﻿1
00:00:18,906 --> 00:00:21,484
Introducing Over Current room

2
00:00:21,641 --> 00:00:26,875
This room is used for testing overcurrent functions. It includes three main windows

3
00:00:27,109 --> 00:00:31,562
: “Test View”, “Over Current Characteristic”, and “Medium Detail View”

4
00:00:31,875 --> 00:00:37,109
These are used to enter test points and display them on the characteristic curve.

5
00:00:38,281 --> 00:00:45,703
The first step in relay testing is to input the relay information and settings into the software.

6
00:00:45,938 --> 00:00:52,656
. To do this, select “Test Object” from the top toolbar. Then, under the “Device” section

7
00:00:52,813 --> 00:00:59,765
 in the tree diagram, enter the “I primary” and “I secondary” values, which represent the “CT” ratio

8
00:01:00,859 --> 00:01:10,859
Please note that any mismatch between these settings and the relay’s actual configuration will lead to incorrect test results

9
00:01:13,281 --> 00:01:19,843
Next, go to the “Over Current” block in the tree diagram to enter the relay settings

10
00:01:20,078 --> 00:01:25,781
Double-clicking this block opens the “Overcurrent Protection Parameters” window,

11
00:01:26,250 --> 00:01:33,671
which includes two tabs: “Relay Parameters” and “Elements”. In the “Relay Parameters” tab,

12
00:01:33,906 --> 00:01:41,484
under the “Relay Behavior” section, start by specifying whether the relay is “Directional” or “Non-Directional”.

13
00:01:41,797 --> 00:01:52,500
Then, in the “Tolerance” section, enter the tolerance values for “Current”, “Time”, and—if you're working with a directional test—”Angle” as well.

14
00:01:54,297 --> 00:02:01,093
In the “Elements” section, you need to define the relay’s characteristic curve and its specifications.

15
00:02:01,250 --> 00:02:08,281
To do this, first select the desired type of overcurrent protection under “Selected Elements” Type.

16
00:02:08,756 --> 00:02:16,802
Then, enter the characteristic curve data into the table on this page and generate the relay’s “Curve”.

17
00:02:18,599 --> 00:02:28,755
By clicking “Add”, you can insert a new row into the table and create an additional “Curve” if the protection has multiple “Stages”.

18
00:02:29,849 --> 00:02:41,177
The “Copy to” and “Remove” options are used to apply a defined curve to other protection elements or to delete a selected row, respectively

19
00:02:41,959 --> 00:02:51,490
. The “Move Up” and “Move Down” options allow you to reorder the stages by moving a “Stage” up or down in the list.

20
00:02:53,209 --> 00:03:00,865

In the “Define Element Characteristic” tab, under the “Characteristic” section, you define the type of characteristic curve

21
00:03:01,646 --> 00:03:07,974
If you want to set current or time limits for the curve, enable the “Active Range Limits”

22
00:03:08,209 --> 00:03:12,193
checkbox and enter the relevant data in this section

23
00:03:12,349 --> 00:03:19,224
In the “Reset Characteristic” section, if a specific curve has been defined for the relay’s

24
00:03:19,303 --> 00:03:24,302
drop-off behavior, its settings can be entered here

25
00:03:25,162 --> 00:03:31,411
On the right-hand side, you can view the “Curve” of each “Stage” individually on the graph.

26
00:03:32,193 --> 00:03:40,786
In the “View Resulting Characteristic” section, the final combined curve based on the defined “Stages” is displayed.

27
00:03:41,568 --> 00:03:46,177
If the relay type has been set to “Directional” in the “Relay Behavior” page,

28
00:03:46,490 --> 00:03:51,021
an additional tab named “Define Element Directional Behavior” appears.

29
00:03:51,802 --> 00:03:57,036
. This is where you configure the zone or area the relay is protecting

30
00:03:57,662 --> 00:04:05,006
A polar diagram is also added, visually showing the angle the relay is monitoring for protection.

31
00:04:06,959 --> 00:04:12,740
In the “Overcurrent” section of the “Test Object”, there is a subsection called “Compatibility”.

32
00:04:12,896 --> 00:04:18,443
By selecting different “Element Versions”, the “Pickup” current factors for each “Element” will change.

33
00:04:19,146 --> 00:04:25,552
When you choose “Advanced Element”, the factors for the defined characteristics are applied as shown in the diagram.

34
00:04:25,787 --> 00:04:35,083
This means the “Pickup” current defined for a given characteristic is multiplied by the displayed factor and applied to the corresponding Fault Type.

35
00:04:35,318 --> 00:04:43,755
For example, if you’ve defined an element in the “Negative Sequence” and want to test it under an L1-L2 fault condition

36
00:04:44,146 --> 00:04:49,927
, the characteristic will be tested by multiplying the “Pickup” current by √3.

37
00:04:50,474 --> 00:04:56,411
These factors are derived from the positive, negative, and zero sequence matrices

38
00:04:56,724 --> 00:05:02,427
One example of how these factors are calculated is provided, and the rest follow the same method.

39
00:05:02,662 --> 00:05:09,302
However, in “Simple Fault Loops”, which are used by older relays, these factors are different.

40
00:05:09,849 --> 00:05:16,958
To put it simply, in the “Advanced Element” mode, all defined “Elements” are considered when the relay operates

41
00:05:17,115 --> 00:05:25,005
. For example, if you’ve defined one element under Phase and another under “Negative Sequence”, and you're testing an L1-L2 fault,

42
00:05:25,162 --> 00:05:31,255
, the relay will operate based on the shortest operating time between the two elements

43
00:05:31,568 --> 00:05:34,849
 In contrast, under the “Simple Fault Loops” method,

44
00:05:35,162 --> 00:05:41,646
only the “Phase Element” is involved in the relay's response for an L1-L2 fault.

45
00:05:41,803 --> 00:05:46,411
To make it easier to analyze the impact of the factors on the characteristics

46
00:05:46,568 --> 00:05:52,349
, a section called “More Details” is provided in the Test View page. By double-clicking on it,

47
00:05:52,506 --> 00:05:58,286
a window opens showing the characteristic information along with their corresponding factors.

48
00:05:58,599 --> 00:06:02,349
The main difference between “Advanced Element” and “Zero-Sensitive Elements”

49
00:06:02,506 --> 00:06:08,990
lies in the 3I0 characteristic factor, and depending on the relay’s algorithm

50
00:06:09,375 --> 00:06:12,265
one of these two options should be selected.

51
00:06:12,500 --> 00:06:19,609
In the “Other” section, there is an option called “Sensitive” as a separate fault, which is used for relays

52
00:06:19,922 --> 00:06:27,109
relays that require a dedicated current input labeled “Sensitive”. By enabling this option, a new “Sensitive” type

53
00:06:27,656 --> 00:06:32,656
is added to the list of “Elements” in the “Elements” section.

54
00:06:33,047 --> 00:06:40,000
You can then define a dedicated curve for it, and a new “Fault Type” labeled “Sensitive” will also appear in the “Test View”.

55
00:06:40,313 --> 00:06:44,843
After entering the relay specifications and confirming the changes,

56
00:06:45,078 --> 00:06:51,562
you can select test points on the characteristic curve and run the test in both the “Test View”

57
00:06:52,188 --> 00:06:59,532
and the “Characteristic View”: “Overcurrent”. Additionally, if the relay is defined as “Directional”,

58
00:06:59,844 --> 00:07:05,625
”, its polar diagram will be visible in the “Medium Detail View” window.

59
00:07:06,094 --> 00:07:15,390
. In upcoming videos, each of these sections will be explained in greater detail and with more precision.
