﻿1
00:00:18,828 --> 00:00:26,015
In this video, we’ll walk through how to transmit Sampled Value packets using the Vebko test device

2
00:00:26,406 --> 00:00:33,984
First, we connect to the device using the MAC Address and set the data acquisition rate to Fast

3
00:00:34,844 --> 00:00:42,343
 Then, under the Time Synchronizer tab, we set the time synchronization protocol to PTP.

4
00:00:42,891 --> 00:00:48,203
Next, we go to the Sequencer room and open the Hardware Configuration window.

5
00:00:48,906 --> 00:00:56,015
In the SV Setting tab, you can either load an SCL file related to the Sampled Value

6
00:00:56,328 --> 00:01:03,046
or manually define a new stream. In this tutorial, we’ll go with the second method.

7
00:01:04,141 --> 00:01:10,390
We click the Add Stream button to add a new stream, and then use the plus icon (+)

8
00:01:10,547 --> 00:01:14,921
in the first column to define the desired number of Attributes

9
00:01:15,703 --> 00:01:24,765
In this test, we’ve added four Attributes—one configured as a voltage data and the other three as current data.

10
00:01:25,469 --> 00:01:33,984
We link two of these data points to the output of the test device, and assign fixed values to the other two.

11
00:01:34,844 --> 00:01:44,921
We then set the Sample Rate to 4 kHz and specify that each packet should contain only one ASDU.

12
00:01:46,641 --> 00:01:50,937
The linked data is displayed under the Analog Output tab.

13
00:01:52,734 --> 00:01:59,453
In the Voltage Output Signal and Current Output Signal tables, you can assign each data point

14
00:01:59,844 --> 00:02:05,859
point to the voltage or current outputs of the device—or define a Virtual output.

15
00:02:06,516 --> 00:02:11,828
After applying and confirming the settings, you’ll see that two outputs

16
00:02:12,219 --> 00:02:17,375
one voltage and one current—appear in the Table View module.

17
00:02:17,844 --> 00:02:23,781
The voltage data is linked to the Phase 1 voltage output of the device

18
00:02:23,938 --> 00:02:28,000
while the current data is defined as a virtual output.

19
00:02:28,547 --> 00:02:35,187
To monitor the packets sent by the device, you can use Wireshark software

20
00:02:35,422 --> 00:02:43,781
Once the test starts, packets following the IEC 61850 Sampled Value

21
00:02:44,250 --> 00:02:47,765
protocol will be generated and visible in Wireshark

22
00:02:48,156 --> 00:02:56,203
WiresharkAs you can see, based on the configuration, each ASDU contains four Data Attributes

23
00:02:56,438 --> 00:03:04,016
two of them are set to fixed values, while the other two are dynamically changing.
