1
00:00:27,091 --> 00:00:30,841
Introducing “Test View” window in “Distance” room, Part I

2
00:00:30,866 --> 00:00:34,746
As mentioned before, one of the windows of “Distance” room is “Test View”.

3
00:00:34,771 --> 00:00:41,201
This window consists of 6 tabs of “Shot Test”, “Check Test”, “Search Test”, “Setting”, “Trigger” and “Binary Output”.

4
00:00:41,226 --> 00:00:50,067
In “Shot Test” tab, it is possible to specify fault type and test point and after performing the test, you can view the results of the evaluation.

5
00:00:50,092 --> 00:00:55,434
In “Test Point” section in this tab, the test point can be specified using two methods:

6
00:00:55,459 --> 00:01:03,915
first, the impedance magnitude is entered in “lZl” field in terms of ohm and in “Phi” field the impedance angle is entered in terms of degree.

7
00:01:03,940 --> 00:01:12,521
Then, by clicking on “Add” the values are entered and the software displays the real and imaginary values of this impedance in “R” and “X” fields respectively.

8
00:01:12,546 --> 00:01:21,093
In the second method, it is possible to directly enter the real and imaginary values in “R” and “X” fields and by selecting “Add” select your intended point.

9
00:01:21,140 --> 00:01:27,373
If you wish to enter your test points in terms of a percentage of length of the line, you should use “%” field.

10
00:01:27,398 --> 00:01:34,210
By checking “Z Relative” option, the test point is made dependent on the length of the line and recorded in the table.

11
00:01:34,235 --> 00:01:46,577
By changing the length of the line from 1 to 3 ohms, in “Test Object” section, in “Distance Parameters” window in “System Settings”, the entered impedance value is changed in accordance with the length of the line.

12
00:01:46,617 --> 00:01:53,397
But, if this option is not checked, by changing the length of the line, the entered values in the table do not change.

13
00:01:53,424 --> 00:01:59,889
In fact, each test point consists of three “States” which simulate “Prefault”, “Fault” and “Post Fault” states.

14
00:01:59,913 --> 00:02:11,200
By default, in “Prefault”, “Fault” and “Post Fault”, 0 nominal voltage and current, 0 voltage and current and a voltage and a current based on the test point are injected respectively.

15
00:02:11,225 --> 00:02:16,299
To change “Prefault” and “Post Fault” states you should use “Setting” tab and “Time” section.

16
00:02:16,324 --> 00:02:20,372
More explanation about this section will be provided in “Setting” videos.

17
00:02:20,397 --> 00:02:29,335
Just note that if “Pt Connection” is wired as “At Busbar”, in “Post Fault” the zero current and nominal voltage will not be available.

18
00:02:29,360 --> 00:02:37,056
The Fault Type is specified in “Fault Type” section. These Faults include phase to ground, two-phase and three-phase faults.

19
00:02:37,081 --> 00:02:46,807
Before specifying the fault type and fault current, it is necessary to select the test model from among fixed current, fixed voltage and fixed resource impedance.

20
00:02:46,832 --> 00:02:53,775
In fixed current model the injection current is fixed and the voltage changes in accordance with the test impedance.

21
00:02:53,806 --> 00:03:00,057
In Constance test voltage model, the test voltage is fixed and the fault current changes in accordance with the test impedance.

22
00:03:00,082 --> 00:03:11,283
In Constance source impedance method, the source impedance includes the impedance from the origin to fault plus the impedance of ground to the fault point, angle and the grounding factor.

23
00:03:11,308 --> 00:03:15,367
By selecting “Add”, the selected test point is added to the table in this window.

24
00:03:15,392 --> 00:03:24,877
By selecting any of the rows and clicking on “Insert” option, the selected row is repeated in the table and by clicking on “Remove”, the selected point is removed.

25
00:03:24,932 --> 00:03:32,549
By selecting “Add to” option, it is possible to copy the point or points selected for one of the “Fault Types” to another “Fault Type”.

26
00:03:32,612 --> 00:03:38,424
By selecting “Remove All” option, it is possible to remove all of the test points added to the table.

27
00:03:38,473 --> 00:03:47,267
By clicking on “Sequence” option, “Sequence Test Points To” page opens where it is possible to create test points with equal steps.

28
00:03:47,362 --> 00:03:55,033
By selecting “Angle” in “Step On” field in “Step” section, the angular steps are directly entered in terms of degrees.

29
00:03:55,073 --> 00:04:04,978
This means that the test points are specified according to the “Origin” point entered in “Origin” section in a way that the required angles resulted in proportion to the horizon.

30
00:04:04,974 --> 00:04:16,166
For example if the start and end angles equal “45” and “90” degrees with “5” degrees as their steps and the origin points are entered for “Z” and “Phi” or “R” and “X”,

31
00:04:16,191 --> 00:04:27,814
after selecting “5” ohms as impedance and “36” degrees as the origin and by applying this settings, you can see that multiple points are added on the “Impedance View”.

32
00:04:27,839 --> 00:04:34,892
For example the last point is selected; you can see that the resulted angle is “85” degrees not “90” degrees.

33
00:04:34,924 --> 00:04:39,596
This happens because the “Origin” point is also considered as one of the points.

34
00:04:39,627 --> 00:04:50,291
But by selecting “Direction”, an “angle” is specified in “Angle” field where from the “Origin” point with the length entered in “Length” field and with steps specified in “Step Size”,

35
00:04:50,316 --> 00:04:53,057
some points are shot on the characteristic curve.

36
00:04:53,072 --> 00:04:57,408
Note that the length and the steps of the points are in terms of ohm.

37
00:04:57,424 --> 00:05:06,478
For example if the angle is “45” degrees, the length is “5”, the step size is “0.5” ohm and the origin point is “0” ohm,

38
00:05:06,487 --> 00:05:14,142
by applying this settings you can see that some points are created in “45” degrees with “0” origin in “Impedance View”.

39
00:05:14,182 --> 00:05:25,213
Note that in both states of “Angle” and “Direction”, it is possible to make the origin dependent on the length of the line and specify it in form of a percentage of it in “Z Relative” section.

40
00:05:25,238 --> 00:05:34,025
If the performed test has “Failed” points, by selecting “Clear All Failed Tests” option, it is possible to clear the results of all these points.

41
00:05:34,041 --> 00:05:48,330
In “Detail” section, the information related to “Trip” nominal time, the allowed operation time range, actual time and test point evaluation are entered in “T nom”, “T min” “T max”, “T act” and “State” fields respectively.

42
00:05:48,355 --> 00:05:52,963
The test points are entered with detail in the table at the bottom of the page.

43
00:05:53,010 --> 00:06:03,627
The details include test evaluation, test current, nominal time, operation time, fault value in terms of percent and seconds and the minimum and maximum operation time.

44
00:06:03,705 --> 00:06:09,471
Also, if you wish to add a comment about any of the test points, you can use the “User Comment” cell.

45
00:06:09,495 --> 00:06:15,275
At the bottom of this page, it is possible to select test points table from different “Fault Types”.

46
00:06:15,275 --> 00:06:19,439
To test, a point is shot in “L1-E” “Fault Type”.

47
00:06:19,455 --> 00:06:26,697
By using “Add to” option, this point is also added to “L1L2” and “L1L2L3” “Fault Types”.

48
00:06:27,916 --> 00:06:36,517
Note that if “L1-E” option remains checked, the point added for the “L1-E” “Fault Type” will be repeated in this “Fault Type”.

49
00:06:36,682 --> 00:06:40,416
Then, open the “Signal View” window and run the test.

50
00:06:40,455 --> 00:06:46,267
You can see how the voltage and current signals are injected for every test point.

51
00:06:46,362 --> 00:06:52,962
After testing each point, its evaluation is recorded in the table as well as the “Impedance View”.
