﻿1
00:00:19,219 --> 00:00:21,250
"Pick Up - Drop Off" Window

2
00:00:22,109 --> 00:00:26,015
In this tab, the relay's "Pick Up - Drop Off" test is performed

3
00:00:26,562 --> 00:00:30,702
The "Test Point" section is where the test points are configured.

4
00:00:31,016 --> 00:00:41,093
If you want to carry out the "Pick Up - Drop Off" test for a "Non-directional" relay, you need to select "Current" from the "Target type" section.

5
00:00:41,563 --> 00:00:46,485
For angle-based "Pick Up - Drop Off" testing, select "Angle" instead.

6
00:00:46,719 --> 00:00:51,875
Start by selecting "Current" to perform the test for a "Non-directional" relay.

7
00:00:52,891 --> 00:00:57,031
In the "Pickup" field, the relay's pickup current is set

8
00:00:57,344 --> 00:01:04,218
meaning that, ideally, the relay should pick up at this current. Here, it is set to 1 ampere

9
00:01:04,688 --> 00:01:10,546
In the "Reset Ratio" field, the ratio of the relay’s drop-off current to its pickup

10
00:01:10,859 --> 00:01:16,484
current is defined. In this case, it's set to 0.95.

11
00:01:16,796 --> 00:01:20,468
. Note that once the "Reset Ratio" is configured

12
00:01:20,781 --> 00:01:27,968
the software automatically calculates the relay’s drop-off current and displays it in the "Drop Off" field

13
00:01:28,984 --> 00:01:33,437
The "Angle" field defines the angle of the pickup current.

14
00:01:33,828 --> 00:01:40,781
This parameter is not relevant for non-directional relays, so depending on the test type,

15
00:01:40,938 --> 00:01:44,376
, the user can set it to any desired value

16
00:01:44,922 --> 00:01:50,625
Now, since the "Pickup - Drop Off" test uses both increasing and decreasing Step Ramps,

17
00:01:50,859 --> 00:01:55,312
the time intervals between each step must be configured

18
00:01:55,625 --> 00:02:06,250
These are set in the "Pickup Δt" and "Drop Off Δt" fields, which by default are both set to 100 milliseconds

19
00:02:07,006 --> 00:02:16,849
The "ΔI" field determines the current increment for each step, which in this case is set to 20 milliamperes

20
00:02:17,162 --> 00:02:24,115
Next, the "Pickup Start" field sets the initial current value for the ramp signal during the test

21
00:02:24,662 --> 00:02:28,880
By default, this is set to 800 milliamperes

22
00:02:29,115 --> 00:02:34,818
meaning the ramp will begin at 800 milliamperes and increase from there

23
00:02:35,443 --> 00:02:40,130
Additionally, the final current values of the ramp must also be defined.

24
00:02:40,443 --> 00:02:47,630
The end value for "Pickup" is set in the "Pickup End" field, and for "Drop Off", in the "Drop Off End" field

25
00:02:48,256 --> 00:02:58,177
For example, in this case, the final current for "Pickup" is set to 1.2 amperes, and for "Drop Off", it is 800 milliamperes

26
00:02:59,115 --> 00:03:08,568
Now, based on the values configured in the "Test Point" section, the software applies an increasing ramp for the Pickuptest.

27
00:03:08,881 --> 00:03:15,287
This ramp starts from 800 milliamperes and goes up to 1.2 amperes

28
00:03:15,443 --> 00:03:20,208
with 20-milliampere steps and 100-millisecond intervals.

29
00:03:20,521 --> 00:03:25,208
The relay is then expected to respond with a Pickup signal

30
00:03:25,364 --> 00:03:31,301
.Next, a decreasing ramp is applied with the same 20-milliampere steps

31
00:03:31,615 --> 00:03:36,224
and 100-millisecond intervals until the relay drops

32
00:03:36,771 --> 00:03:41,927
drops off. These ramp signals can be visualized in the "Signal View" section

33
00:03:42,553 --> 00:03:48,803
In the "Fault Type" section, as previously mentioned, the type of fault can be selected.

34
00:03:50,209 --> 00:03:59,818
Then, by clicking the "Add" button, this test point is added both to the relay’s characteristic curve in the "Overcurrent Characteristic" window

35
00:04:00,209 --> 00:04:06,302
and as a new row in the "Pickup - Drop Off" table at the bottom of the screen

36
00:04:06,615 --> 00:04:16,068
In the "Detail" section, once the test is complete, the relay’s actual pickup current is shown in the "Pickup act" field

37
00:04:17,099 --> 00:04:22,411
and the actual drop-off current is displayed in the "Drop Off act" field

38
00:04:23,193 --> 00:04:29,521
There are two important points to keep in mind when performing the "Pickup - Drop Off" test.

39
00:04:30,068 --> 00:04:34,599
This test is performed at only one point for each "Fault Type".

40
00:04:35,224 --> 00:04:42,568
Immediately after receiving the Pickup contact, the decreasing ramp begins from the "Pickup End" value.

41
00:04:42,803 --> 00:04:48,193
However, if you want the ramp-down to start from the exact point

42
00:04:48,349 --> 00:04:57,255
where the relay picked up, you need to go to the "Settings" tab and check the option "Continue Last State Amplitude".

43
00:04:58,818 --> 00:05:05,615
For "Directional" testing in this section, after selecting the "Test Object" from the top toolbar

44
00:05:06,006 --> 00:05:11,630
, right-click on the "Overcurrent" block and go to the "Relay Parameters" tab.

45
00:05:12,021 --> 00:05:19,208
There, set the relay’s directional function to "Directional".Next, in the "Elements" tab

46
00:05:19,521 --> 00:05:30,146
you can create, for example, two stages with different pickup current values. In the "Direction" column for both stages, select "Forward".

47
00:05:35,615 --> 00:05:40,068
Then, open the "Define Element Directional Behavior" tab.

48
00:05:40,615 --> 00:05:46,474
In the "Trip Sector Definition" section, select the "RCA-90" method

49
00:05:46,631 --> 00:05:53,271
and set the "Maximum torque angle" to -60 degrees and the "Sector opening"

50
00:05:53,506 --> 00:06:00,302
to 180 degrees, then confirm the settings.To view the "Directional Plane"

51
00:06:01,084 --> 00:06:05,849
and select test points, open the "Medium Detail View" window.

52
00:06:06,787 --> 00:06:14,599
In this window, the relay’s operating range for different stages is displayed using color-coded sectors.

53
00:06:15,146 --> 00:06:24,208
You’ll notice that the sector is defined between 30 degrees (calculated as 90 minus 60) and -150 degrees (90 minus 60, then negative)

54
00:06:25,271 --> 00:06:35,193
In the "Pickup - Drop Off Data" section, the selected test line from the test lines created in the "Test View" table is displayed.

55
00:06:36,521 --> 00:06:45,896
On the left-hand side of this window, you’ll find a set of tools for interacting with the graph, such as zooming and panning.

56
00:06:47,303 --> 00:06:55,583
You can also right-click on the graph to view "Test Information" and "Result Information" for each test directly in this window.

57
00:06:57,771 --> 00:07:02,146
Now, from the "Target type" field, "Angle" is selected.

58
00:07:02,615 --> 00:07:08,630
This means that the Ramp states generated by the software will apply to the angle.

59
00:07:09,256 --> 00:07:17,927
.In this mode, the fault current magnitude and its angle are entered in the "Current" and "Angle" fields, respectively.

60
00:07:18,396 --> 00:07:25,974
The angular step size for each increment is set in the "Δ∅" field.

61
00:07:26,912 --> 00:07:31,911
The starting angle for the Ramp state is entered in the "Pickup Start" field

62
00:07:32,928 --> 00:07:38,240
and the final angle for this ramp is set in the "Pickup End" field.

63
00:07:38,943 --> 00:07:45,739
Finally, the ending angle for the decreasing ramp state is set in the "Drop Off End" field.

64
00:07:46,756 --> 00:07:50,896
When performing this test, you need to carry it out twice

65
00:07:51,365 --> 00:07:57,693
once at the upper angle limit and once at the lower angle limit of the Pickup current.

66
00:07:58,084 --> 00:08:02,380
. So, you must create two search lines at the boundary points

67
00:08:02,615 --> 00:08:08,943
The first search line is configured with a Pickup current of 1 ampere and an angle of 30 degrees

68
00:08:09,334 --> 00:08:15,427
You’ll see that the related test fields on the right are automatically populated by the software.

69
00:08:16,131 --> 00:08:21,208
Note that these values can be manually adjusted by the user

70
00:08:21,531 --> 00:08:29,422
In the graphical display of the "Medium Detail View" window, the selected angular test range is shown as a black arc

71
00:08:30,516 --> 00:08:35,828
By clicking the "Add" button, this test line is added to the "Pickup - Drop Off" test table.

72
00:08:36,141 --> 00:08:43,015
To create the second test line, set the angle to -150 degrees in the "Angle" field

73
00:08:43,406 --> 00:08:48,093
and this line will also be added to the list of test lines.

74
00:08:48,406 --> 00:08:55,906
As you select each of the created test lines, their details are displayed in the "Pickup - Drop Off Data" window.
