﻿1
00:00:23,520 --> 00:00:26,450
Complementary explanations of “Device” section:

2
00:00:26,481 --> 00:00:30,515
Before talking about the “AMT-Sequencer” room and its features,

3
00:00:30,540 --> 00:00:34,937
because there are items that are related to the “Device Setting” information,

4
00:00:34,962 --> 00:00:39,218
it is necessary to provide some additional information about this section.

5
00:00:39,243 --> 00:00:43,111
At the left of this page, the general information about the relay is entered.

6
00:00:43,136 --> 00:00:50,717
This information includes name of the manufacturer, type of the relay, serial number, installation location etc.

7
00:00:50,742 --> 00:00:59,320
As the type of information in this section indicates, this information is used merely as report and does not affect the test or its results.

8
00:00:59,345 --> 00:01:08,593
But the information at the right which is partly derived from the relay settings can be used as a reference for determining the voltage and current output of the device.

9
00:01:08,618 --> 00:01:16,170
In “Nominal Values” section the information related to nominal frequency and turn ratio of PT and CT are entered.

10
00:01:16,322 --> 00:01:24,933
From the information of this section, the PT secondary voltage is known as nominal voltage while the CT secondary voltage is known as nominal current.

11
00:01:24,957 --> 00:01:33,415
Note that in “Vprimary” and “Vsecondary” section, it is possible to enter the ratio of transformation in line to line or phase.

12
00:01:33,440 --> 00:01:36,365
In “Residual Voltage/Current Factor” section,

13
00:01:36,390 --> 00:01:45,151
the coefficients of residual voltage and current for relays where the residual voltage and current are separated from the input voltage and current are mentioned.

14
00:01:45,176 --> 00:01:49,071
These coefficients are used to calculate VE and IE.

15
00:01:49,096 --> 00:01:56,273
In “Limits” section, the range of maximum output voltage and current of the device are specified and the user can,

16
00:01:56,298 --> 00:02:04,383
according to the type of wiring specified in “Hardware Configuration” section, determine the maximum output voltage and current of the device.

17
00:02:04,408 --> 00:02:08,078
In the “Debounce Time” field In “Debounce/Deglitch Filter” section,

18
00:02:08,103 --> 00:02:14,274
it is specified that every 3 milliseconds, the device examines the signal transmission from the relay.

19
00:02:14,299 --> 00:02:24,261
In “Deglitch Time” section, it is specified that the transferred signal from the relay should be retained for 400 microseconds until the reception of signal is detected.

20
00:02:24,286 --> 00:02:29,718
Note that both of these values can range from 200 to 1.5 microseconds.

21
00:02:29,743 --> 00:02:31,734
By using “Save to template” option,

22
00:02:31,759 --> 00:02:36,102
the information entered in this section is saved in the software as a template

23
00:02:36,127 --> 00:02:40,403
and it is possible to load this template by using the “Load Template” option.

24
00:02:40,428 --> 00:02:51,901
The “Import” option is used when the user wishes to use the settings of this section on another computer  or to be able to recover the settings after cleaning the cache of the software.
