1
00:00:19,091 --> 00:00:20,181
“Check Test” tab:

2
00:00:20,215 --> 00:00:25,062
After performing “Shot Test” in “Distance” room, it is time to do “Check Test” and “Search Test”.

3
00:00:25,087 --> 00:00:32,831
In “Check Test” the upper and lower tolerances of the relay which are displayed as dotted line in “Impedance View” are tested and evaluated.

4
00:00:32,856 --> 00:00:38,700
To perform a “Check Test”, first it is necessary to draw lines named “Check Line” in different parts of the diagram.

5
00:00:38,725 --> 00:00:48,926
To draw this line first from “Check Line” section, the origin point of this line is specified in “Origin”. In “|Z|” field the test impedance value is entered as a number.

6
00:00:48,951 --> 00:00:55,780
Note that if a negative number , for example -2.5 is entered, since there is no negative impedance,

7
00:00:55,805 --> 00:01:02,939
this negative value will influence the angle; this means that it will be subtracted from 180 degrees angle in “Phi” field.

8
00:01:02,964 --> 00:01:11,844
The impedance angle is entered within the range of -180 to 180 in “Phi” field and if in this cell a number higher than this range is entered,

9
00:01:11,869 --> 00:01:15,790
automatically that number will be displayed in the specified range.

10
00:01:15,908 --> 00:01:22,262
For example if 455 degrees is entered in this field, 95 degrees will be displayed.

11
00:01:22,708 --> 00:01:28,950
In addition to using |Z| & "Phi" filed, you can specify origin impedance using "R" & "X" fields.

12
00:01:28,974 --> 00:01:32,426
"R" & "X" are real and imaginary of impedance.

13
00:01:32,458 --> 00:01:39,879
In fact the four fields of “|Z|”, “Phi”, “R” and “X” are linked and by changing the value of one of them, the others change accordingly.

14
00:01:39,852 --> 00:01:46,606
In “Angle” field the angle of the “Check Line” and In the cell of the “Length” section the length of the “Check Line” is entered.

15
00:01:46,638 --> 00:01:55,348
In “%” field it is possible to specify the length of “Check Line” in terms of a percentage of the length specified in “Test Object” by default.

16
00:01:55,364 --> 00:02:02,629
By enabling the “Relative” option, you can make the length of the line dependent on the parameter specified in “of” field.

17
00:02:02,645 --> 00:02:10,207
The value of the parameter specified in “of” field is multiplied by the value of the “%” field and the length of the line is formed.

18
00:02:10,251 --> 00:02:19,247
If “Relative” is checked, by changing the value of the “of” parameter, the value of the “%” cell does not change and the new value of the “Length” is calculated.

19
00:02:19,278 --> 00:02:28,559
If “Relative” checkbox is not enabled and the value of “of” parameter is changed, the value of “Length” field remains fixed and the value of the “%” changes.

20
00:02:28,584 --> 00:02:35,942
Note that the drawn “Check Lines” need to have an intersection with at least one of the tolerance lines of the characteristic curve.

21
00:02:35,974 --> 00:02:41,364
Then, click on “Add” option so that the “Check Line” is added to the “Check Test” lines table.

22
00:02:41,402 --> 00:02:52,622
Another method for drawing the “Check Line” is to hold down the left-click and “Ctrl” key on “Impedance View” window and then move the cursor in the desired direction on the characteristic curve.

23
00:02:52,669 --> 00:02:58,793
You can see that the information of the drawn “Check Line” is displayed in “Check Test” lines table.

24
00:02:58,966 --> 00:03:10,715
After drawing the “Check Line”, the software evaluates the crossing place of “Check Line” and tolerance lines as “Shot” test in accordance with the performance of the relay.

25
00:03:10,778 --> 00:03:20,082
Here, after performing the test, the relay does not perform in upper tolerance and performs a trip in the lower tolerance so the result of the test is “Passed”.

26
00:03:20,106 --> 00:03:25,449
Other parts of this section such as “Fault Type” and “Remove All” and “Sequence” etc.

27
00:03:25,504 --> 00:03:32,037
options are the same at those of “Shot Test” section which have been explained in previous videos.

28
00:03:32,067 --> 00:03:35,668
The only additional option in this section is “Copy to Search”.

29
00:03:35,693 --> 00:03:48,528
By marking any of the test lines and selecting this option, it is possible to copy the selected line in “Search Test” and by selecting “Add” option in “Search Test”, add this line to the “Search Test” test lines table.
