Relay Settings in the "Overcurrent" Room – Part 4

2
00:00:23,516 --> 00:00:30,859
To perform the “Overcurrent Directional” test, first select “Test Object” from the top toolbar.

3
00:00:31,172 --> 00:00:37,265
. Then, in the “Device” section of the tree diagram, enter the “I Primary” and “I Secondary” values

4
00:00:37,891 --> 00:00:43,593
, which represent the “CT ratio”. Make sure these values match exactly

5
00:00:43,671 --> 00:00:48,514
any mismatch between them will result in incorrect test outcomes.

6
00:00:48,672 --> 00:00:54,140
After double-clicking on the "Over Current" block in the "Relay Parameters" page

7
00:00:54,531 --> 00:00:59,296
, go to the "Relay Behavior"section and select the "Directional" option.

8
00:00:59,688 --> 00:01:05,312
Next, in the "VT Connection" section, set the direction of the VT

9
00:01:05,547 --> 00:01:12,109
and in the "Start Point Connection CT" section, define the direction of the CT star point.

10
00:01:12,422 --> 00:01:18,515
Be aware that any mismatch in these settings compared to the relay configuration

11
00:01:18,672 --> 00:01:25,000
can cause a “180-degree phase shift” between the device settings and the relay.

12
00:01:25,703 --> 00:01:34,140
After configuring the current, time, and angle tolerances in the "Relay Parameters" section, go to the "Element" area.

13
00:01:34,453 --> 00:01:40,234
Once you've entered the desired Stages, you need to specify the relay protection direction

14
00:01:40,702 --> 00:01:49,764
either "Forward" or "Reverse"—in the "Direction" field. Next, under the "Define Element Directional Behavior" tab

15
00:01:50,391 --> 00:01:59,531
, input the values for Maximum Torque Angle and Sector Opening based on the "RCA-90" method

16
00:01:59,688 --> 00:02:07,968
or the formula "(90 – Setting Angle) - 90". The method for calculating these parameters

17
00:02:08,193 --> 00:02:13,427
will be explained in the videos related to protection function testing.

18
00:02:13,818 --> 00:02:20,302
In Directional mode, a Directional Plane is added to the page, allowing you to visualize the range

19
00:02:20,771 --> 00:02:24,052
within which the relay provides protection

20
00:02:24,599 --> 00:02:34,833
In the "View Resulting Characteristic" tab, you can see both the overall characteristic curve and the “Directional Plane” diagram side by side

21
00:02:35,693 --> 00:02:44,130
. Note that if you have multiple directional “Stages”, each with a different Pick-Up current and operation time

22
00:02:44,365 --> 00:02:53,896
they will be shown with different colors on the characteristic curve—based on the color assigned to each one in the table above

23
00:02:55,303 --> 00:03:02,021
To display the “Directional” characteristic curve, also known as the Directional Plane,

24
00:03:02,412 --> 00:03:11,708
, and to add test points, select "Medium Detail View" from the top toolbar, then place your test points directly on the curve.

25
00:03:12,959 --> 00:03:18,661
If the relay’s “Config” allows for exporting an “XRIO” file

26
00:03:19,053 --> 00:03:24,209
another way to create the relay’s characteristic curve is by using this “XRIO” file.

27
00:03:25,693 --> 00:03:32,724
To do this, first select "Test Object" from the top toolbar, then click on "Import From List".

28
00:03:33,037 --> 00:03:39,755
In the "Search" field, specify the relay “Template” type—for example, here we’ll select "7UT613".

29
00:03:39,912 --> 00:03:48,349
Next, go to the "File" section and choose "Load Relay Setting".

30
00:03:48,818 --> 00:03:58,740
Under "Relay Config Type", select the “XRIO” format, and then load the “XRIO” file into the “Config File Path”.

31
00:03:59,365 --> 00:04:08,740
To ensure the imported data is correct, you can review the entered parameters using the tree diagram in this section.

32
00:04:09,211 --> 00:04:17,257
. If needed, use the "Reference Map" to check the parameter values that affect relay operation.

33
00:04:17,648 --> 00:04:25,773
If any discrepancies are found compared to the relay’s actual settings, make the necessary corrections.
