00:00:23,634 --> 00:00:28,916
‪The general settings of the device are adjusted in the “Hardware” tab on the “Preferences” page

2
00:00:28,942 --> 00:00:38,576
‪In the “Fan mode” section, selecting "Silent" will change the speed of the "Fan" depending on the temperature of the switches or heatsinks of the device which is displayed on this page

3
00:00:38,601 --> 00:00:45,059
‪But, if the "Max.Power" option is selected, the fan of the device will work at its maximum power constantly

4
00:00:45,084 --> 00:00:54,784
‪By activating the "Smart Delay" option, if the temperature of the device reaches 55 degrees, in the rooms such as "Distance" and "OverCurrent"

5
00:00:54,998 --> 00:01:02,712
‪where points are used for the test, the test will automatically pause and a message saying "Cooling" will be displayed on the bottom bar of the test screen

6
00:01:02,737 --> 00:01:06,581
‪The test will not resume until the temperature reaches 45 degrees

7
00:01:06,606 --> 00:01:11,557
The maximum operating temperature of the device is specified in the "Maximum Temperature" section.

8
00:01:11,582 --> 00:01:16,640
If the temperature of the device exceeds this value, the device will stop working completely.

9
00:01:16,665 --> 00:01:23,842
This value can be changed up to 70 degrees but,  except for certain conditions, the user must not set the temperature above 60 degrees

10
00:01:23,866 --> 00:01:31,788
In the "Switch Off After Test" section, the user can specify how many seconds after the test is finished, the current and voltage switches should be opened

11
00:01:31,812 --> 00:01:36,692
This number is set to 5 seconds by default but it can be increased up to 10 seconds

12
00:01:36,717 --> 00:01:40,983
In the "Deviation" section, the reporting conditions for “Other” errors can be specified

13
00:01:41,007 --> 00:01:53,900
By default, it is specified in the software that if there is a difference between actual voltage of the device and value specified in the software exceed 4 volts or the current difference goes over 500 mA, the “Other” error should be displayed.

14
00:01:53,924 --> 00:01:59,480
In the "Relative" section, this value is specified as a percentage of the value specified in the test

15
00:01:59,504 --> 00:02:06,013
In the actual operating mode, the device uses the lowest value among these two for the error message.

16
00:02:06,037 --> 00:02:12,269
In the "Binary Input Status" section, it is specified which binary is connected and which binary is not.

17
00:02:12,293 --> 00:02:16,326
In the "Disable Error" section, we can disable possible error of the device

18
00:02:16,350 --> 00:02:23,821
"Select All Error Other":  “Other” error is displayed when the device is unable to produce the current and voltage asked by the user

19
00:02:23,846 --> 00:02:30,572
The cause for this error can be the voltage outputs' short circuting or the current outputs' open-circuting

20
00:02:30,943 --> 00:02:37,424
By opening the drop-down of each errors’ fields, any error can be disabled for a number of voltage and current outputs

21
00:02:37,448 --> 00:02:45,627
"Select All Error Self": every time before running the test, the device checks its internal hardware to determine whether it is capable of

22
00:02:45,651 --> 00:02:57,487
generating +50V or -50V of voltage and +5A and -5A of current، If there is a problem, the device displays a "Self Calibration" error

23
00:02:57,511 --> 00:03:03,693
"Error Thermal": this error is displayed when the temperature of the device's sensors is increased

24
00:03:03,717 --> 00:03:11,735
Occasionally, the thermal sensor of one of the switches has a problem, indicating irrational temperatures such as 800 degrees

25
00:03:11,759 --> 00:03:18,345
In this case, in the slider of this section, it is possible to deactivate the thermal error to continue working with the device

26
00:03:18,369 --> 00:03:24,685
"Error Over Current Binary 9": the binary 9 of the device can measure the current up to 500mA

27
00:03:24,709 --> 00:03:29,535
If the input current of this binary exceeds this value, this error is displayed

28
00:03:29,559 --> 00:03:34,818
"Select All Error Over Voltage Binary": depending on the duration specified for them,

29
00:03:34,842 --> 00:03:40,520
if their input voltage exceeds the specified limit, the binary inputs of the device will display this error

30
00:03:40,544 --> 00:03:49,123
For instance, in the 4.5V mode, if the input voltage of any of the binaries exceeds 4.5V, the device will display this error

31
00:03:49,147 --> 00:03:56,115
In the "Times For ignoring Over Voltage Binary" field, the maximum time allowed to ignore the "Over Voltage" error of the binary is specified

32
00:03:56,147 --> 00:04:04,020
By default, it is set that if the time for the "Over Voltage" error is not shorter than 100 milliseconds, the device will not display any error about this matter

33
00:04:20,452 --> 00:04:25,176
This should be noted that, since "Thermal Error" and "Error Over Current Binary 9" are among the fatal "Errors" of the device, their deactivation setting will not be saved by the software and will be disabled each time the software is run, then if this "Error" needs to be disabled, the user must do this manually.

34
00:04:25,201 --> 00:04:31,846
In the "Repetition" field, the number of times that a series of data are written in the RAM and erased is specified.The "Check RAM" section is used for testing the RAM that is used in the “AMT”.

35
00:04:31,886 --> 00:04:36,693
This section can be used in case of uncertainty about the performance of the device's RAM.

36
00:04:37,037 --> 00:04:42,131
Since the writing and reading operations are performed on the RAM multiple times, eventually

37
00:04:42,156 --> 00:04:47,371
if there is a problem in this process, the error light on the panel of the device will turn on

38
00:04:47,396 --> 00:04:52,046
In the "Earth" section, it is possible to enable or disable the "Earth" error of the device

39
00:04:52,071 --> 00:04:57,662
If the "Enable" option is checked, it is necessary to connect the "Earth" cable to perform the test

40
00:04:57,687 --> 00:05:01,896
 Otherwise, an “Earth” error will be displayed and the device will stop working

41
00:05:01,921 --> 00:05:07,167
This error can be deactivated by unchecking the “Enable” option. But, it is vital to note that,

42
00:05:07,192 --> 00:05:16,013
doing so during the test can be lethal and as it is ,also, stated in the displayed message, Vebko company will not be responsible.

43
00:05:16,038 --> 00:05:21,537
It is possible to activate or deactivate the main hardware switches of the device in the “Switches” section

44
00:05:21,562 --> 00:05:26,472
The switch number 1 is related to the voltages and currents of the group A output

45
00:05:26,497 --> 00:05:30,857
The switch number 2 is related to the voltages and currents of the group B output

46
00:05:30,882 --> 00:05:35,893
By deactivating every switch, all outputs of that switch will be deactivated

47
00:05:35,918 --> 00:05:44,484
In the "Combination Cable" section, if the "Voltage" option is selected, the outputs of the Neutrik cable will include three current and three voltage phases

48
00:05:44,509 --> 00:05:54,679
But if the "Current" option is selected, the output of the cable will consist of two three-phase current groups which are used for various tests such as differential test

49
00:05:54,703 --> 00:06:00,789
The "Open VDC Setting" option is used to enable the DC output voltage of the device

50
00:06:00,813 --> 00:06:04,722
By clicking on this option, the "VDC Diagrams" page opens

51
00:06:04,746 --> 00:06:11,620
On this page, in the "DC Value" field of the "Apply" section, the output DC value of this port is specified

52
00:06:11,644 --> 00:06:15,735
This value can be set up to a maximum of 212V DC

53
00:06:15,759 --> 00:06:23,640
By clicking on the "Apply" option, the "AUX DC" port of the device will inject the amount that is specified in the "DC Value" field

54
00:06:23,665 --> 00:06:28,488
The "AUX DC" output can be disabled by clicking on the "Disable DC" option

55
00:06:28,512 --> 00:06:35,828
By activating the "Record Period" option in the next field, a duration of time is specified for recording the output signal of this port

56
00:06:35,852 --> 00:06:41,542
In the "Now Value" section, the amount of current and voltage produced by the "AUX DC" port is displayed

57
00:06:41,566 --> 00:06:45,720
The "Max Current" field shows the maximum current taken from this port

58
00:06:45,744 --> 00:06:51,892
In the following two diagrams, the instantaneous amounts of voltage and DC current of this port are indicated

59
00:06:51,916 --> 00:06:58,781
It is also possible to save the settings set on this page as a PDF file by clicking on the "Export Report" option

60
00:06:58,805 --> 00:07:07,268
To reset and update the amount of the current displayed in the "Max Current" section, you can click on the "Reset Max Current" option

61
00:07:07,292 --> 00:07:14,338
By checking the "Dancing Light" option, the LEDs in front of the device will turn on in a dancing manner.

62
00:07:14,363 --> 00:07:19,510
This operation is to test the healthy "LED" binary inputs of the device.
