Relay Settings in the "Overcurrent" Room – Part 1

2
00:00:24,141 --> 00:00:31,562
As mentioned earlier, the first step in relay testing is entering the relay specifications into the software.

3
00:00:31,719 --> 00:00:38,437
To begin, we’ll first go over how to input the settings for a "Non-directional" relay.

4
00:00:38,672 --> 00:00:48,828
Start by opening the "General Test Object" window. From the "Device" block, enter the current transformer ratio, or "CT" ratio.

5
00:00:48,906 --> 00:00:56,250
Then, by double-clicking on the "Overcurrent" block, the "Overcurrent Protection Parameters" window will open,

6
00:00:56,563 --> 00:01:04,063
, where you can enter the relay settings. In the "Relay behavior" section, you’ll define the directionality

7
00:01:04,297 --> 00:01:11,328
of the protection function, the configuration of the "VT"s, and how the "CT"s are connected.

8
00:01:11,484 --> 00:01:19,140
 Since the relay we’re working with here is "Non-directional", select "Non-directional" in this window.

9
00:01:19,453 --> 00:01:29,062
Please note that the "VT Connection" and "CT Connection" options are only active when the relay is set to "Directional" mode.

10
00:01:29,375 --> 00:01:33,984
For "Non-directional" relays, these options will be disabled.

11
00:01:34,453 --> 00:01:40,859
In the "Tolerances" section, you can set the current and time tolerances for all relays,

12
00:01:41,328 --> 00:01:46,171
and the angle tolerance specifically for "Directional" relays.

13
00:01:46,328 --> 00:01:54,609
To set the current tolerance, enter the desired value as a percentage of the test current in the "Relative" field.

14
00:01:54,766 --> 00:02:00,156
As you can see, the default setting is 5%.

15
00:02:00,703 --> 00:02:08,671
You can also set the tolerance based on a multiple of the nominal "CT" current using the "Absolute" field,

16
00:02:09,021 --> 00:02:14,724
where the actual calculated value is displayed in the field next to it.

17
00:02:15,193 --> 00:02:24,177
Keep in mind, the software automatically selects the larger of the two defined tolerances when evaluating the characteristic curve.

18
00:02:24,803 --> 00:02:34,569
 For example, if the test current is set to 1 amp, a 5% tolerance results in a pickup range between

19
00:02:34,803 --> 00:02:41,911
0.95 amps and 1.05 amps

20
00:02:42,068 --> 00:02:49,255
. But if an absolute tolerance of 40 milliamps is used, the range would be between

21
00:02:49,568 --> 00:02:55,036
0.96 amps and 1.04 amps.

22
00:02:55,193 --> 00:03:04,568
. In this case, the software uses the larger range—between 0.95 and 1.05 amps

23
00:03:04,645 --> 00:03:12,145
as the effective tolerance. In the "Time" section, time tolerances can also be configured

24
00:03:12,381 --> 00:03:22,302
as either a percentage or a fixed value. For "Directional" relays, the angle tolerance is set in the "Angle" section.

25
00:03:23,787 --> 00:03:35,349
The “Compatibility” and “Other” sections were covered in the first video of the “Overcurrent” room. To define a characteristic curve, go to the "Elements" tab.

26
00:03:35,584 --> 00:03:45,583
In the "Element Name" column, you enter a name for the defined "Stages"—for example, here we’re naming it "Stage1".

27
00:03:45,974 --> 00:03:51,130
In the "Tripping Characteristic" column, you can select the type of characteristic curve.

28
00:03:51,287 --> 00:03:56,443
By default, it is set to "IEC Definite Time".

29
00:03:56,599 --> 00:04:06,599
To change the characteristic curve, either double-click on "IEC Definite Time", or click the three-dot icon

30
00:04:06,834 --> 00:04:13,396
in the "Characteristic" section to open the "Manage / Select Characteristic" window.

31
00:04:13,786 --> 00:04:20,895
. In the "Standard" section, you’ll find all the characteristic curves defined under the IEC standard.

32
00:04:21,209 --> 00:04:28,865
By selecting any of them, you can view its formula and coefficients in the "Characteristic" area.

33
00:04:30,584 --> 00:04:39,021
It’s important to make sure the curve selected here matches the characteristic curve that’s already configured in the relay.

34
00:04:41,756 --> 00:04:46,365
If the relay’s characteristic curve is not listed in this section,

35
00:04:46,599 --> 00:04:56,052
or if its coefficients differ from the formulas shown here, you’ll need to go to the "Predefined" folder.

36
00:04:56,365 --> 00:05:09,255
From there, look through the "Inverse", "I2T", "IAC", or "Reclosers" folders to find the curve formula that matches the relay and select it

37
00:05:10,115 --> 00:05:16,599
nIf the relay’s formula isn’t available in any of those folders, you can go to the "Custom" folder.

38
00:05:16,834 --> 00:05:24,255
By selecting "Custom Formula", you can enter the desired formula manually in the designated field,

39
00:05:24,490 --> 00:05:35,583
based on the provided coefficients, as well as the "Itest/Ipickup" and "Time Dial" values—marked as "M" and "Td".

40
00:05:36,053 --> 00:05:41,991
Once entered, just click "Save" and the formula will be ready to use.

41
00:05:42,224 --> 00:05:49,099
Additionally, if the relay’s characteristic curve is defined by a table of points, you can select "Table Example 2",

42
00:05:49,256 --> 00:05:56,130
then click "Copy to User Defined". After that, choose it from the "User Defined" folder

43
00:05:56,443 --> 00:06:03,083
and use the "Grabber" tool in the software to input the relay’s curve point by point.

44
00:06:03,630 --> 00:06:07,926
This way, you’ll be able to visualize the curve directly.

45
00:06:08,162 --> 00:06:14,724
This window and its functions will be explained in full detail in the upcoming videos.

46
00:06:15,787 --> 00:06:21,490
If the relay’s characteristic curve formula already exists in the software,

47
00:06:21,646 --> 00:06:28,052
but the coefficients used in it differ from those specified in the relay manual,

48
00:06:28,209 --> 00:06:39,693
you’ll need to select the desired formula, click on "Copy to User Defined", and then adjust the coefficients accordingly in the "User Defined" folder.

49
00:06:40,006 --> 00:06:47,661
For example, here we select the formula for the "Basler I2T-46N"

50
00:06:48,053 --> 00:06:51,881
" curve and copy it into the "User Defined" folder.

51
00:06:52,584 --> 00:06:58,521
Now, by selecting it, we can enter the required coefficients based on the relay manual.

52
00:06:58,678 --> 00:07:07,350
. After clicking "Save", the new curve with the updated coefficients will be stored in the software and ready for use.

53
00:07:08,443 --> 00:07:14,380

To continue, the "IEC Normal Inverse" curve is selected here.

54
00:07:16,099 --> 00:07:23,755
As you can see, in the "Elements" tab, a "Stage" of the type "IEC Normal Inverse" has been added.

55
00:07:23,912 --> 00:07:30,161
Now, in the "I Pick-up" column, the relay's pick-up current must be set as a multiple

56
00:07:30,396 --> 00:07:37,505
of the CT’s secondary rated current—here, it’s set to 1.1.

57
00:07:37,895 --> 00:07:46,723
You can also set the pick-up current using the "I Pick-up" field at the bottom of this tab. Once it’s configured,

58
00:07:47,113 --> 00:07:51,957
 its actual value will be displayed in the "Absolute" column.

59
00:07:52,115 --> 00:07:59,849
Next, in the "Time" column, the relay’s TMS—or "Time Dial" setting—is entered.

60
00:08:00,084 --> 00:08:05,709
This value can also be entered from the "Time Index" field at the bottom of the tab;

61
00:08:06,099 --> 00:08:10,551
; in this case, it’s set to 0.5.

62
00:08:11,102 --> 00:08:21,335
In the "Reset Ratio" column, the relay’s drop-out ratio is defined, which by default is set to 0.95

63
00:08:22,117 --> 00:08:30,789
And finally, in the "Direction" column, you’ll notice that this curve has been defined as "Non-Directional".
