Restricted Earth Fault

2
00:00:20,466 --> 00:00:27,999
This document reviews the operating principle of five common relays with respect to the low-impedance REF function.

3
00:00:28,733 --> 00:00:34,466
For each relay, the function behavior is first examined in the same manner as described in the relay manual. Then

4
00:00:34,867 --> 00:00:39,400
the method for designing a complete test plan for that function is presented.

5
00:00:39,639 --> 00:00:50,866
The relays covered in this document are MiCOM P632, Siemens 7UT6x, Siemens 7UT8x, ABB RET521, and ABB RET620.

6
00:00:57,400 --> 00:01:00,133
In some of the listed relays

7
00:01:00,533 --> 00:01:07,066
relay operation is based on comparing the neutral-branch current with the zero-sequence current calculated by the relay.

8
00:01:07,533 --> 00:01:13,800
 In practice, the relay operates based on the difference, or differential quantity, between these two currents.

9
00:01:14,266 --> 00:01:22,266
In some other relays, however, the comparison of these two currents is used only for relay stability by determining whether the fault is inside or outside the protection zone.

10
00:01:22,667 --> 00:01:26,800
In those cases, relay operation is based only on the neutral-branch current,

11
00:01:27,067 --> 00:01:30,866
and the differential quantity between the two currents is not used for relay operation.

12
00:01:32,467 --> 00:01:44,399
Restricted Earth Fault (REF) protection is used to detect earth faults inside different equipment such as transformers, autotransformers, reactors, motors, and similar apparatus.

13
00:01:44,723 --> 00:01:47,856
Because of its high accuracy and sensitivity,

14
00:01:48,190 --> 00:01:55,190
this protection can largely cover the areas that are not fully covered by transformer differential protection and conventional earth-fault protection.

15
00:01:55,590 --> 00:02:01,056
REF protection can be applied only when it is possible to measure the current flowing through the neutral point.

16
00:02:01,323 --> 00:02:07,256
During normal system operation, Isp and 3I0 are approximately zero. As

17
00:02:07,523 --> 00:02:17,056
As soon as an earth fault occurs, both currents change. Depending on the fault conditions, their values may be equal or may differ from one another.

18
00:02:19,923 --> 00:02:22,856
MiCOM P632

19
00:02:23,457 --> 00:02:33,123
The ground differential protection of this relay is based on comparing the vector sum of the phase currents on the relevant transformer side with the neutral-point current IY.

20
00:02:33,323 --> 00:02:40,256
To begin analyzing the behavior of this function, the relay parameters are first reviewed according to the relay manual.

21
00:02:40,857 --> 00:02:46,323
The first parameter used by this relay is the Matching Factor, which is calculated as follows.

22
00:02:47,923 --> 00:02:51,123
The following conditions apply to the Matching Factors:

23
00:02:51,523 --> 00:02:54,923
The Matching Factor must always be less than 16.

24
00:02:55,390 --> 00:02:58,989
The Matching Factor must always be greater than 0.5.

25
00:02:59,590 --> 00:03:05,323
If the Matching Factor does not satisfy the above conditions, an alarm is issued and the function is blocked.

26
00:03:05,856 --> 00:03:11,723
Two operating modes are described for this relay in the manual. Each mode is reviewed separately below.

27
00:03:12,123 --> 00:03:14,323
Low imped. / sum(IP)

28
00:03:14,723 --> 00:03:21,656
In this mode, the difference between each phase current and the neutral current is calculated as the differential current.

29
00:03:21,990 --> 00:03:25,523
The bias current is also considered to be the phase current.

30
00:03:26,723 --> 00:03:30,323
Low imped. / IP, max

31
00:03:31,057 --> 00:03:37,190
For this operating mode, the differential current and the bias current are defined as follows.

32
00:03:37,590 --> 00:03:42,856
Compared with the "Low imped. / Sum (IP)" operating mode

33
00:03:43,057 --> 00:03:46,190
a dual-slope characteristic is used here.

34
00:03:46,523 --> 00:03:47,457
Test Procedure

35
00:03:48,857 --> 00:03:55,390
To test this function, REF must be selected as the Protection Function in the Differential room.

36
00:03:55,523 --> 00:04:00,856
In the Primary column, the phase-side information (Main Side) must be entered, and

37
00:04:01,057 --> 00:04:05,256
and in the Secondary column, the neutral-side information must be entered.

38
00:04:06,723 --> 00:04:10,723
In the Protection Device tab and the Characteristic Definition tab,

39
00:04:10,923 --> 00:04:15,323
the information must be entered according to the operating mode selected in the relay.

40
00:04:16,057 --> 00:04:19,056
Low imped. / Sum (IP)

41
00:04:19,457 --> 00:04:25,856
Considering the bias-current formula for this mode, in which the phase current is used as the bias current,

42
00:04:26,257 --> 00:04:29,656
the appropriate formula is Max(Ip,Is).

43
00:04:29,923 --> 00:04:36,390
By default, the software assumes Ip to be the larger current, which causes the selected formula to match the relay formula.

44
00:04:36,857 --> 00:04:41,390
Since the REF characteristic-curve data are fixed, the information for Idiff>, Idiff>>,

45
00:04:41,923 --> 00:04:45,523
and the Characteristic Definition tab can be entered as shown below.

46
00:04:45,857 --> 00:04:50,723
In this mode, the information in the relay settings does not affect the characteristic curve.

47
00:04:51,590 --> 00:04:54,990
Low imped. / Ip,max

48
00:04:57,789 --> 00:05:03,923
In this mode, the selected bias-current formula is (|IP| + |IS|) / 2. This

49
00:05:04,923 --> 00:05:11,256
This is because, for each single-phase Fault Type, the tester injects current from only one phase on each side;

50
00:05:11,523 --> 00:05:21,190
therefore, Ip = 3I0. For the characteristic-curve data, the relay settings must be checked and the relay characteristic curve must be completed accordingly.

51
00:05:21,856 --> 00:05:26,922
Siemens 7UT6x (SIPROTEC 4)

52
00:05:27,590 --> 00:05:37,390
As mentioned earlier, REF protection uses two currents, Isp and 3I0, to perform the protection process. In

53
00:05:38,123 --> 00:05:47,190
In this process, the only operate current is Isp, while 3I0 is used to determine whether the system fault is internal or external.

54
00:05:48,057 --> 00:05:53,590
. During normal system operation, Isp and 3I0 are approximately zero.

55
00:05:54,057 --> 00:05:57,256
. As soon as an earth fault occurs, both currents change.

56
00:05:57,590 --> 00:06:01,990
Depending on the fault conditions, they may be equal or may differ from one another.

57
00:06:03,123 --> 00:06:09,190
If the fault occurs inside the protection zone, both Isp and 3I0 will flow.

58
00:06:09,590 --> 00:06:16,323
Considering that the directions of these currents are toward the inside of the transformer, both currents are considered positive.

59
00:06:19,257 --> 00:06:24,390
If the fault occurs outside the protection zone, both Isp and 3I0 will flow

60
00:06:24,790 --> 00:06:29,256
Isp flows toward the inside of the transformer and is considered positive,

61
00:06:29,457 --> 00:06:33,523
whereas 3I0 flows out of the transformer and is considered negative.

62
00:06:33,790 --> 00:06:39,390
To prevent REF protection from producing a false operation for faults outside the protection zone,

63
00:06:39,657 --> 00:06:44,323
a stabilizing method must be defined for the relay in addition to defining an operate current.

64
00:06:44,790 --> 00:06:50,056
Based on this explanation, IREF and Istab are defined as follows.

65
00:06:50,523 --> 00:06:54,990
To clarify the concept, three different fault conditions are described below.

66
00:06:56,123 --> 00:07:01,056
External-zone fault with equal magnitudes of Isp and 3I0

67
00:07:01,456 --> 00:07:06,256
In this condition, assuming equal magnitudes for Isp and 3I0,

68
00:07:06,523 --> 00:07:11,656
the direction of Isp is toward the inside of the transformer and is considered positive,

69
00:07:12,057 --> 00:07:16,523
while the direction of 3I0 is out of the transformer and is considered negative.

70
00:07:16,923 --> 00:07:25,056
 In this condition, the stabilizing current is twice the operate current, and REF protection remains stable.

71
00:07:28,323 --> 00:07:32,123
Internal-zone fault with the fault fed only from the star point

72
00:07:32,657 --> 00:07:39,856
In this condition, Isp is toward the inside of the transformer and positive, while 3I0 is zero.

73
00:07:40,057 --> 00:07:45,190
In this condition, REF protection is at its highest sensitivity and will trip.

74
00:07:45,990 --> 00:07:50,723
Internal-zone fault with the fault fed equally from the star point and the system

75
00:07:53,123 --> 00:08:01,723
In this condition, the directions of Isp and 3I0 are both toward the inside of the transformer and are considered positive.

76
00:08:02,457 --> 00:08:05,390
In this condition, Istab is negative.

77
00:08:05,723 --> 00:08:11,190
Therefore, it is set to zero, and REF protection operates at its highest sensitivity and will trip.

78
00:08:12,257 --> 00:08:18,990
According to the explanations above, for an internal-zone fault the relay has no stabilizing current and will trip.

79
00:08:19,657 --> 00:08:25,523
For an external-zone fault, however, a large stabilizing current exists and the relay will not trip.

80
00:08:26,256 --> 00:08:34,123
In all the examples above, it was assumed that the directions of Isp and 3I0 are either the same

81
00:08:34,323 --> 00:08:40,923
or have a 180-degree angular difference. This assumption is valid for primary quantities. However, for secondary quantities,

82
00:08:41,257 --> 00:08:52,390
conditions such as CT saturation and angle measurement errors may create angular deviations and reduce the value of ISTAB.

83
00:08:52,590 --> 00:08:58,056
Based on the method described above, assuming equal magnitudes for Isp and 3I0,

84
00:08:58,323 --> 00:09:05,656
if the angle between Isp and 3I0 is 90 degrees, the value of ISTAB becomes zero.

85
00:09:05,856 --> 00:09:06,856
Example:

86
00:09:07,257 --> 00:09:14,390
In the Siemens relay, a parameter called Limit Angle is defined, and its value is 100 degrees

87
00:09:14,790 --> 00:09:21,990
 If the angle between Isp and 3I0 is greater than this value, the relay will remain stable.

88
00:09:22,390 --> 00:09:29,990
The REF operating characteristic based on the angle between Isp and 3I0 is shown below.

89
00:09:30,923 --> 00:09:32,390
Test Procedure

90
00:09:32,790 --> 00:09:41,590
Because the REF function in Siemens SIPROTEC 4 relays is not designed as a differential function and no differential characteristic curve is defined for it,

91
00:09:42,057 --> 00:09:47,190
 it cannot be tested in the Differential room. It must be tested in the AMT Sequencer room.

92
00:09:47,390 --> 00:09:53,256
For this purpose, one current from group A and one current from group B must be activated in the Hardware Config.

93
00:09:53,590 --> 00:09:58,190
Current IA is connected to the phase side, and current IB is connected to the neutral side.

94
00:09:59,857 --> 00:10:02,990
In the first test step, the Setting value must be tested.

95
00:10:03,257 --> 00:10:06,723
For example, for a value of 0.15In,

96
00:10:06,923 --> 00:10:12,990
 current must be injected only from the neutral side using a Step Ramp, increasing the current in 2.5 mA steps.

97
00:10:13,323 --> 00:10:18,790
Note that in this relay, In is considered based on the transformer rated current, not the CT rated current.

98
00:10:19,123 --> 00:10:26,056
For example, if the rated current on the HV side is 250 A and the CT used is 300/1,

99
00:10:26,790 --> 00:10:38,656
then with the 0.15In setting the intended value is 0.15 × 250 = 37.5 A on the primary side and 0.125 A on the secondary side.

100
00:10:40,057 --> 00:10:47,190
In the next test step, the stabilizing method and the angle between the neutral current and the phase current must be tested.

101
00:10:47,523 --> 00:10:53,856
To test the stabilizing method, the phase current must be injected with the same magnitude as the neutral current.

102
00:10:54,057 --> 00:11:01,590
In the first case, it must be in phase with the neutral current; in the second case, it must have a 180-degree angular difference.

103
00:11:02,057 --> 00:11:08,990
In the in-phase condition, the relay trips, while in the 180-degree condition the relay must remain stable.

104
00:11:10,990 --> 00:11:15,990
In the final step, the Limit Angle, whose value is 100 degrees, must be tested.

105
00:11:16,457 --> 00:11:24,590
To do this, it is sufficient to select Quick mode and manually change the angle so that the relay behavior dependent on this angle can be tested and verified.

106
00:11:25,390 --> 00:11:29,923
Siemens 7UT8x (SIPROTEC 5)

107
00:11:31,323 --> 00:11:39,523
This relay uses IY, which is the neutral current, and 3I0, which is the zero-sequence current, for its calculations.

108
00:11:39,790 --> 00:11:44,590
From these two parameters, a differential current and a bias current are calculated.

109
00:11:45,123 --> 00:11:54,123
The characteristic curve provided for this function is in the form of Ichar versus Ibias. Ichar has separate definitions for pickup and trip,

110
00:11:54,523 --> 00:11:59,790
and therefore REF pickup operation and REF trip operation must be analyzed separately.

111
00:12:00,790 --> 00:12:02,723
Trip Operation

112
00:12:03,523 --> 00:12:13,456
For relay trip, the ratio of the neutral current to the Ichar value corresponding to Ibias on the characteristic curve is evaluated.

113
00:12:13,857 --> 00:12:19,056
According to the information provided in the relay manual, in order for the relay to issue a trip,

114
00:12:19,323 --> 00:12:27,656
the value of Itrip must first be greater than 1. In addition, relay trip depends on the angle between the neutral current and 3I0.

115
00:12:27,923 --> 00:12:32,256
If this angle is less than 90 degrees, the fault is considered internal.

116
00:12:32,457 --> 00:12:40,390
If it is greater than 90 degrees, the fault is identified as either internal or external depending on the ratio of IY to 3I0.

117
00:12:41,923 --> 00:12:43,590
Pickup Operation

118
00:12:43,856 --> 00:12:48,122
The pickup of this function is independent of the angle between the currents.

119
00:12:48,390 --> 00:12:53,256
If the calculated Idiff is greater than Ichar, the relay will pick up.

120
00:12:55,657 --> 00:12:56,790
Test Procedure

121
00:12:57,390 --> 00:13:04,923
Since the REF trip characteristic curve in Siemens SIPROTEC 5 relays is not treated as a differential characteristic curve,

122
00:13:05,189 --> 00:13:08,188
relay trip cannot be tested in the Differential room.

123
00:13:08,590 --> 00:13:12,456
The trip test must be performed in the AMT Sequencer room.

124
00:13:12,923 --> 00:13:18,923
Note that the characteristic curve has bias on the horizontal axis and Ichar on the vertical axis.

125
00:13:19,323 --> 00:13:26,723
For relay trip, this vertical axis represents IY; therefore, relay trip cannot be tested in the Differential room.

126
00:13:27,657 --> 00:13:34,790
For testing in the Sequencer room, three currents from group A and one current from group B must be activated in the Hardware Config.

127
00:13:35,057 --> 00:13:40,523
The three group-A currents are connected to the phase side, and current IB is connected to the neutral side.

128
00:13:41,657 --> 00:13:44,990
In the first test step, the Setting value must be tested.

129
00:13:45,657 --> 00:13:49,456
To do this, current must be injected into one of the three phases,

130
00:13:49,723 --> 00:13:53,190
and then the neutral current must be increased step by step. After

131
00:13:53,657 --> 00:13:59,056
After the relay trips, the neutral current that caused the trip must be matched with the characteristic curve.

132
00:13:59,657 --> 00:14:07,856
For this matching, the corresponding bias current must first be calculated using the provided equation, and then IY must be compared with Ichar.

133
00:14:10,057 --> 00:14:17,456
In the next test step, the stabilizing method and the angle between the neutral current and the phase current must be tested.

134
00:14:18,390 --> 00:14:23,590
To test the stabilizing method, the phase current must be injected with a specified magnitude,

135
00:14:24,123 --> 00:14:27,456
and the neutral current must also be injected under different conditions.

136
00:14:27,657 --> 00:14:37,856
For this purpose, current must be injected into both the phase side and the neutral side and adjusted so that the IY current lies in the operating area of the relay characteristic curve.

137
00:14:38,323 --> 00:14:43,123
To test this condition, the current magnitudes must be kept constant in Quick mode,

138
00:14:43,390 --> 00:14:50,990
and the angle must be checked at the threshold value, for example 90 degrees, to verify correct relay operation. As shown in the curve on the right,

139
00:14:51,457 --> 00:14:58,390
the angle threshold varies depending on the ratio of IY to 3I0, which can be considered during testing.

140
00:15:00,657 --> 00:15:06,790
For testing relay pickup, the Differential room can be used because, according to the relay manual,

141
00:15:06,990 --> 00:15:15,923
 the vertical axis of the Ichar-Ibias characteristic curve is the differential quantity between the neutral current and the zero-sequence current.

142
00:15:18,923 --> 00:15:28,323
For testing in the Differential room, in the Test Object window, the Differential block must be configured by selecting REF as the Protection Function.

143
00:15:28,856 --> 00:15:35,256
Then, the Main Side and Neutral information must be completed according to the side on which this function is applied.

144
00:15:35,790 --> 00:15:39,390
The Ibias formula must be entered as IP + IS.

145
00:15:39,722 --> 00:15:45,990
Since only one phase current is injected during a single-phase fault, this formula corresponds to the relay formula.

146
00:15:47,387 --> 00:15:50,456
ABB RET521

147
00:15:51,323 --> 00:15:55,990
To detect an internal-zone earth fault, the relay uses two elements: the

148
00:15:56,123 --> 00:15:59,656
the diff-bias characteristic curve and a directional element.

149
00:16:00,257 --> 00:16:08,256
In this relay, the neutral current (IN) is--- considered the directional reference because its direction is fixed in both internal and external fault conditions.

150
00:16:08,857 --> 00:16:13,256
For this relay, the equations given for Idiff and Ibias are as follows.

151
00:16:13,723 --> 00:16:19,256
Based on the structure provided in this relay manual, the phase-side CTs must be grounded toward the transformer,

152
00:16:19,457 --> 00:16:23,656
while the neutral-side CT must be grounded in the opposite direction to the transformer.

153
00:16:23,857 --> 00:16:27,990
For this reason, the negative sign in the Idiff calculation becomes meaningful.

154
00:16:28,123 --> 00:16:34,123
In general, in order for the relay to identify an earth fault inside the protection zone,

155
00:16:34,323 --> 00:16:39,256
the directions of the currents seen by the relay must be opposite to each other.

156
00:16:40,723 --> 00:16:45,790
For faults outside the protection zone, the differential quantity is approximately zero.

157
00:16:45,990 --> 00:16:50,590
Based on the relay definition, the direction of the current in both CTs is the same, which

158
00:16:50,923 --> 00:16:54,990
which causes the relay to identify the fault as being outside the protection zone.

159
00:16:55,990 --> 00:17:00,856
The diff-bias characteristic curve provided by the relay consists of three sections.

160
00:17:01,190 --> 00:17:06,523
In the first section, the threshold current is adjustable by the user from 5% to 50%, while

161
00:17:06,857 --> 00:17:09,123
 while the other sections are defined and fixed.

162
00:17:09,590 --> 00:17:10,723
Test Procedure

163
00:17:11,323 --> 00:17:16,790
This function in the RET521 relay can be tested in the Differential room.

164
00:17:17,123 --> 00:17:22,456
 The following points must be considered when entering the information for this protection function.

165
00:17:22,923 --> 00:17:28,656
To test this function, REF must be selected as the Protection Function in the Differential room.

166
00:17:29,190 --> 00:17:37,323
The phase-side information (Main Side) must be entered in the Primary column, and the neutral-side information must be entered in the Secondary column.

167
00:17:37,590 --> 00:17:45,590
The Starpoint Grounding direction for the Neutral side must be selected as Toward Line, and the Ibias relation must be selected as Max(Ip,Is).

168
00:17:46,590 --> 00:17:52,656
In this example, the differential characteristic curve has been drawn for an operating threshold of 0.3.

169
00:17:53,457 --> 00:17:56,190
ABB RET620

170
00:17:56,590 --> 00:18:06,590
For REF protection, this relay uses the differential quantity between the phase zero-sequence current (3I0) and the neutral current IY.

171
00:18:07,057 --> 00:18:11,923
 A bias current is also defined for the diff-bias characteristic curve of this function,

172
00:18:12,123 --> 00:18:14,789
which is the average of the three phase currents of the relay.

173
00:18:15,057 --> 00:18:17,590
According to the points stated in the relay manual,

174
00:18:17,857 --> 00:18:25,923
COSphi is considered equal to 1 when the angle between the neutral current (IY) and the phase zero-sequence current (3I0) is 180 degrees.

175
00:18:26,190 --> 00:18:30,523
If the angle between them is less than 90 degrees, COSphi is considered zero.

176
00:18:30,857 --> 00:18:39,057
Therefore, the relay will trip only when the angle between the neutral current (IY) and the phase zero-sequence current (3I0) is greater than 90 degrees.

177
00:18:39,323 --> 00:18:41,456
Two Connection Types are defined for this relay.

178
00:18:41,590 --> 00:18:48,257
In summary, if the CTs on both sides are grounded either toward the equipment or away from the equipment,

179
00:18:48,656 --> 00:18:59,086
the connection is Type 1. If one CT is grounded toward the transformer and the other is grounded in the opposite direction, the connection is Type 2.

180
00:19:00,687 --> 00:19:03,620
Internal and External Fault Identification

181
00:19:04,087 --> 00:19:11,820
In the relay manual, the structure below (Type 1) is used to explain internal and external faults and to analyze relay behavior.

182
00:19:12,687 --> 00:19:21,286
In this structure, if the angle between 3I0 and IY is less than 90 degrees, the fault is identified as external and the function is blocked.

183
00:19:21,887 --> 00:19:23,419
Test Procedure

184
00:19:23,687 --> 00:19:28,486
This function in the RET620 relay can be tested in the Differential room.

185
00:19:28,687 --> 00:19:33,753
The following points must be considered when entering the information for this protection function.

186
00:19:34,020 --> 00:19:39,486
To test this function, REF must be selected as the Protection Function in the Differential room.

187
00:19:39,753 --> 00:19:44,219
In the Primary column, the phase-side information (Main Side) must be entered,

188
00:19:44,620 --> 00:19:48,419
and in the Secondary column, the neutral-side information must be entered.

189
00:19:48,820 --> 00:19:56,020
If the Connection Type in the relay is Type 1, the Starpoint Grounding direction of both CTs must be selected as Toward Object;

190
00:19:56,353 --> 00:19:59,553
otherwise, the neutral-side CT must be selected as Toward Line.

191
00:19:59,820 --> 00:20:08,553
The Ibias relation must be selected as Max(Ip,Is) / K1, with K1 = 3.

192
00:20:09,220 --> 00:20:15,820
In this example, the differential characteristic curve has been drawn for an operating threshold of 0.3.
