NO COMBINED CHARACTERISTIC

2
00:00:21,249 --> 00:00:26,875
According to the operation of differential relays, the differential of each phase is calculated separately

3
00:00:27,031 --> 00:00:33,906
and based on the differential characteristic, the relay will either trip or not trip. In single-phase faults

4
00:00:34,141 --> 00:00:42,343
you will notice that the differential and bias currents in the tested phase are twice those of the other two phases

5
00:00:42,578 --> 00:00:50,468
In such conditions, the relay essentially operates with two characteristics. The first
characteristic is the one set on the relay

6
00:00:50,703 --> 00:00:59,921
and the second characteristic is obtained by
multiplying the Idiff and Ibias of the set characteristic by 2

7
00:01:00,156 --> 00:01:09,609
In differential characteristics with two slopes, by plotting the two mentioned
characteristics, the resulting differential characteristics are obtained as shown

8
00:01:09,844 --> 00:01:15,781
To derive the practical characteristic from these two characteristics, for each Ibias

9
00:01:16,094 --> 00:01:21,328
you need to find the lowest Idiff value that causes the relay to operate

10
00:01:21,563 --> 00:01:27,421
which typically refers
to lower differential currents and is obtained as shown

11
00:01:27,578 --> 00:01:31,562
The following explanation can help clarify this concept

12
00:01:31,796 --> 00:01:40,937
In single-phase fault types, in a section of the characteristic (the green region shown in the figure below), the test point in question falls in the NO trip region

13
00:01:41,406 --> 00:01:52,343
However, if you check the differential and bias currents of the other two phases, you'll see that they are in the TRIP region, and the relay will trip

14
00:01:55,156 --> 00:02:00,781
With the mentioned modifications, the differential characteristic is adjusted accordingly

15
00:02:01,016 --> 00:02:09,453
That is, changes are made so that in this part of the characteristic, the selected point falls within the Tripping region

16
00:02:10,156 --> 00:02:21,562
For relays that can filter out high differential currents in healthy phases, such as the ABB RET670

17
00:02:21,719 --> 00:02:31,718
to deactivate the use of combined characteristics, select the "No combined characteristic" option in the Protection Device tab
