﻿1
00:00:23,733 --> 00:00:25,232
“Table View” window

2
00:00:25,280 --> 00:00:30,101
The first step in designing a test is to make different states of the test in “Table View” window.

3
00:00:30,173 --> 00:00:36,330
This means that to simulate fault state, it is necessary to inject signal several stage and receive feedback.

4
00:00:36,441 --> 00:00:43,648
Every stage of the test is showed on this window in form of a table named “state” and each “state” is made of several components.

5
00:00:43,704 --> 00:00:49,188
To open the “Table View” window, it is possible to use “View” menu or the toolbar at the top of the page.

6
00:00:49,212 --> 00:00:58,964
In the first part of every “state”, RMS value, phase and frequency of the outputs of the device, which are selected in “Hardware Configuration” part, are specified.

7
00:00:58,988 --> 00:01:07,657
In the first column of this part, the RMS value of the outputs of the device is specified. The maximum allowed value is determined in “Limits” section in “Test Object” page.

8
00:01:07,722 --> 00:01:14,800
In the second column, the phase of the output signals of the device is specified which can be between 0 to 360 degrees.

9
00:01:14,825 --> 00:01:26,698
Also, in the third column the frequency of the output signals of the device are specified which can be between 0 to 1.5 kHz. If DC signal is needed, the frequency should be specified as 0.

10
00:01:26,754 --> 00:01:33,836
In the “Bin. Out” section, the open/close state of “Binary Outputs” of the device is determined in accordance with the user’s wish.

11
00:01:33,879 --> 00:01:38,803
In the “Trigger” section, the conditions of “state” completion are determined which can be based on time,

12
00:01:38,827 --> 00:01:47,675
by pressing “space” button by the user and, also, based on receiving a specified signal from the relay or a combination of all three of these conditions.

13
00:01:47,684 --> 00:01:50,313
It is necessary to consider these two points:

14
00:01:50,370 --> 00:01:57,932
The first point is that in this section, it is possible to activate the related condition by double-clicking on any of the icons.

15
00:01:57,980 --> 00:02:05,980
To adjust the settings related to the “Inputs” you can do so from “Detail View” window or simply by checking “Trigger Condition” option.

16
00:02:06,005 --> 00:02:09,796
The second point: these conditions have “OR” logic with each other.

17
00:02:09,852 --> 00:02:15,315
This means that if several conditions are met, if one of them is true, the current “state” ends.

18
00:02:15,348 --> 00:02:21,244
In the next section the type of “state” is determined which can be selected from the available drop-down list.

19
00:02:21,300 --> 00:02:24,896
Note that each of these types is described in “Detail View” section.

20
00:02:24,921 --> 00:02:31,665
In “Bin. Input” section, the momentarily receival state of signal on every activated binary inputs is specified.

21
00:02:31,713 --> 00:02:36,763
In the “Comment” section, any important note about each “state” is recorded by the user.

22
00:02:36,788 --> 00:02:41,501
Note that entering information in this section is only possible in “Detail View” page.

23
00:02:41,526 --> 00:02:43,369
Right-click on “Table View” window

24
00:02:43,394 --> 00:02:44,948
RMS value column

25
00:02:44,996 --> 00:02:50,075
By right-clicking on any column of the “Table View” window, a list containing several options opens.

26
00:02:50,100 --> 00:02:53,238
Each of these options is designed for a specific purpose.

27
00:02:53,263 --> 00:02:58,003
After right-clicking on the column related to “RMS” value, by selecting “Nominal Value”,

28
00:02:58,028 --> 00:03:04,328
the amount of current and voltage in each cell is changed to specified nominal values in “Device” block in “Test Object” page

29
00:03:04,353 --> 00:03:08,059
By selecting “Zero” it is possible to set the cell value to zero.

30
00:03:08,092 --> 00:03:13,376
If the user wishes the voltage or current in all three phases to be equal to the selected cell value,

31
00:03:13,448 --> 00:03:16,213
they can select the “Equal Magnitudes” option.

32
00:03:16,277 --> 00:03:21,685
Also by checking “Link Magnitude” option, the values of all three phases will be linked together.

33
00:03:21,734 --> 00:03:27,162
It should be noted that if two groups of voltage or current are activated from “Hardware Configuration”,

34
00:03:27,187 --> 00:03:33,684
you can see that the three phases of group A are linked together while the three phases of Group B are linked together.

35
00:03:33,740 --> 00:03:43,768
To better understand this, enter 2amps as the current for one of the phases of group A and enter 4amps as the current for one of the phases of group B.

36
00:03:44,069 --> 00:03:48,069
The “100% Load” option is used for changing the current to nominal value.

37
00:03:48,094 --> 00:03:55,933
The “50% Load” option is used for changing the current to half of the nominal value and the “Unloaded” option is used for changing the current to zero.

38
00:03:55,958 --> 00:04:00,626
Note that by selecting any of these options, the voltage is changed to the nominal value.

39
00:04:00,634 --> 00:04:06,934
If the user copies the  values of voltage and current by right-clicking in “Vector View” window and selecting “Copy to Clipboard”,

40
00:04:06,967 --> 00:04:13,696
by selecting “Paste From Vector View Clipboard” in “Table View” window they can paste these values in their intended “state”.

41
00:04:13,871 --> 00:04:22,945
Also, by clicking on “L1L2L3->L3L1L2” option, the rotation of the phases as well as their values will change.

42
00:04:23,001 --> 00:04:31,757
“Link to XRio” option enables the user to relate the value of voltage, current, phase or frequency to any desired parameter in “XRio”.

43
00:04:31,790 --> 00:04:37,377
By selecting this option, “Link to XRio” window opens where the desired parameter can be selected.

44
00:04:37,639 --> 00:04:45,162
For example, in the “XRio” tree diagram in “Rio” section, in “Nominal Value” branch in “Device” block, the “In” parameter is selected.

45
00:04:45,209 --> 00:04:54,951
Also, it is possible to multiply the selected parameter by a specific value or add it to a specific value which is, finally, displayed in the box at the bottom.

46
00:04:54,976 --> 00:04:59,061
On the top right of this window it is possible to search a parameter.

47
00:04:59,347 --> 00:05:08,583
By checking “Filter by Sender Unit” on the left, all “XRio” parameters which have the same “unit” with the selected parameter in “Sequencer” are marked.

48
00:05:08,655 --> 00:05:10,833
After linking the intended voltage,

49
00:05:10,793 --> 00:05:17,675
you can see that the selected cell is turned purple which indicates that this cell is linked with a value from the “XRio”.

50
00:05:17,713 --> 00:05:24,841
By selecting “Go to Linked Value”, it is possible to view that the selected parameter in “Sequencer” is linked with which parameter in “XRio”.

51
00:05:24,849 --> 00:05:34,935
If the user does not wish the parameter to be linked with “XRio”, it is possible to remove the link by selecting “Remove Link” option.

52
00:05:34,960 --> 00:05:35,960
Phase column

53
00:05:35,985 --> 00:05:43,987
By right-clicking on this column and selecting “Line Angle”, the angles of the selected voltage or current will equal with angle value of transmission line.

54
00:05:44,012 --> 00:05:48,200
It is possible to view and adjust this value in “Distance” block in “Test Object” page.

55
00:05:48,272 --> 00:05:52,658
By selecting “Zero”, it is possible to set the selected voltage or current to zero.

56
00:05:52,714 --> 00:05:58,036
If the user wishes to have the minimum amount of received current in the beginning of voltage injection,

57
00:05:58,051 --> 00:06:03,151
by selecting "90°" option, the phase of the injected voltage is set to 90 degrees.

58
00:06:03,207 --> 00:06:05,726
Balance Angle” option is selected for each cell,

59
00:06:05,751 --> 00:06:11,891
the related signal is selected as the reference signal and other phases are set at a degree with a 120 degrees,

60
00:06:12,080 --> 00:06:15,152
degree of difference with the reference signal.

61
00:06:15,219 --> 00:06:19,016
The “Reverse Rotation” option does the same in counterclockwise.

62
00:06:19,041 --> 00:06:28,042
This means that if this option is selected for a cell, regardless of its phase value, -120 degrees is Added to the next phase, respectively.

63
00:06:28,127 --> 00:06:34,755
By clicking on “Link angles (Equals)”, the angles of all three phases are equated and if one of them is changed,

64
00:06:34,803 --> 00:06:36,747
the others change accordingly.

65
00:06:36,811 --> 00:06:41,492
Also, the “Link angles (Balance)” option causes that if one of the phases is changed,

66
00:06:41,533 --> 00:06:45,368
the others change with a 120 degree difference.

67
00:06:45,393 --> 00:06:46,058
“Frequency” Column

68
00:06:46,082 --> 00:06:50,019
By selecting the “Nominal Value” from the options available for this column,

69
00:06:50,044 --> 00:06:56,596
the frequency value in each cell is changed to its nominal value in the “Device” block in the “Test Object” page.

70
00:06:56,628 --> 00:07:01,419
By selecting “DC”, the frequency is changed to zero and it is possible to produce “DC” signal.

71
00:07:01,539 --> 00:07:06,750
If the user wishes all the frequency values to be equal, the “Equal Frequency” option can be used.

72
00:07:06,894 --> 00:07:12,311
By selecting this option for any cell, the frequency of other signals is set equal to the selected cell.

73
00:07:12,407 --> 00:07:15,982
"Link Frequency" links all values of the frequencies with each other.

74
00:07:15,998 --> 00:07:18,667
This means that if one of the frequencies is changed,

75
00:07:18,699 --> 00:07:24,547
the other frequencies change the same amount as well and all the signals will always have the same frequency.

76
00:07:24,666 --> 00:07:28,535
If you need signals with different frequencies, you should uncheck this option.

77
00:07:28,899 --> 00:07:30,099
Decaying signal

78
00:07:30,225 --> 00:07:38,225
If you wish to create “DC” decaying signal, after setting the frequency to zero, it is possible to enter the time constant in the phase column.

79
00:07:38,470 --> 00:07:46,489
As you know, the relation of a decaying signal is written as “A*e^(-t*T)”.

80
00:07:46,561 --> 00:07:51,829
In this relation “A” is amplitude while “T” is the opposite of time constant.

81
00:07:51,892 --> 00:07:55,028
This means that the number you enter is the “T”.
