﻿1
00:00:18,984 --> 00:00:21,328
DISTANCE GROUNDING FACTOR

2
00:00:21,875 --> 00:00:31,171
Numeric distance protection relays use various algorithms, based on measured current and voltage, to calculate fault impedance

3
00:00:31,563 --> 00:00:37,969
The calculated impedances differ under certain conditions, such as single-phase-to-ground faults

4
00:00:38,281 --> 00:00:48,671
Generally, three methods are commonly used for calculating impedance in phase-to-ground faults: Type A, Type B, and Type C

5
00:00:48,828 --> 00:00:55,312
Here, a single-phase-to-ground fault (Phase E1-L) has been applied to three relays with different algorithms

6
00:00:55,625 --> 00:01:00,781
The voltage and current measured by each relay are displayed as shown.

7
00:01:01,094 --> 00:01:06,015
The line impedances calculated by the distance relays are shown as displayed

8
00:01:06,250 --> 00:01:16,250
The different measured impedance values are due to the varying grounding factors used in the distance relays. Below, these three methods are introduced

9
00:01:16,875 --> 00:01:22,578
As you may know, the distance relay determines the fault location by calculating impedance

10
00:01:23,125 --> 00:01:33,593
The shown diagram represents the equivalent circuit of a double-fed line where a single-phase-to-ground fault has occurred in Phase L1

11
00:01:33,906 --> 00:01:41,796
In this circuit, the relay at point M measures voltage and current and calculates impedance based on Kirchhoff's law

12
00:01:42,500 --> 00:01:52,109
In the written equation, the term RF is considered as zero undefined due to the arc caused by the short circuit

13
00:01:52,266 --> 00:02:00,625
Therefore, by making certain assumptions to simplify this equation, the relay calculates the voltage at point M

14
00:02:01,021 --> 00:02:10,552
In the equations, RF is assumed to be zero, and IE.ZE are determined using the grounding factor.

15
00:02:11,099 --> 00:02:21,177
 The grounding factor (K) is used in phase-to-ground faults and relates to line parameters, defined as the ratio of ground impedance to line impedance

16
00:02:21,412 --> 00:02:28,208
. The diagram shows the equivalent circuit for a phase-to-ground fault, assuming RF = 0

17
00:02:28,678 --> 00:02:41,490
where the total impedance ZS is divided into line impedance ZL and ground impedance ZE. With these assumptions, we have the equations as shown.

18
00:02:41,959 --> 00:02:53,521
In the displayed equations, Z0s and Z1s represent the positive sequence and zero sequence impedances of the source, respectively

19
00:03:00,865 --> 00:03:08,911
In general, there are three methods for expressing the grounding factor (K), which are convertible to one another

20
00:03:09,381 --> 00:03:16,490
The first method is the ratio of ground impedance to line impedance, which is a complex number

21
00:03:16,881 --> 00:03:24,068
The second method is the division of zero-sequence impedance by positive-sequence impedance.

22
00:03:24,537 --> 00:03:33,755
The third method represents the grounding factor as a pair of real numbers. Depending on what information about the grounding factor is available

23
00:03:34,068 --> 00:03:43,755
it can be independently entered in the Object Test window, Distance Block, Factor Grounding section of the Vebko software

24
00:03:44,693 --> 00:03:55,474
The Factor Grounding section in the Parameters Protection Distance window allows for inputting the grounding factor and selecting the relay's algorithm

25
00:03:55,865 --> 00:04:05,693
Using the Mode dropdown menu, the method of entering the factor (RL/RE or KL K, K0) can be chosen without affecting the relay's algorithm.

26
00:04:07,178 --> 00:04:14,052
As mentioned, there are equations for converting different types of grounding factors into each other

27
00:04:14,209 --> 00:04:21,396
The relationship between the KL factor and other grounding-related factors is shown.

28
00:04:27,724 --> 00:04:33,505
Distance Protection Relay Algorithm Type A, ‘KL Complex’:

29
00:04:33,974 --> 00:04:39,599
The distance relay with Type A algorithm uses the KL factor, as shown

30
00:04:39,912 --> 00:04:43,505
 for calculating impedance in a phase-to-ground fault.

31
00:04:43,896 --> 00:04:50,927
In the shown equation, assuming that the first-phase current, ground current, and fault current are equal  (-=1IL=IIF=IE )

32
00:04:51,240 --> 00:04:56,240
, and with V as the voltage measured by the relay during the fault

33
00:04:56,474 --> 00:05:08,896
the impedance measured by the relay is calculated as shown. Distance Protection Relay Algorithm Type B, ‘XL/XE, RL/RE’:

34
00:05:11,084 --> 00:05:22,490
The distance relay with Type B algorithm calculates impedance for a phase-to-ground fault using the complex grounding factors KrKr and KxKx, as displayed.

35
00:05:22,708 --> 00:05:30,129
In the given equation, it is assumed that the first-phase current, ground current, and fault current are equal (i.e., IL1=I=IF=IEIL1=I=IF=IE).

36
00:05:30,521 --> 00:05:40,599
Additionally, V represents the voltage measured by the relay during the fault. Based on this, the impedance measured by the relay is calculated as shown.

37
00:05:41,459 --> 00:05:49,583
Type C distance relays use an algorithm similar to Type B for calculating the imaginary part of the fault impedance X.

38
00:05:49,896 --> 00:05:55,286
However, they calculate the real part of the fault impedance R differently.

39
00:05:55,599 --> 00:06:04,114
This algorithm considers the arc resistance (RF arc) by assuming that the fault current IF is equal to the line current.

40
00:06:04,428 --> 00:06:11,302
The main concept in this algorithm is to combine arc resistance with line resistance

41
00:06:11,537 --> 00:06:19,818
 In other words, the real part of the ground impedance is subtracted from the real part of the phase-to-ground fault impedance (ground-fault loop).

42
00:06:20,131 --> 00:06:30,365
The ground resistance value can then be determined from the calculated XL as a function of the factor Kr and the line angle.

43
00:06:41,615 --> 00:06:45,755
Interpretation of Results for Different Algorithms

44
00:06:45,990 --> 00:06:50,599
Simplifying (IE=−IF=IL1IE=−IF=IL1) allows for comparing the obtained results

45
00:06:51,459 --> 00:06:58,802
The displayed table shows the line impedance calculated by different distance protection algorithms.

46
00:06:59,896 --> 00:07:03,958
The displayed table shows a key result of the analysis

47
00:07:04,193 --> 00:07:13,177
The measured impedance (Zmeas = Rmeas +j xmeas) by the distance relay includes the line impedance ( Z_L) along with a portion of the arc resistance.

48
00:07:13,568 --> 00:07:21,693
The amount of added RF arc resistance  to the line impedance depends on the distance protection algorithm used.

49
00:07:22,709 --> 00:07:26,068
As shown in the table, in Type A relays

50
00:07:26,303 --> 00:07:34,115
the grounding factor or  KL  impacts both the real and imaginary parts of the impedance as a complex value.

51
00:07:34,271 --> 00:07:40,443
In this case, the arc effect from a short circuit is considered an inductive and resistive phenomenon

52
00:07:40,678 --> 00:07:46,224
represented as a complex impedance. In Type B algorithms,

53
00:07:46,693 --> 00:07:57,240
the relays reduce the arc resistance ( RF ) by a factor of 1 /(1+Kr) in the real part

54
00:07:57,474 --> 00:08:05,911
. In Type C algorithms, relays measure impedance without any compensation factor for arc resistance ( RF)

55
00:08:06,303 --> 00:08:14,661
Distance relays of Types A, B, and C define measured impedance differently. Consequently:

56
00:08:14,818 --> 00:08:27,865
Scaling on the impedance plane changes and will no longer depend solely on ( X ) and (R). The relevant axes scaling is illustrated in the accompanying diagrams.

57
00:08:28,568 --> 00:08:36,536
Measured impedances from different relay types are not directly comparable on the same impedance plane.

58
00:08:36,849 --> 00:08:46,693
All distance protection algorithms produce the same ( R_L ) and ( X_L ) results at the line angle or when RF = 0.

59
00:08:46,928 --> 00:08:55,990
Outside the line angle, depending on the fault's location on the impedance plane, the arc resistance is added to the line impedance

60
00:08:57,630 --> 00:09:07,318
All distance protection algorithms function correctly; however, grounding factors must be considered when setting zones and testing relays.

61
00:09:08,646 --> 00:09:11,771
Considering Grounding Factors During Testing

62
00:09:12,162 --> 00:09:19,974
The Vebko software, including the Test and Stable versions, implements all mentioned distance protection algorithms.

63
00:09:20,359 --> 00:09:25,515
As discussed, depending on the available grounding factor data

64
00:09:26,063 --> 00:09:33,641
it can be entered independently according to the equations in the Vebko software’s Object Test window

65
00:09:33,875 --> 00:09:37,468
within the Distance Block under the Factor Grounding section.

66
00:09:37,938 --> 00:09:44,656
You can also select any of the mentioned algorithms to calculate current and voltage.

67
00:09:45,125 --> 00:09:51,843
It’s crucial that both the testing software and the relay use the same algorithm during testing

68
00:09:52,078 --> 00:09:56,609
otherwise, this may result in inaccurate test outcomes.

69
00:09:56,844 --> 00:10:03,484
The choice of distance protection algorithm is selected by checking boxes, as shown in the figure.

70
00:10:03,953 --> 00:10:09,968
For the algorithms used by distance protection relays, refer to the relevant manuals and documentation

71
00:10:10,125 --> 00:10:21,218
Since algorithms are not always publicly available, some common examples are listed in the displayed table.
