Comparative Analysis of AMT105, AMT205, AMT103, and AMT203 Devices

2
00:00:28,516 --> 00:00:35,626
In this video, we’ll carry out a comparative analysis of the hardware features of several models from Vebco’s product line

3
00:00:35,781 --> 00:00:36,781
Voltage Sources

4
00:00:37,031 --> 00:00:42,265
Starting with the AMT105, this device is equipped with two voltage groups

5
00:00:42,656 --> 00:00:51,484
one three-phase group rated at 150 volts, and one single-phase group also rated at 150 volts.

6
00:00:51,797 --> 00:00:59,687
In total, it provides four 150-volt sources, each capable of delivering up to 500 milliamps per phase

7
00:00:59,844 --> 00:01:08,515
The minimum sampling rate for measuring real-time values in this device is 1.2 milliseconds.

8
00:01:08,906 --> 00:01:16,875
This applies both to the applied voltage and the drawn current, ensuring accurate and timely data acquisition.

9
00:01:17,266 --> 00:01:27,343
Additionally, the AMT105 includes an independent DC voltage source with a maximum output of 212 volts.

10
00:01:27,734 --> 00:01:36,328
This DC source operates separately from the other voltage outputs, allowing for greater flexibility in various testing scenarios.

11
00:01:37,188 --> 00:01:44,922
In contrast, the AMT205 device offers two groups of three-phase 300-volt voltage outputs

12
00:01:45,078 --> 00:01:56,015
each with a maximum amplitude of 1.2 amperes. The sampling rate for measuring actual values is at least 25 microseconds

13
00:01:56,328 --> 00:02:03,203
which applies to both the supplied voltage and the drawn current. These voltage sources

14
00:02:03,553 --> 00:02:14,881
can be converted into 1.2-ampere current sources, capable of providing up to 300 volts of electrical potential for current injection

15
00:02:15,115 --> 00:02:25,193
This feature enables the device to inject extremely small currents — as low as 20 microamperes — with high precision

16
00:02:25,506 --> 00:02:31,990
The device does not include a separate DC source, so if a DC source is required

17
00:02:32,459 --> 00:02:36,286
, the user must dedicate one of the six available phases to that purpose.

18
00:02:36,521 --> 00:02:38,787
Current Sources

19
00:02:39,178 --> 00:02:44,646
The AMT105 device includes two groups of 32-ampere current outputs

20
00:02:44,881 --> 00:02:54,568
each capable of supplying 12 volts per phase. The sampling rate for measuring the actual values from these sources is at least 1.2 milliseconds,

21
00:02:54,803 --> 00:02:57,927
and it is used to monitor the drawn current.

22
00:02:58,162 --> 00:03:04,724

In contrast, the AMT205 device includes two groups of 32-ampere current outputs

23
00:03:05,271 --> 00:03:12,536
each capable of supplying 22 volts per phase. The sampling rate for measuring actual values

24
00:03:12,771 --> 00:03:22,068
values from these sources is at least 25 microseconds, and is used to monitor both the injected current and the voltage supplied by the device

25
00:03:22,615 --> 00:03:31,286
These current sources can be converted into 22-volt voltage sources with a maximum current of 32 amperes.

26
00:03:31,599 --> 00:03:40,193
This feature allows the device to apply very small voltages — as low as 40 microvolts — with high precision.

27
00:03:40,506 --> 00:03:47,849
The Neutrik port on the AMT105 device provides three-phase voltage and three-phase current outputs

28
00:03:48,083 --> 00:03:53,083
 for use in impedance and directional testing. It can also

29
00:03:53,474 --> 00:03:58,318
be reconfigured into six current phases for differential testing.

30
00:03:58,474 --> 00:04:05,505
However, on the AMT205 device, the Neutrik port provides only three-phase voltage

31
00:04:05,818 --> 00:04:12,693
and three-phase current outputs for impedance and directional testing, and does not support reconfiguration.

32
00:04:13,021 --> 00:04:21,224
The AMT105 device includes eight binary/analog inputs, which can operate in either DRY (binary) mode

33
00:04:21,459 --> 00:04:32,552
 or WET (analog) mode. In analog mode, the device supports three input voltage ranges: 4.5 volts, 30 volts, and 188 volts.

34
00:04:34,349 --> 00:04:40,130
The sampling rate for measuring values can be selected starting from 400 microseconds

35
00:04:40,443 --> 00:04:47,083
and higher. Naturally, as the measurement range increases, the accuracy tends to decrease.

36
00:04:47,631 --> 00:04:56,380
The AMT205 device also features eight binary inputs, which can operate in both DRY (binary) and WET (analog)modes

37
00:04:57,318 --> 00:05:02,943
. However, unlike the AMT105, in addition to the 4.5-volt

38
00:05:03,099 --> 00:05:09,661
30-volt, and 188-volt ranges, it also includes a 500-volt range.

39
00:05:09,974 --> 00:05:16,224
The sampling rate for measuring values can be selected from 12.5 microseconds and above.

40
00:05:16,537 --> 00:05:22,708
As expected, when the measurement range increases, the accuracy of the measurement tends to decrease

41
00:05:27,787 --> 00:05:38,177
The AMT105 device includes two AC/DC analog inputs: one dedicated solely to current measurement, with a maximum range of 750 milliamperes,

42
00:05:38,568 --> 00:05:45,911
and the other dedicated to voltage measurement, with a maximum range of 400 millivolts.

43
00:05:46,381 --> 00:05:52,240
The sampling rate for measuring values can be selected from 400 microseconds and above.

44
00:05:52,709 --> 00:05:59,974
The AMT205 device also includes two AC/DC analog inputs, but with extended capabilities

45
00:06:00,287 --> 00:06:07,239
For current measurement, it offers four selectable ranges: 250 microamperes, 39 milliamperes

46
00:06:07,474 --> 00:06:12,240
, 750 milliamperes, and 10 amperes

47
00:06:12,786 --> 00:06:16,614
. For voltage measurement, it provides four ranges as well

48
00:06:17,162 --> 00:06:23,255
10 millivolts, 50 millivolts, 120 millivolts, and 400 millivolts.

49
00:06:23,490 --> 00:06:30,052
The sampling rate for measuring values can be selected from 12.5 microseconds and above.

50
00:06:30,521 --> 00:06:36,302
These inputs offer higher precision, especially when measuring smaller signals.

51
00:06:37,865 --> 00:06:43,333
The AMT105 device features four binary outputs with relay switches

52
00:06:43,724 --> 00:06:47,708
, where neither the switch type nor current measurement can be changed.

53
00:06:48,178 --> 00:06:53,802
In contrast, the AMT205 device also includes four binary outputs

54
00:06:54,037 --> 00:07:03,646
, but with the option to select between transistor-types and relay-type switches. The relay type offers higher current capacity

55
00:07:04,427 --> 00:07:13,880
but has a slower switching speed, while the transistor type provides very high switching speed but can handle lower current levels

56
00:07:15,756 --> 00:07:20,677
A key advantage of the AMT205 is that its binary outputs

57
00:07:20,755 --> 00:07:25,364
can measure current, a capability not available in the AMT105.

58
00:07:32,631 --> 00:07:45,443
The AMT205 device can be connected to a laptop via both LAN and Wi-Fi. Thanks to its support for IEC 61850 testing

59
00:07:45,834 --> 00:07:54,740
the device is equipped with three LAN ports, which can be used to create a ring connection between the device and two other IED systems.

60
00:07:55,053 --> 00:08:01,225

The AMT105 device also supports connection via LAN and Wi-Fi, but it does not support

61
00:08:01,693 --> 00:08:07,396
IEC 61850 testing and includes only one LAN port.

62
00:08:10,131 --> 00:08:16,224
The AMT103 device shares the same technical specifications as the AMT105

63
00:08:16,693 --> 00:08:22,474
, with a few key differences: it includes four 150-volt voltage sources

64
00:08:22,883 --> 00:08:28,976
and three 32-ampere current sources, and it does not have an independent DC source.

65
00:08:29,211 --> 00:08:34,289
The number of binary/analog inputs has been reduced from 8 to 4

66
00:08:34,523 --> 00:08:42,257
, and on the Neutrik port, the number of voltage and current sources is fixed at three voltage outputs and three current outputs.

67
00:08:42,648 --> 00:08:49,054
The AMT203 device shares the same technical specifications as the AMT205

68
00:08:49,367 --> 00:08:54,445
with a few key differences: it includes four 300-volt voltage sources

69
00:08:54,680 --> 00:09:00,929
and three 32-ampere current sources. Additionally, the number of binary/analog inputs

70
00:09:01,164 --> 00:09:03,820
has been reduced from 8 to 4.
