:06:40,619 --> 00:06:42,469
After adding the intended points,

61
00:06:42,494 --> 00:06:50,359
the test can be started and after the time specified in accordance with the pulses and Wh elapsed, the results are displayed.

62
00:06:56,875 --> 00:07:00,070
In performing this test, some points must be considered:

63
00:07:00,095 --> 00:07:08,312
If a test point is specified in Wh mode, zero is entered as the value for reactive power by default and to change this,

64
00:07:08,337 --> 00:07:12,172
first the current angle needs to be changed from “Angle” field.

65
00:07:12,197 --> 00:07:18,210
2- The time entered in “Time” field by the user changes in accordance with the characteristic curve of the meter.

66
00:07:18,250 --> 00:07:22,179
This change is in a way that the number of pulses changes to integer.

67
00:07:22,204 --> 00:07:28,397
3- Being “Out of Range” for the points in this test depends on the required time for performing the test.

68
00:07:28,422 --> 00:07:32,865
Since the maximum injection time of the device is 4000 seconds,

69
00:07:32,890 --> 00:07:38,279
if a test point needs more time for the test, that point becomes “Out of Range”;

70
00:07:38,304 --> 00:07:45,061
 to change the state of this point, more voltage or current can be entered in “Advanced View” section.

71
00:07:45,086 --> 00:07:55,406
4- If a too large value is entered in “Wh” field, this value is recorded as “na” and by selecting “Add”, this point becomes “Out of Range”.
