Relay Settings in the "Overcurrent" Room – Part 2

2
00:00:23,671 --> 00:00:31,170
After defining a “Stage” for the relay’s trip characteristic curve, you can set the current and time limits

3
00:00:31,250 --> 00:00:39,297
for the curve in the “Active Range Limits” section. To do this, first check the “Active Range Limit” box

4
00:00:39,531 --> 00:00:47,889
to activate the section. Then, enter the desired values in the relevant fields. For example, if you set “tmin”

5
00:00:48,516 --> 00:00:57,734
” to 1 second and “tmax” to 30 seconds, you’ll notice that the characteristic curve is now limited within this time range.

6
00:00:57,968 --> 00:01:07,577
In the current range section, you might enter “Imin” as 1.2 times “Iref”,

7
00:01:07,813 --> 00:01:17,421
and “Imax” as 100 times “Iref”. On the right-hand side of the window, you’ll see that the relay’s characteristic curve is now defined between 1.2 and 100 times the reference current,

8
00:01:18,438 --> 00:01:23,516
which is “Iref”, or the secondary rated current of the CT.

9
00:01:23,750 --> 00:01:29,922
Additionally, for relays that operate in “Definite Time” mode beyond a certain current level,

10
00:01:30,313 --> 00:01:35,937
you can use the “Limit t from I” option. For example,

11
00:01:36,172 --> 00:01:42,656
, if you have a relay that starts operating from 1.1 times the defined “Pickup” current,

12
00:01:43,125 --> 00:01:50,468
and switches to “Definite Time” mode from 20 times the “Pickup” current, you should enter “1.1”

13
00:01:50,625 --> 00:01:57,421
” in the “I min” field, and 20 in the “Limit t from I” field.

14
00:01:58,359 --> 00:02:04,609
Keep in mind that the “Range Limits” settings can also be adjusted from the “Manage / Select Characteristic” page.

15
00:02:04,943 --> 00:02:09,005

If the relay’s characteristic curve consists of multiple “Stages”,

16
00:02:09,318 --> 00:02:14,630
you’ll need to define the required number of stages using the “Add” button.

17
00:02:14,865 --> 00:02:20,333
. Then, by configuring the parameters for each one, you can proceed with testing the relay

18
00:02:20,490 --> 00:02:26,036
For instance, here we create another stage of the “Definite Time” type.

19
00:02:26,271 --> 00:02:36,505
We set its pickup current to 1.5 times I ref, and its operating time to 200 milliseconds in the “Time” column

20
00:02:36,818 --> 00:02:44,943
As you click on each stage, its corresponding characteristic curve is displayed in the right-hand window.

21
00:02:45,178 --> 00:02:55,958
Then, under the “View Resulting Characteristic” tab, you can see the final characteristic curve generated by combining all the defined stages in the table

22
00:03:01,506 --> 00:03:08,458
In the Color column, each stage is assigned a specific color for visual distinction

23
00:03:08,849 --> 00:03:16,661
And in the “Active” column, you can enable or disable any defined stage using the “Yes” or “No” options.

24
00:03:17,053 --> 00:03:26,975
For example, here, the second stage is deactivated by selecting “No”, and it is removed from the resulting characteristic curve.

25
00:03:27,756 --> 00:03:35,177
Using the “Save as User-defined” option, you can save the characteristic curve created in any “Stage”

26
00:03:35,334 --> 00:03:41,740
to the “User Defined” folder under the “Manage / Select Characteristic” window for future use.

27
00:03:46,584 --> 00:03:53,224
For example, here we select the first stage and click on “Save as User-defined”.

28
00:03:53,459 --> 00:03:59,474
This opens the “Manage / Select Characteristic” window. Then, by clicking “OK”

29
00:03:59,709 --> 00:04:07,365
and returning to this window, you can see that the curve and its settings have been saved under the name

30
00:04:07,516 --> 00:04:12,906
“IEC Normal Inverse2” in the “User Defined” folder.
