00:00:19,297 --> 00:00:21,093
Test View Window

2
00:00:22,500 --> 00:00:28,437
The "Test View" window, as previously mentioned, is one of the panels within the "Overcurrent" room

3
00:00:28,906 --> 00:00:37,187
This window includes five tabs: "Shot Test", "Pickup-Drop Off", "Setting", "Trigger", and "Binary Output".

4
00:00:37,734 --> 00:00:42,812
Test points are defined within the "Shot Test" and "Pickup-Drop Off" tabs.

5
00:00:43,047 --> 00:00:48,437
In the "Shot Test" tab, you can select the fault type and define specific test points

6
00:00:48,906 --> 00:00:54,609
, then evaluate the results after running the test. In this tab, under the "Test Point" section

7
00:00:54,922 --> 00:01:03,125
the fault current is set, and under "Fault Type", you choose the type of fault to be simulated. Within the "Test Point" section

8
00:01:03,281 --> 00:01:10,859
the fault current is entered in the "I Test" field, and the angle between the current and voltage is set in the "Angle" field

9
00:01:11,172 --> 00:01:16,640
Keep in mind that this angle setting is only relevant for conducting "Directional" tests.

10
00:01:17,656 --> 00:01:21,015
If you want to define the fault current as a multiple

11
00:01:21,406 --> 00:01:26,953
of the rated CT current or the pickup current of one of the defined stages,

12
00:01:27,188 --> 00:01:35,704
, first, check the "ITest Relative" option. Then, in the "Factor" field, enter the desired multiplier,

13
00:01:36,172 --> 00:01:42,890
and from the "Relative to" dropdown menu, select the reference current to base the fault current on.

14
00:01:43,281 --> 00:01:50,312
This reference current can be either the pickup current of one of the stages or the CT secondary rated current

15
00:01:50,469 --> 00:01:54,687
Once the fault current has been defined, select the fault type

16
00:01:54,844 --> 00:01:59,218
 from the list of standard options in the "Fault Type" section.

17
00:02:00,390 --> 00:02:07,265
. These include various types of phase-to-ground faults, phase-to-phase faults,

18
00:02:07,646 --> 00:02:15,927
three-phase faults, unbalance, "3I0", as well as individual phase faults like "L1", "L2", and "L3"

19
00:02:16,709 --> 00:02:20,536
To understand the concept of "L1," "L2," and "L3" faults

20
00:02:20,849 --> 00:02:29,443
imagine a line where a transformer with a delta connection is present on the primary side. When a fault occurs on the secondary side

21
00:02:30,146 --> 00:02:38,818
the corresponding phase current of the fault will flow on the primary side, and the fault current will be supplied by the other phase or phases.

22
00:02:38,974 --> 00:02:43,583
.To better grasp the difference between this type of fault and single-phase faults

23
00:02:43,740 --> 00:02:50,693
faults like "L1-E," "L2-E," or "L3-E," you can use the "Vector View" window

24
00:02:50,849 --> 00:02:55,536
to observe the current values of other phases during a fault

25
00:02:55,849 --> 00:03:00,146
. For example, compare "L1-E" and "L1" faults:

26
00:03:00,537 --> 00:03:07,568
in an "L1-E" fault, the current values in phases 2 and 3 are zero, but in an "L1" fault,

27
00:03:08,115 --> 00:03:13,115
 the current in phase 1 is supplied by phases 2 and 3.

28
00:03:13,584 --> 00:03:19,990
Testing unbalance faults, also known as "Negative Sequence" faults, can be done by selecting "I2".

29
00:03:20,381 --> 00:03:25,068
Since relays detect unbalance faults based on the negative sequence current,

30
00:03:25,537 --> 00:03:31,630
, when this "Fault Type" is selected, the injected fault current will be purely the negative sequence component.

31
00:03:31,943 --> 00:03:38,036
To inject an "Earth Fault" current, you should use "3I0" when the relay operates in "Summation" mode

32
00:03:38,193 --> 00:03:41,318
and "L-E" when it operates in "Measuring" mode.

33
00:03:41,709 --> 00:03:49,677
Once the fault current and type have been specified, clicking the "Add" button will insert the selected test point into the table in this window

34
00:03:49,990 --> 00:03:52,880
Now, a key point about test points:

35
00:03:53,115 --> 00:03:59,365
if you check the "ITest Relative to" option and define the test current based on a parameter,

36
00:03:59,678 --> 00:04:04,444
point will always remain dependent on that parameter.

37
00:04:05,068 --> 00:04:11,318
So, if the parameter value changes, the test current will automatically adjust

38
00:04:11,943 --> 00:04:20,771
. For example, if you enable "ITest Relative to", set the test current to be twice the rated current, and add that point to the test table

39
00:04:21,396 --> 00:04:29,208
then change the rated current to 5 amps—you’ll see that the test current increases from 2 amps to 10 amps accordingly

40
00:04:32,959 --> 00:04:41,396
By selecting a row and clicking "Insert", the selected test point is duplicated and added below the original in the table

41
00:04:42,724 --> 00:04:46,240
Clicking "Remove" deletes the selected row

42
00:04:46,709 --> 00:04:52,958
Using the "Add to" option, you can copy selected test points from one "Fault Type" to another.

43
00:04:53,662 --> 00:04:59,677
And finally, clicking "Remove All" deletes all test points listed in the table.

44
00:05:00,146 --> 00:05:02,958
By clicking on the "Sequence" option

45
00:05:03,349 --> 00:05:10,536
the "Sequence Test Points to" window opens, allowing you to create multiple test points with equal steps.

46
00:05:14,834 --> 00:05:18,349
. In the "Advanced" mode, under the "Current Data" section

47
00:05:18,818 --> 00:05:23,818
you can define steps to increase or decrease either the current magnitude or phase angle.

48
00:05:24,365 --> 00:05:30,458
 In the "Sequence Type" field, if you select "Current", the current steps are entered directly in amperes.

49
00:05:30,693 --> 00:05:38,505
But if you choose "Factor", the current is defined as a multiple of a parameter selected in the "Relative to" dropdown

50
00:05:39,287 --> 00:05:46,552
This reference parameter can be the "Pickup" current of one of the defined "Stages", or the secondary rated current of the "CT".

51
00:05:46,709 --> 00:05:53,974
Here as well, you'll see the "ITest Relative" checkbox, which works exactly as described in the previous section.

52
00:05:54,209 --> 00:05:58,661
In the "Start Value" field, you define the starting point of the current sequence

53
00:05:59,053 --> 00:06:05,615
in the "End Value" field, the final point; and in the "Step Size" field, the increment between each test point.

54
00:06:06,006 --> 00:06:12,958
. For example, if you set the "Sequence Type" to "Factor", choose "Relative to" as the "Pickup" current of Stage 1

55
00:06:13,349 --> 00:06:19,365
 define the "Start Value" as 2 times the pickup current, the "End Value" as 6 times,

56
00:06:19,787 --> 00:06:23,146
and the "Step Size" as half the pickup current

57
00:06:23,615 --> 00:06:32,599
you'll see that the "Step Count"—which indicates the number of current steps or test points—is automatically calculated and shown as 9.

58
00:06:33,381 --> 00:06:38,615
In addition, under the "Angle Data" section, you can enter the starting angle

59
00:06:39,084 --> 00:06:46,427
in the "Start Value" field, the final angle in the "End Value" field, and the angular step size in the "Step Size" field

60
00:06:46,740 --> 00:06:51,896
for example, 30, 45, and 5 degrees respectively.

61
00:06:52,209 --> 00:06:57,990
The "Step Count" field here shows the number of angle steps, which in this case is 4.

62
00:06:58,693 --> 00:07:03,458
The "Total Shot Count" field displays the total number of calculated test points.

63
00:07:03,849 --> 00:07:12,443
This number reflects how each point—based on the current and angle steps defined above—will be generated and added to the test table.

64
00:07:13,146 --> 00:07:17,677
Once you select the "Fault Type" options "L1-E" and "L2-E"

65
00:07:18,146 --> 00:07:22,990
and confirm them, you'll see that these points are added to the test point table.

66
00:07:24,084 --> 00:07:31,271
In the "Simple (1.5X, 2X, 4X)" mode, you can select and add 1.5,

67
00:07:31,662 --> 00:07:37,833
2, or 4 times the secondary nominal current of the "CT" for different "Fault Type" options.

68
00:07:38,928 --> 00:07:43,458
If a test contains points with a "Failed" evaluation,

69
00:07:43,928 --> 00:07:49,552
clicking the "Clear All Failed Tests" button will remove these points from the table,

70
00:07:49,943 --> 00:07:53,458
changing their status from "Failed" to "Not Tested".

71
00:07:54,396 --> 00:07:59,318
In the "Detail" section, the nominal "Trip" time is recorded in the "t nom" field,

72
00:07:59,943 --> 00:08:05,880
, the allowed operation time range is recorded in the "t min" and "t max" fields, the actual time in the "t act" field,

73
00:08:06,193 --> 00:08:13,614
 and the test point evaluation is registered in the "State" field.

74
00:08:14,398 --> 00:08:17,992
By double-clicking on the "More Details (Double click to expand)" section

75
00:08:18,383 --> 00:08:22,914
the details related to the relay's characteristic curve will be displayed.

76
00:08:23,773 --> 00:08:29,945
In the table at the bottom of the page, the test points are listed along with various details.

77
00:08:30,336 --> 00:08:34,789
These details include the test evaluation, test current

78
00:08:35,180 --> 00:08:43,539
test point angle, whether the test point is "Relative" or not, the factor and base parameter if the point is "Relative"

79
00:08:44,086 --> 00:08:49,398
", nominal time, operating time, error value in percentage and seconds,

80
00:08:49,555 --> 00:08:52,835
and the minimum and maximum operating times.

81
00:08:53,383 --> 00:09:00,335
Additionally, if you want to add a note for any test point, you can use the "User Comment" cell.

82
00:09:01,039 --> 00:09:06,585
Below this section, the test points for different "Fault Type" options can be selected.

83
00:09:06,977 --> 00:09:12,210
By right-clicking on this table and selecting the "Show/Hide" option,

84
00:09:12,758 --> 00:09:18,070
you can configure which columns are displayed in the table or in the "Report".
