﻿1
00:00:23,093 --> 00:00:27,739
After getting familiar with “Xrio Converter”, it is necessary to, also,

2
00:00:27,764 --> 00:00:32,249
, get familiar with the concept of “Name”, “ID”, “Foregin ID” and “Description”.

3
00:00:32,274 --> 00:00:32,670
"ID"

4
00:00:32,695 --> 00:00:38,613
The relay producer companies define a unique “ID” for every parameter and in all relays of a brand,

5
00:00:38,638 --> 00:00:45,175
this ‘ID” is used for a specific parameter; for example, in the “7UT613” Siemens relay,

6
00:00:45,200 --> 00:00:49,996
“ID=21015” is related to the “PROT.OBJECT” parameter.

7
00:00:50,021 --> 00:00:54,647
This “ID” is used in other relays produced by this company for the same parameter.

8
00:00:54,672 --> 00:01:00,130
Also, in connecting to the relay via Modbus protocol, if this “ID” is sent to the relay as a “Packet”,

9
00:01:00,155 --> 00:01:04,110
the relay will return the parameter value related to the sent “ID”.

10
00:01:04,135 --> 00:01:05,082
‫"Foreign ID"

11
00:01:05,107 --> 00:01:11,720
Unlike “ID” which is used as a standard for identification of the same parameters in relays produced by a company,

12
00:01:11,745 --> 00:01:19,187
“Foreign ID” is used as a means of differentiation between parameters of different relays which allows them to be used in other software’s.

13
00:01:19,212 --> 00:01:30,302
As an example, in “7UT613” relay of Siemens, there is a parameter named “PROT.OBJECT” defined with “ID=21015” and “Foreign ID=0105”.

14
00:01:30,334 --> 00:01:37,529
If the user intends to enter and analyze some models of relays produced by different companies in a software like “Digsilent”,

15
00:01:37,572 --> 00:01:46,143
‫"Foreign ID=0105 means the parameter in "PROT. OBJECT" in relay is "7UT613"

16
00:01:46,187 --> 00:01:50,008
The interesting point is that in some relays such as Siemens, the “ID” and

17
00:01:50,033 --> 00:01:54,838
“Foreign ID” are different while in some other relays such as “P441”,

18
00:01:55,428 --> 00:01:59,985
after loading its file in the “Load XRio and Rio file from list” page,

19
00:02:00,010 --> 00:02:03,309
it can be seen that the “ID” and “Foreign ID” are the same.

20
00:02:03,440 --> 00:02:06,861
Also, in “Name” and “Description” sections there is information,

21
00:02:06,886 --> 00:02:12,673
provided by the producer company, about name of the parameter as well as some description about that parameter.

22
00:02:12,698 --> 00:02:16,389
An introduction to “XRio” and its difference with “XRio Converter”:

23
00:02:16,414 --> 00:02:22,074
By clicking on the “Import from list” icon on the “Load XRio and Rio file from list” page,

24
00:02:22,099 --> 00:02:29,089
“XRio Converter” of a relay is selected where the information regarding the relay is complete in the “Custom” and “Rio” sections.

25
00:02:29,114 --> 00:02:38,563
It should be noted that it is not possible to extract the “XRio Converter” file from a relay because producer companies do not put the file in their relays.

26
00:02:38,588 --> 00:02:44,549
In fact, the relay producer companies never limit their relays to a single tester device such as “Omicron”.

27
00:02:44,574 --> 00:02:48,136
Therefore, instead of the “XRio Converter” file,

28
00:02:48,161 --> 00:02:51,438
the relay producer companies provide a file with

29
00:02:51,463 --> 00:02:59,405
“.CSV” or “.text” format in which information of the “Custom” section along with the values set to the relay can be found.

30
00:02:59,430 --> 00:03:04,512
Upon extensive use of “XRio” which has been created by “Omicron” company,

31
00:03:04,537 --> 00:03:10,518
most relay producers decided to provide their users with “XRio” output files of their relays too.

32
00:03:10,543 --> 00:03:14,390
You should consider that this file is not the same as the “XRio Converter”

33
00:03:14,415 --> 00:03:20,547
file which is designed and written by producers of the tester device and is available in the tester software.

34
00:03:20,572 --> 00:03:27,158
The “XRio” file of the relay contains “Custom” section as well as “Relay Parameter Section” and “Additional Information”

35
00:03:27,183 --> 00:03:30,593
blocks with the information and values set to the relay,

36
00:03:30,618 --> 00:03:34,818
but it does not contain “Rio Plus” and “Template Controller” sections.

37
00:03:34,843 --> 00:03:39,248
If, in the tester software, the “XRio Converter” file is selected correctly,

38
00:03:39,273 --> 00:03:43,126
after loading the “XRio” file of the relay in the “XRio Converter”,

39
00:03:43,151 --> 00:03:48,417
the settings and necessary information of the relay are completely imported to the “Rio” section.

40
00:03:48,442 --> 00:03:52,645
Some more points regarding “XRio” and “XRio Converter” should be mentioned:

41
00:03:52,670 --> 00:04:01,104
The first point is that if the “XRio” file of the “7SA522” relay is opened in “notepad++”,

42
00:04:01,129 --> 00:04:05,754
by opening the “Rio Converter” tag it can be seen that unlike “XRio Converter”,

43
00:04:05,779 --> 00:04:08,686
there are no “Script References” functions in this section.

44
00:04:08,711 --> 00:04:16,209
The second point is that in the “Custom” tag, only information regarding “Setting” block is available which is the same as “Relay Parameter Section”

45
00:04:16,234 --> 00:04:23,484
in the software and in some relays such as “7SA522”, the information regarding “Additional Parameter”

46
00:04:23,509 --> 00:04:27,481
is also available which is the same as “Additional Information” in the software.

47
00:04:27,506 --> 00:04:33,954
Also, the information regarding “Device” block has been made available in the “Rio” section by a producer of the relay.

48
00:04:33,979 --> 00:04:42,127
The third point is that if the “XRio” file of a relay is selected and loaded by clicking on “Import from file” and without “XRio Converter”,

49
00:04:42,152 --> 00:04:49,625
it can be seen that the mentioned sections are available in the “XRio” section of the software but because of not using the “XRio Converter”,

50
00:04:49,650 --> 00:04:59,199
the values of “RIO” section are not linked with the “XRio” information and only the “DEVICE” section has been completed according to the information of the “XRIO” file,

51
00:04:59,224 --> 00:05:05,163
and other blocks(like distance) are empty of information because in the “XRio” file of the relay there is no information about them.
