﻿1
00:00:18,984 --> 00:00:23,593
Distance Protection Voltage and Current Calculations in the Test Room

2
00:00:24,141 --> 00:00:32,812
In distance protection testing, an impedance relay is used to protect a line by calculating impedance using line current and voltage

3
00:00:32,969 --> 00:00:41,484
The calculations in the distance room require injecting current and voltage proportional to the impedance of the relay

4
00:00:41,953 --> 00:00:49,687
The training covers distance test calculations, along with proof for various fault types and testing methods

5
00:00:49,844 --> 00:00:56,484
There are three common methods to calculate fault voltage and current for distance relay testing

6
00:00:57,734 --> 00:01:07,734
. Constant Z-I Method In this method, the fault current is considered constant, and the fault voltage is calculated by entering the impedance

7
00:01:08,594 --> 00:01:14,062
In the Test Object window (Test Block), pay attention to the maximum test impedance (max(V))

8
00:01:14,375 --> 00:01:23,281
which depends on the maximum test voltage displayed in the table for various fault types under the **Device Limits** section

9
00:01:25,703 --> 00:01:27,890
Constant Z-V Method

10
00:01:28,281 --> 00:01:35,937
In this method, the fault voltage is considered constant, and the fault current is calculated by entering the impedance

11
00:01:36,563 --> 00:01:41,485
calculated by entering the impedance. In the Test Object window (Test Block), pay attention to the minimum test impedance (maxI)

12
00:01:41,719 --> 00:01:49,765
which depends on the maximum fault current displayed in the table for various fault types under the ‘Device Limits’ section

13
00:01:52,578 --> 00:01:55,156
Constant Source Impedance Method

14
00:01:55,547 --> 00:02:07,500
In this method, neither voltage nor current is considered constant, but instead, the fault voltage is calculated using the source impedance (Zs) and the source factor (Ks)

15
00:02:07,834 --> 00:02:17,365
). Information from the source may vary, but eventually, Ks and Zs are converted into usable values for calculations

16
00:02:17,756 --> 00:02:23,380
All of this data is related to source impedance and is finally used in calculations

17
00:02:23,770 --> 00:02:32,365
In the next step, based on the chosen test method, fault current and voltage can be calculated in the ‘Distance Room’ under the ‘Setting’ tab

18
00:02:32,599 --> 00:02:39,865
, ‘Fault’ subsection, and ‘Test Model’ group. Click on the sliding field to select the desired mode

19
00:02:40,490 --> 00:02:44,552
Understanding the Concept of Source Impedance Ratio (SIR)

20
00:02:45,099 --> 00:02:52,599
Consider a single-phase equivalent circuit of the network with a source or SV voltage

21
00:02:52,990 --> 00:03:03,771
. This network consists of the source impedance (Zs) up to the relay installation location and the line impedance (ZL), which the protection relay will monitor

22
00:03:04,553 --> 00:03:09,553
 The voltage measured by the relay is denoted as RV.

23
00:03:10,099 --> 00:03:17,443
The system voltage seen by the relay is calculated using the ratio between Zs and ZL

24
00:03:17,833 --> 00:03:24,473
known as the ‘Source Impedance Ratio (SIR)’, which is represented by the following equation

25
00:03:25,725 --> 00:03:35,177
Also, using the following relationship, the voltage from the source to the short circuit level can be calculated asTherefore

26
00:03:36,349 --> 00:03:45,958
, the voltage measured by the relay during a fault depends on the SIR value and ultimately on the line impedance

27
00:03:46,271 --> 00:03:54,240
Using the relationships for Ks and Zs, fault voltage and current can be calculated for the test.

28
00:03:55,568 --> 00:03:58,849
Current and Voltage in Different Fault Types

29
00:03:59,084 --> 00:04:05,021
So far, explanations have been provided regarding methods for impedance calculation

30
00:04:05,412 --> 00:04:16,896
This section discusses the relationships of fault current and voltage in the software using the equivalent circuit for single-phase, two-phase, and three-phase faults

31
00:04:59,240 --> 00:05:01,505
Single-Phase Fault:

32
00:05:01,740 --> 00:05:07,755
The figure below shows the equivalent circuit of the line in the case of a single-phase fault

33
00:05:07,990 --> 00:05:13,302
For calculating the current and voltage of the faulted phase and the other phases

34
00:05:13,459 --> 00:05:24,005
methods such as constant current, constant voltage, and constant source impedance are used, with the calculations for each provided separately.

35
00:05:25,334 --> 00:05:37,052
In Z-I Constant Method, the fault current (test current) is considered constant for all test points. Using the impedance and test current, the voltage is calculated as follows:

36
00:05:54,865 --> 00:06:07,583
In Z-V Constant Method the fault voltage (test voltage) is fixed for all test points. Using the impedance and test voltage, the current is determined by:

37
00:06:08,285 --> 00:06:16,646
In the Constant Source Impedance method, the fault current and voltage are calculated according to Kirchhoff's law as follows:

38
00:06:17,584 --> 00:06:20,865
Proof of calculations in the Constant method:

39
00:06:21,256 --> 00:06:23,208
. Two-Phase Fault

40
00:06:23,756 --> 00:06:27,896
The equivalent circuit for a two-phase fault is shown below

41
00:06:28,912 --> 00:06:40,630
For the faulted and healthy phases, methods like constant current, constant voltage, and constant source impedance are used, with each calculation presented separately

42
00:06:41,568 --> 00:06:52,974
In Z-I Constant Method, the fault current remains constant across all test points and is the same for the two faulted phases but 180° out of phase

43
00:06:53,600 --> 00:06:57,974
This results in the following relationships for current and voltage:

44
00:06:59,459 --> 00:07:03,599


45
00:07:15,756 --> 00:07:27,318
Assume a fault impedance of 1 ohm with an angle of 0° is used for testing

46
00:07:27,865 --> 00:07:36,536
. In this fault type, the angle between the line-to-line voltage and the corresponding current creates the desired impedance angle

47
00:07:36,771 --> 00:07:40,208
The results for phase angles and magnitudes are:

48
00:07:41,537 --> 00:07:49,505
In the Constant Source Impedance method, the fault current and voltage are obtained as follows according to Kirchhoff's law:

49
00:07:56,615 --> 00:07:58,333
Three-Phase Fault

50
00:07:58,646 --> 00:08:04,193
The equivalent circuit for a three-phase symmetrical fault is illustrated below

51
00:08:04,428 --> 00:08:12,006
Faulted phase calculations are performed separately for constant current, constant voltage, and constant source impedance methods.

52
00:08:13,099 --> 00:08:23,099
In Z-I Constant Method, fault current is fixed across all test points, and the fault voltage for all three phases is calculated using:

53
00:08:24,037 --> 00:08:31,693
In the Z-V Constant Method the fault voltage is set equal to the phase-to-ground voltage for all test points

54
00:08:32,240 --> 00:08:36,302
Fault currents for each phase are determined as:

55
00:08:36,928 --> 00:08:45,756
In this method, both fault current and voltage are calculated using Kirchhoff's laws, considering the source impedance

56
00:08:46,320 --> 00:08:52,335
The relationships for fault current and relay voltage are
