00:00:18,906 --> 00:00:21,796
Zero Sequence Elimination

2
00:00:22,031 --> 00:00:27,734
To explain this concept, consider a transformer with a vector group of YNd5.

3
00:00:28,047 --> 00:00:37,421
In the transformer with the specified vector group, the secondary vectors relative to the primary are derived using the following equations.

4
00:00:37,734 --> 00:00:44,453
Using these equations, the schematic of the winding connections and the direction of the currents

5
00:00:44,922 --> 00:00:56,406
on the secondary side can be drawn. For example, in the first step, the connection of the windings and the direction of currents for phase A' is shown as illustrated

6
00:00:56,953 --> 00:01:01,796
Finally, the connections will look as shown in the following diagram.

7
00:01:02,031 --> 00:01:08,593
Given the figure above, the matrix of currents on the star side is as shown below.

8
00:01:08,672 --> 00:01:15,390
The overall transfer matrix from the secondary side to the primary side is also as shown:

9
00:01:15,703 --> 00:01:20,859
For YNd5, it is represented as shown below.

10
00:01:21,484 --> 00:01:28,984
In the differential protection of a transformer with the given vector group and a 1:1 turn ratio

11
00:01:29,141 --> 00:01:35,468
if an earth fault occurs outside the protective zone, the relay will operate

12
00:01:35,625 --> 00:01:43,437
In the event of an earth fault outside the protection zone, the currents shown will be present on both sides

13
00:01:43,984 --> 00:01:50,937
According to the equation above, if a fault with current If occurs in phase C

14
00:01:51,406 --> 00:02:00,078
the corresponding winding on the secondary side will have If/sqrt(3) flowing through it.

15
00:02:01,055 --> 00:02:08,007
According to the differential protection convention, the currents entering the transformer are considered positive

16
00:02:08,398 --> 00:02:11,757
and those leaving the transformer are negative

17
00:02:11,914 --> 00:02:20,195
Therefore, the matrices shown will apply for the primary side and the transfer from secondary to primary

18
00:02:20,898 --> 00:02:24,882
The differential current of the above will be as shown below:

19
00:02:25,195 --> 00:02:28,710
With these differential currents, the relay will trip

20
00:02:28,945 --> 00:02:37,539
However, if the zero-sequence current from the YN side is eliminated, the primary side current will be as shown

21
00:02:38,398 --> 00:02:44,101
With the changes made, the differential currents will be as shown and will remain stable:

22
00:02:44,258 --> 00:02:54,023
However, if the fault is inside the protection zone, the current seen by the CTs on the YN side will be zero:

23
00:02:54,883 --> 00:03:03,710
Therefore, for an earth fault within the protective zone, the differential will be as shown below, and the relay will trip.
