﻿1
00:00:23,620 --> 00:00:23,713
A

2
00:00:23,714 --> 00:00:23,807
An

3
00:00:23,808 --> 00:00:23,900
Ana

4
00:00:23,901 --> 00:00:23,994
Anal

5
00:00:23,995 --> 00:00:24,088
Analo

6
00:00:24,089 --> 00:00:24,182
Analog

7
00:00:24,183 --> 00:00:24,275
Analog

8
00:00:24,276 --> 00:00:24,369
Analog o

9
00:00:24,370 --> 00:00:24,463
Analog ou

10
00:00:24,464 --> 00:00:24,557
Analog out

11
00:00:24,558 --> 00:00:24,650
Analog out

12
00:00:24,651 --> 00:00:24,744
Analog out t

13
00:00:24,745 --> 00:00:24,838
Analog out ta

14
00:00:24,839 --> 00:00:24,932
Analog out tab

15
00:00:24,933 --> 00:00:25,025
Analog out tab:

16
00:00:25,026 --> 00:00:25,526
Analog out tab:

17
00:00:25,806 --> 00:00:31,583
In the beginning of this video, we close the “Measurement View” window and change the size of other windows.

18
00:00:31,615 --> 00:00:40,359
In “State Type” section, the type of “State” is selected from the “State Type” dropdown field and in the “State Name” field a name (Vebko) is selected for the “State”.

19
00:00:40,384 --> 00:00:47,288
In “Set Mode and Fault Type” section, the outputs of the device are specified according to parameters and types of faults.

20
00:00:47,313 --> 00:00:53,844
For example, in “Direct” mode, the output voltage and current of the device are determined directly but in “Line-Line” mode,

21
00:00:53,869 --> 00:00:58,516
the user specifies values of the line voltage and the zero sequence voltage,

22
00:00:58,564 --> 00:01:03,669
and the device produces the output voltage and current values in accordance with those other values.

23
00:01:03,694 --> 00:01:11,909
It should be noted that in this video, the instruction is done in “Direct” mode and descriptions about different “Set Modes” will be provided in future videos.

24
00:01:11,934 --> 00:01:13,487
In “Binary Outputs” box,

25
00:01:13,512 --> 00:01:21,181
the state of binary Outputs of the device are specified where the user can enable or disable any binary according to the condition of the test.

26
00:01:21,206 --> 00:01:27,292
Moreover, from the “Binary Out” tab the user can adjust the settings related to binary Outputs in more details.

27
00:01:27,317 --> 00:01:33,831
In “Binary Inputs” section, the state of active binaries of the device and the reception time of contact is specified.

28
00:01:33,856 --> 00:01:35,292
“Trigger setting” section

29
00:01:35,317 --> 00:01:38,751
In “Comment” field, the user can add a note about the current “State”.

30
00:01:38,776 --> 00:01:42,384
This note is, also, viewable from the “Table View” window, “Comment” field.

31
00:01:42,409 --> 00:01:44,078
In “State Termination” section,

32
00:01:44,103 --> 00:01:49,774
the user determines the conditions for termination of the current “State” and initiation of the next “State”.

33
00:01:49,799 --> 00:01:56,561
In “Timeout” field, the signal injection time is determined by the user and after that the test ends or goes to the next “State”.

34
00:01:56,625 --> 00:02:04,131
If the user wishes to specify conditions to terminate the current “State” according to reception of “PickUp” and “Trip” signals from the relay,

35
00:02:04,156 --> 00:02:09,266
they need to use the “Use binary trigger condition as specified below” option.

36
00:02:09,291 --> 00:02:15,678
To do this, first, the needed binaries should be enabled from the “Hardware Configuration” page.

37
00:02:17,837 --> 00:02:20,594
Then, in “Binary Trigger Condition” section,

38
00:02:20,634 --> 00:02:25,421
the condition of each binary for terminating the current “State” is specified.

39
00:02:25,446 --> 00:02:30,906
The conditions that the user can use are mentioned in the slide bar in front of each contact.

40
00:02:30,931 --> 00:02:34,195
when “0”, no contact has been received by the binary.

41
00:02:34,220 --> 00:02:38,061
when “1”, the binary, has received “Pick Up” or “Trip” contact.

42
00:02:38,086 --> 00:02:44,815
when “0 -> 1”, the binary is first in “0” condition (no contact received) and then “Pick up” or “Trip” contact is received.

43
00:02:44,840 --> 00:02:49,099
In this condition, it is necessary for the binary to detect “0” to “1” signal.

44
00:02:49,124 --> 00:02:55,582
when “1 -> 0”, the binary is, at first, in condition “1” (contact received) and then the contact is removed from the binary.

45
00:02:55,607 --> 00:02:59,833
In this condition, it is necessary for the binary to detect “1” to “0” signal.

46
00:02:59,858 --> 00:03:08,145
when “1 -> 0”. “0 -> 1”, if the binary detects any of the conditions “0 -> 1” or “1 -> 0”, the termination command of “State” is made.

47
00:03:08,170 --> 00:03:13,041
Condition “X” means there is no condition determined for “State” termination of this binary.

48
00:03:13,066 --> 00:03:17,562
It should be noted that if more than one condition is determined for “State” termination,

49
00:03:17,587 --> 00:03:25,418
the user needs to choose one logic from “AND” and “OR” logics from the “Trigger Logic” section to apply to the determined conditions.

50
00:03:25,443 --> 00:03:31,588
By using the “AND” logic, to terminate the “State” all conditions should be met while by using “OR” logic,

51
00:03:31,613 --> 00:03:35,094
if any of the conditions is met, the “State” is terminated.

52
00:03:35,119 --> 00:03:41,243
It should be noted that all this setting can be adjusted in “Binary Inputs” box by checking “Trigger Condition”.

53
00:03:41,267 --> 00:03:45,914
In this section in “Detail View” window, by checking “Show Time from this State” option,

54
00:03:45,946 --> 00:03:50,920
the contact reception time origin since the current “State” started is specified.

55
00:03:50,960 --> 00:04:04,337
Also, if you wish only for the last binaries state change to be displayed, check “Show only last change” and select one from among “1”, “0” and “0&1” radio-buttons in accordance with your needs.

56
00:04:04,504 --> 00:04:08,603
“0&1” option displays the last state of zero and one.

57
00:04:08,636 --> 00:04:14,007
It should be reminded that in the default mode of the software, if the binary is open circuited,

58
00:04:14,032 --> 00:04:21,052
, it means that no contact is received and when the two ends of the binary are short circuited it means that contact has been received.

59
00:04:21,106 --> 00:04:28,825
This setting can be adjusted by changing the value of each binary from “True” to “False” in “Reverse” column of the “Hardware Configuration” page.

60
00:04:28,849 --> 00:04:33,306
For example, from the “Hardware Configuration” window and “Binary / Analog Input”,

61
00:04:33,330 --> 00:04:36,745
6 binaries are selected with specific active “Targets”.

62
00:04:36,769 --> 00:04:38,316
Then, in “Trigger” section,

63
00:04:38,340 --> 00:04:48,457
the conditions of the binary are set at "0"، "1"،"1 ˃˗ 0"، 0 ˃˗ 1، 0 ˃˗ 1 . 1 ˃˗ 0 and X and “OR” is selected as the logic between them.

64
00:04:48,481 --> 00:04:50,955
In this case, by fulfilling any of condition,

65
00:04:50,979 --> 00:04:58,323
the current state is terminated but if “AND” logic is selected, all conditions must be fulfilled for the “State” to be terminated.

66
00:04:58,355 --> 00:05:02,542
Note that in “State Termination” section, between “Time Out”,

67
00:05:02,567 --> 00:05:10,477
“Space Key Press” and “Use Binary trigger condition as specified below” there is an “OR” logic and if they are selected simultaneously,

68
00:05:10,501 --> 00:05:14,150
if any of the conditions is fulfilled , the current “State” is terminated.

69
00:05:14,174 --> 00:05:16,376
By using “Trigger Logic Minimum Time”,

70
00:05:16,400 --> 00:05:21,991
the user specifies that how long the determined condition should last for the “State” to be terminated.

71
00:05:22,015 --> 00:05:26,259
It should be noted that this feature only works on conditions “1” and “0”.

72
00:05:26,283 --> 00:05:34,739
In the field related to “Delay after Binary Trigger”, the user makes a delay time between when the condition is fulfilled and when the “State” is terminated.

73
00:05:34,763 --> 00:05:40,207
For example, to simulate key performance delay, if 50 milliseconds is entered in this field,

74
00:05:40,232 --> 00:05:46,115
the current “State” is terminated after a 50 milliseconds delay and the key cutoff time is simulated.

75
00:05:46,140 --> 00:05:50,929
View videos of “Synchronizer Room” to see how “Synchronizer Mode” works.

76
00:05:51,035 --> 00:05:54,048
In “Other Setting” section, by checking “Disable Error Other”,

77
00:05:54,072 --> 00:05:56,953
errors of “Other” type are disabled in the current “State”.

78
00:05:56,977 --> 00:06:00,244
Also, by checking “Disable Error Overvoltage of Binary”,

79
00:06:00,387 --> 00:06:05,847
the “Overvoltage” errors of the analog binary inputs of the device are disabled in the current “State”.

80
00:06:05,871 --> 00:06:16,141
In the "Error/Trigger Overcurrent" box a condition for the software overcurrent error or the termination of the state in case high current extraction is specified.

81
00:06:16,165 --> 00:06:23,451
By selecting "Overcurrent trigger" if the current extracted is more than 2A from the device, current state terminate.

82
00:06:23,475 --> 00:06:31,976
Therefore the software applies the next "state" and if it’s the last "state" the test ends without giving any error message.

83
00:06:32,823 --> 00:06:39,124
In “Overcurrent” section, the user adjusts the settings related to “Overcurrent” error of the outputs of the voltage outputs.

84
00:06:39,148 --> 00:06:44,947
Note that the maximum current of each output is 400 milliamps and 2amps in transient state.

85
00:06:44,971 --> 00:06:48,013
In the field related to “Percent Error Overcurrent”,

86
00:06:48,037 --> 00:06:54,457
the maximum voltage output current is specified in percent and in the field related to “Threshold Error Overcurrent”,

87
00:06:54,481 --> 00:06:59,237
the maximum output current is specified as a number for the “Overcurrent” error.

88
00:06:59,262 --> 00:07:04,184
For example, if in the “Percent Error Overcurrent” field 90 percent is entered,

89
00:07:04,970 --> 00:07:12,421
if the output current of the device reaches to 90 percent of the voltage output current, which is 1.8 amps, the device errors.

90
00:07:12,446 --> 00:07:17,240
Also, if in the “Threshold Error Overcurrent” field, 1 amps  is entered,

91
00:07:17,716 --> 00:07:25,243
as soon as the current drawn from the voltage outputs exceeds 1 amps , the “Overcurrent” error is displayed and the test stops.

92
00:07:25,246 --> 00:07:25,291
“

93
00:07:25,292 --> 00:07:25,338
“D

94
00:07:25,339 --> 00:07:25,384
“Di

95
00:07:25,385 --> 00:07:25,431
“Dis

96
00:07:25,432 --> 00:07:25,477
“Disa

97
00:07:25,478 --> 00:07:25,524
“Disab

98
00:07:25,525 --> 00:07:25,570
“Disabl

99
00:07:25,571 --> 00:07:25,617
“Disable

100
00:07:25,618 --> 00:07:25,663
“Disable

101
00:07:25,664 --> 00:07:25,710
“Disable R

102
00:07:25,711 --> 00:07:25,756
“Disable Re

103
00:07:25,757 --> 00:07:25,803
“Disable Rel

104
00:07:25,804 --> 00:07:25,849
“Disable Rela

105
00:07:25,850 --> 00:07:25,895
“Disable Relay

106
00:07:25,896 --> 00:07:25,942
“Disable Relay”

107
00:07:25,943 --> 00:07:25,988
“Disable Relay”

108
00:07:25,989 --> 00:07:26,035
“Disable Relay” s

109
00:07:26,036 --> 00:07:26,081
“Disable Relay” se

110
00:07:26,082 --> 00:07:26,128
“Disable Relay” sec

111
00:07:26,129 --> 00:07:26,174
“Disable Relay” sect

112
00:07:26,175 --> 00:07:26,221
“Disable Relay” secti

113
00:07:26,222 --> 00:07:26,267
“Disable Relay” sectio

114
00:07:26,268 --> 00:07:26,314
“Disable Relay” section

115
00:07:26,315 --> 00:07:26,360
“Disable Relay” section:

116
00:07:26,361 --> 00:07:26,861
“Disable Relay” section:

117
00:07:26,885 --> 00:07:33,365
Generally, the device works in a way that there are relays embedded behind all current and voltage outputs of the device.

118
00:07:33,389 --> 00:07:37,703
Before the test, all amplifiers of the device are off and all relays are open.

119
00:07:37,727 --> 00:07:41,900
By “Running” the test, the amplifiers turn on in 20 milliseconds, then,

120
00:07:41,924 --> 00:07:49,898
for 20 milliseconds the device produces a 60 volts voltage and 5 amps current and then examines that there is no “Self-calibration” error.

121
00:07:49,922 --> 00:07:56,024
After that, for 20 milliseconds, zero current and voltage are produced behind the current and voltage outputs.

122
00:07:56,048 --> 00:07:58,289
After these steps, the relays close.

123
00:07:58,313 --> 00:08:02,667
Now, after 100 milliseconds, the voltage and current of the test are created.

124
00:08:02,691 --> 00:08:10,245
By doing this before the test, the device is isolated from any outside voltage. Also, the amplifiers are off and the device is silent.

125
00:08:10,269 --> 00:08:13,628
By checking the box next to the title of every output in each “State”,

126
00:08:13,652 --> 00:08:18,512
the related relay opens and no more voltage or current is sent to the outputs.

127
00:08:18,536 --> 00:08:22,499
For example, to test “Magnetic Balance” of the transformer,

128
00:08:22,523 --> 00:08:29,897
it is necessary to open circuit some wiring in some state which it is done by disabling the relay of the related phase in the device.
